5.Troubleshooting
Diagnosis
Countermeasure
Keep watching
Replace the fan motor
Replace the control PCB
Replace the fan motor
Replace the control PCB
Replace the fan motor
Replace the control PCB
Notes: *2 Refer to resistance on another table (Page 58)
*3 Measurement item Between 1-6 pin of CNFAN connector for control PCB
*4 Speed command voltage 0
~
7.5[V]
*5 Checking by Mente PC or 7-segment
If the same error does not reappear, continue to get data with Mente PC.
Error code
Remote control:
7-segment display:
LED
Green
Red
Keep
flashing
*1
Content
–
E48-1,2 *1
Turn off the unit, connect CNFAN1 & CNFAN2 on control PCB
and turn the unit back on again
Is there DC15V output
for the control PCB?
No
No
Yes
No
Is the fan speed
command same as the
current fan speed?
Is the fan speed
within the normal
command voltage
range?
No
No
A
Y es
Y es
Change CNFAN position on control PCB
(CNFAN1 connect CNFAN2 connector
and CNFAN2 connects on CNFAN1)
Is the faulty fan motor
running?
No
Which is FG signal,
0V
Yes
Y es
No
Y es
5V
Y es
*3
*2
*5
*4
4Is there a short circuit on
the resistance of the fan
motor signal wiring?
Do the
fan motors run?
"0" or "5V "?
Has any anomaly
occurred?
*1
• When fan speed command
is 400min-1 or lower and
overcurrent status is detected
10 times continuously
• When actual fan speed is
100min-1 or lower for 30
seconds (Fan motor is locked.)
• When fan speed command is
400min-1 or lower and over
current status is detected 10
times continuously
• When actual fan speed is 100
min-1 or lower for 30 seconds
All models
• Disconnection of wiring or
loose connection of connector
• Fan motor anomaly
• Control PCB anomaly
• Power PCB anomaly
Condensing
unit
DC fan motor anomaly (2/2)
*1 E48-1:FMO1 / 1-time flash, E48-2:FMO2 / 2-time flash
1. Applicable model
2. Error detection method
4. Presumable cause
3. Condition of error displayed
User Guide | Optyma™ iCO2
© Danfoss | Climate Solutions | 2023.01 | LCA012A030
BC408445719305en-000101 | 59