Instructions
22 | AN405821998738en-000102 - 118A5495A
© Danfoss | Climate Solutions | 2023.02 | LCA012A024
Note:
1. Electric characteristics are based on the condenser suction air temperature at 32°C, evaporation temperature -10°C and condensing unit inlet superheat degree
10 deg.
2. Figure in [ ] of the minimum wire size shows the maximum wire length (m) with the voltage drop at 2 V.
Electric characteristics for (50Hz)
Item
(Unit)
OP-UPAC015COP04E
Nominal output
(kW)
6.4
Power supply
3P, 380/400/415 V, 50 Hz
Electric characteristics
Power consumption
(kW)
10.54/10.54/10.54
Operation current
(A)
17.4/16.5/15.9
Min. wire size
(mm
2
)
8 mm
2
× 3 [70]
Operation circuit wire size
(mm
2
)
2.0
Earth cable size
(mm
2
)
3.5
Earth leakage breaker
Rated current
(A)
30
Rated sensitivity current
(mA)
30 (Operation time 0.1 sec. or less)
List of external output
Name
Purpose (Factory default)
Specifications
Point of caution
External
input
CNS1(Green)
no use
Non-voltage
contact
(DC12V)
Stops when open.
CNS2(Red)
ON-OFF SW
Valid when short-circuited.
CNS3(Brown)
Compulsory oil return control input
Valid when short-circuited.
Use connectors fixed with
tapes on the outer wall of
the control box.
CNG1(Blue)
Gas cooler fan snow control input
Valid when short-circuited
CNG2(White)
Multistep demand input
Valid when short-circuited.
External
output
CNH(Blue)
Operation output
12 VDC
output
(10 mA)
-
CNY(White)
Error output
-
CN
NZ1, CNZ2
(Red) (Black)
Set with 7-segment (*)
(Molex: Provide 5557-2R, 5556T at site.)
(*)
0
: Operation output
1
: Error output
2
: Compressor ON output
3
: Fan ON output
4
: Oil return operation output
5
: High pressure control output
6
: Compressor operation time (Maintenance time) time-over output
For the default output, see page 28.
3. Signal cable connection procedures for connecting Module controller
• Signal cables use DC 5 V. Never connect wires for 400 V. It trips the protective fuse on the PCB.
-Confirm that it is so arranged that 400 V power will not be applied to signal cables.
-Check the resistance of signal cable terminal board before turning power on . If the resistance is 100Ω, or less, a power cable may be connected to the
signal cable terminal board.
• Communication method is based on RS485.
• Connect signal cable to A, B on the terminal board.
• Signal cables has the polarity. Connect them as shown in fig. 24.
External signal output
Part of operating states can be output from the controller of condensing unit.
1. Alarm signal
:
If the condensing unit stops under abnormal condition, an alarm signal is released.
2. Compressor operation signal
:
Signals of compressor operation and stop can be extracted.
- Extract signals via a relay.
Where the power for the relay contacts is taken from a terminal box, connect the wires as shown by the electric wiring in the next section.