Danfoss MCD 500 Series Скачать руководство пользователя страница 4

MCD 500 PCB Replacement - Instructions 

 

MCD500 PCB Replacement 

 

MI.17.F1.02  - VLT

®

 is a registered Danfoss trademark 

Page 4/5 

Reconnect the wiring looms. The SCR firing loom 
will align with the relevant number of the 
corresponding phase terminal on the main control 
PCB. Take note of the thermistor wiring (grey/red) 
to the right, and fan wiring (black/red) to the left 
of the board. (The order of the thermistor and fan 

plugs is not critical). 

 

Replace the top plastic, top cover and terminal 
plugs. 

 

4.  Models MCD5-0360C ~ MCD5-1600C  

Remove the top cover and terminal blocks from 
the starter. Undo the 4 x Torx screws holding the 
top plastic.  

 

Tilt the top plastic to the right to expose the wiring 
looms. Label each SCR firing loom with the number 
of the corresponding phase terminal on the main 
control PCB assembly and unplug the SCR firing 
looms. 

Unplug the thermistor, fan and CT wires from the 
LCP and main control PCB assembly. 

 

Undo the 4 x Torx screws from the model PCB 
support bracket and set aside. 

Отзывы: