background image

Instructions

6 | AN293820378892en-000101

© Danfoss | DCS (CC) | 2019.01

• When brazing, protect the valves and all other 

unit components from torch heat damage 

(painted surfaces, gaskets, connecting box).

• Note that it is not necessary to remove com-

pressor shut-off valves for connection to the 

system, hence no need to replace associated 

gaskets. 

• Be sure to connect the required safety and control 

devices onto compressor shut-off valves or fittings.

• In case of oil return through the Schrader fitting 

on the compressor shell, make sure the internal 

valve is removed.

5 - Leak detection

Never use oxygen or dry air in order to avoid the 

risk of fire or explosion.

• Perform a leak detection test on the complete 

system by means of: a dry nitrogen pressure test, 

a mixture of nitrogen and the refrigerant to be 

used in the system, a helium leak test and/or a 

deep vacuum test.

• The test should be long enough in duration to 

ensure the absence of any slow leaks in the sys-

tem.

• Use tools specifically designed for detecting leaks.

• The low side test pressure must not exceed 1.1 

x Ps pressure indicated on the compressor name-

plate.

• For high side test pressure, do not exceed the pres-

sure indicated on the condensing unit nameplate. 

• Whenever the condensing unit is equipped 

with suction and liquid shut-off valves, these 

valves are to remain in the closed position while 

performing the leak test (condensing unit leak 

test already performed in the factory).

• Should a leak be discovered, proceed with re-

pair steps and repeat the leak detection. 

• When a deep vacuum leak detection test is se-

lected, observe the following:

  1) The level to reach is 500 μm Hg.

  2) Wait 30 min.

  3) If pressure increases rapidly, the system is 

not airtight. Locate and repair leaks. Restart the 

vacuum procedure, followed by steps 1, 2, etc.

  4) If pressure increases slowly, the system 

contains moisture inside. Break the vacuum with 

nitrogen gas and restart the vacuum procedure, 

followed by steps 1, 2, etc.

  5) Connect the compressor to the system by 

opening the valves. 

  6) Repeat the vacuum procedure, followed by 

steps 1, 2, etc.

  7) Break the vacuum with nitrogen gas. 

  8) Repeat the vacuum procedure, steps 1, 2; 

a vacuum of 500 μm Hg (0.67 mbar) should be 

reached and maintained for 4 hours. This pres-

sure is to be measured in the refrigeration sys-

tem, and not at the vacuum pump gauge.

 Do not use a megohmeter or apply power to the 

compressor while it is under vacuum, as this may 

cause motor winding damage (motor burn-out).

 Do not use colored leak detection fluids. Do 

not use chlorofluorocarbon in leak testing sys-

tems designed for HFC fluids.

6 - Vacuum dehydration procedure

Whenever possible (if shut-off valves are pre-

sent), the condensing unit must be isolated from 

the circuit. It is essential to connect the vacuum 

pump to both the LP & HP sides, in order to avoid 

dead-ending system parts.

Recommended procedure:

  1) Once leak detection has been completed,

  2) Pull down the system under a vacuum of 

500 μm Hg (0.67 mbar).

  3) When the vacuum level of 500 μm Hg has 

been reached, the system must be isolated from 

the pump.

  4) A vacuum of 500 μm Hg (0.67 mbar) has 

to be reached and maintained for 4 hours. This 

pressure is to be measured in the refrigeration 

system, and not at the vacuum pump gauge.

If pressure increases, restart the leak-detection 

procedure (refer to the «Leak detection» section 

of this manual if necessary).

Vacuum pump:

A two-stage vacuum pump with gas ballast 

valve (0,04-mbar standing vacuum) shall be 

used; its capacity is to be consistent with system 

volume. 

Never use the compressor as a vacuum pump. It 

is recommended to use large-diameter connec-

tion lines and to connect these lines to the shut-

off valves, rather than to the Schrader connec-

tion.

This recommendation allows avoiding excessive 

pressure losses.

Moisture level:

At the time of commissioning, system moisture 

content may be as high as 100 ppm. During ope-

ration, the liquid line filter dryer must reduce this 

level to < 20 ppm.

Additional notes:

• To improve moisture removal, the temperature 

of the system should not be lower than 10°C.

• A proper vacuum procedure is even more im-

portant with HFC and polyolester lubricant than 

it has “traditionally” been with HCFC (R22) or CFC 

and mineral oil.

• For further details, please refer to TI 3-026.

 Do not use a megohmeter or apply power to 

the compressor while it is under vacuum, as this 

may cause motor winding damage (motor burn-

out).

7 - Electrical connections

• Make sure the main power supply to the sys-

tem has been switched off and isolated, in ac-

cordance with applicable regulations, before 

performing

any electrical connection.

• Please refer to Figs 5 and 6 for typical wiring 

connections and examine the specific wiring 

diagram located in the electrical box cover.

For further details, refer to the condensing unit 

guidelines.

• Note that Maneurop® compressors fitted on 

condensing units are protected against overhea-

ting and overloading by an internal safety motor 

protector. However, an external manual reset 

overload is recommended for protecting the cir-

cuit against over-current.

• The “must trip” value of this overload relay must 

be set in accordance with power line sizing and 

design and shall never exceed the “A max.” value 

stamped on the nameplate.

• On units equipped with an electrical box, all 

electrical connections (condenser fan motor, 

compressor motor, pressure control switch, 

crankcase heater, etc.) have already been wired at 

the factory. For single-phase compressors, start-

and-run capacitors are included in the connec-

ting box.

• The connecting box is equipped with screw type 

terminal blocks, for both power and control lines as 

well as earth terminals for grounding connections.

• All electrical components must be selected as 

per local standards and condensing unit compo-

nent requirements.

8 - Filling the system

• Before charging the refrigerant, verify that the 

oil level is between 1/4 and 3/4 on the com-

pressor oil sight glass and/or ensure that the oil 

charge of the original compressor is sufficient as 

regards system dimension and piping design:

  - An additional quantity of oil might be neces-

sary for line lengths (back and forth) in excess of 

20 m.

  - In the event additional oil is required, use 

only an approved lubricant (refer to the «Intro-

duction» section of this manual).

• Make sure the refrigerant used to fill the system 

is compatible with compressor design. Refer to 

the 

«Introduction»

 section of this manual for an 

approved list of refrigerants.

• Compressor switched off: the liquid refrigerant 

is charged into the condenser and/or liquid re-

ceiver in the liquid phase (compulsory for refri-

gerant blends).The charge must be asclose to 

the nominal system charge as possible in order 

to avoid both low pressure operations and ex-

cessive superheating at start-up. Throughout 

this operation, both compressor service valves 

must remain closed.

• Remember that vapor-charging is only appro-

priate for pure refrigerants, such as R22.

• To the extent possible, maintain the refrigerant 

charge below 2.5 kg per cylinder. Above this li-

mit, install a system, such as a pump-down cycle 

or suction line accumulator, to prevent against 

liquid flood-back into the compressor.

• Be sure that the refrigerant charge is suitable 

for both winter and summer operations.

9 - Verification before commissioning

 Ensure that all service valves are in the open 

position before start-up. A closed discharge or 

suction service valve may cause serious damage 

to the compressor and/or compromise safety 

device operation, thereby resulting in potential 

injury to personnel.

Содержание Optyma Blue OP-LGHE068NTA07D

Страница 1: ...TA07D 114X8060 OP LGHE215NTA07D 114X8048 OP LGHE271NTA07D 114X8061 OP MGZE038MTA07G R404A R507 R134a 114X8062 OP MGZE048MTA07D 114X8063 OP MGZE060MTA07D 114X8064 OP MGZE086MTA07D 114X8065 OP MGZE108MT...

Страница 2: ...temperature C MGZE MTZ MBP Models R134a SH10K Wiring Diagram WD1 MGZE MTZ MBP Models R404A 507 SH10K 15 25 20 35 30 45 40 50 55 35 30 25 20 15 10 5 0 5 40 45 15 25 20 35 30 45 40 50 55 25 20 15 10 5 0...

Страница 3: ...3P 50Hz D 50Hz Voltage range 3 Phases 342V 440V G 220V 240V 1P 50 Hz Compressor 230V 1P 50Hz Fan 230V 1P 50Hz G 50Hz Voltage range 1 Phase 200V 264V D 380V 415V 3P 50 HZ Compressor 415V 3P 50Hz Fan 4...

Страница 4: ...Instructions 4 AN293820378892en 000101 Danfoss DCS CC 2019 01 For R404A models HP bar LP bar MBP 28 8 LBP 28 3 Factory setting...

Страница 5: ...rosive flammable atmosphere 3 Safety measures prior to assembly All installation and servicing is to be performed by qualified personnel in compliance with all pertinent practices and safety procedure...

Страница 6: ...r than to the Schrader connec tion This recommendation allows avoiding excessive pressure losses Moisture level At the time of commissioning system moisture content may be as high as 100 ppm During op...

Страница 7: ...filter dryer expansion valve etc refrigerant charge Low refrigerant charge the correct refrige rant charge is given by the liquid sight glass indication the condenser delta T in relation to the refrig...

Страница 8: ...cut the compressor shell and adjacent tubing release of liquid refrigerant can cause flash freezing on exposed skin Even though fans are fitted with safety guard it is recommended not to work on conde...

Отзывы: