WARNING

DISCHARGE TIME

The frequency converter contains DC-link capacitors, which
can remain charged even when the frequency converter is
not powered. High voltage can be present even when the
warning LED indicator lights are off. Failure to wait the
specified time after power has been removed before
performing service or repair work can result in death or
serious injury.

Stop motor.

Disconnect AC mains and remote DC-link power
supplies, including battery back-ups, UPS, and DC-
link connections to other frequency converters.

Disconnect or lock PM motor.

Wait for the capacitors to discharge fully. The
minimum duration of waiting time is specified in

Table 1.2

.

Before performing any service or repair work, use
an appropriate voltage measuring device to make
sure that the capacitors are fully discharged.

Voltage

[V]

Frequency converter

model

Minimum waiting

time

(minutes)

3x400

N110–N315

20

N90K–N250

20

3x690

N75K–N400

20

N55K–N315

20

Table 1.2 Discharge Time

1.4 Installation

1.4.1 Installing the Top Plate

1.

Along the back side of the top vent opening, remove
the 4 screws (T25).

2.

Place the top plate over the top vent opening.
See 

Illustration 1.2

.

3.

Secure the top plate with the 6 screws without
captive washers provided in the bag. Torque to 2.3
Nm (20 in/lbs).

4.

If lifting eyebolts are needed for the application,
remove the plated eyebolts that came with the unit
and replace with the stainless steel eyebolts provided
in the bag.

NOTICE

UL NEMA 3R RATING

Eyebolts are not required to meet UL NEMA 3R rating.

1

Top  plate

2

Eye  bolt

3

Screw without captive washer

Illustration 1.2 Installing NEMA 3R Top Plate

Installation Instructions

NEMA-3R Cover Kit for D1h–D2h
VLT

®

 FC Series FC 102, FC 103, FC 202, and FC 302

2

Danfoss A/S © 06/2015 All rights reserved.

MI70I102

Содержание NEMA-3R

Страница 1: ...washers For NEMA 3R cover screws 6 without captive washers 1 2 Kit Part Numbers Part number Kit description 176F6302 NEMA 3R cover kit for D1h enclosures 176F6303 NEMA 3R cover kit for D2h enclosures...

Страница 2: ...s are fully discharged Voltage V Frequency converter model Minimum waiting time minutes 3x400 N110 N315 20 N90K N250 20 3x690 N75K N400 20 N55K N315 20 Table 1 2 Discharge Time 1 4 Installation 1 4 1...

Страница 3: ...g with the gasket side facing the opening See Illustration 1 4 4 Secure the new gland plate to the frequency converter using the provided screws with captive washers 6 for D1h or 8 for the D2h Torque...

Страница 4: ...urrent of a frequency converter with the NEMA 3R cover is 90 of its current rating For example in a FC 302N250T5 standard IP54 frequency converter the nominal output current in normal overload mode is...

Страница 5: ...llustration 1 6 Derating for Ambient Temperature Installation Instructions NEMA 3R Cover Kit for D1h D2h VLT FC Series FC 102 FC 103 FC 202 and FC 302 MI70I102 Danfoss A S 06 2015 All rights reserved...

Страница 6: ...Illustration 1 7 Exterior Dimensions for D1h with NEMA 3R Kit Installation Instructions NEMA 3R Cover Kit for D1h D2h VLT FC Series FC 102 FC 103 FC 202 and FC 302 6 Danfoss A S 06 2015 All rights re...

Страница 7: ...ation 1 8 Exterior Dimensions for D2h with NEMA 3R Kit Installation Instructions NEMA 3R Cover Kit for D1h D2h VLT FC Series FC 102 FC 103 FC 202 and FC 302 MI70I102 Danfoss A S 06 2015 All rights res...

Страница 8: ...ucts already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this material are property of the resp...

Отзывы: