Input 10 is the latch reference index input in digital control mode. PCD 1.4 is the latch reference
index input in fieldbus control mode.
Input 1 is the touch probe input.
Input 7 is the reset touch probe input in digital control mode. PCD 1.7 is the reset touch probe
input in fieldbus control mode.
NB!
A delay in the touch probe sensor will make the target position drift. This means the
target position will become larger than stated in parameter 1924. To compensate
for this please specify a delay value in parameter 1903. Only a constant delay can
be compensated for, and not a variable delay.
6. Troubleshooting
MCO351 Positioning Controller
46
MG.33.R1.02 - VLT
®
is a registered Danfoss trademark
6