MCD 500 PCB Replacement - Instructions 

 

MCD500 PCB Replacement 

 

MI.17.F1.02  - VLT

®

 is a registered Danfoss trademark 

Page 2/5 

2.  Models MCD5-0131B ~ MCD5-0215B  

Remove the top cover and terminal blocks from 
the starter. Undo the 4 x Torx screws holding the 
top plastic.   

 

Tilt the top plastic to the right to expose the wiring 
looms. Label each SCR firing loom with the number 
of the corresponding phase terminal on the main 
control PCB, then unplug the looms. 

Unplug the thermistor, fan and CT wires from the 
main control PCB.  

 

Undo the 4 x Torx screws from the model PCB 
support bracket and set aside. 

Remove 4 x Torx screws from the bypass driver 
PCB, slide out to the right and set aside. 

 

Remove 7 x Torx screws from the main control PCB 
and set aside. 

Replace the PCBs, plug in the looms, top plastic, 
top cover and terminal plugs. 