Option
Function
[0]
No
Select
[0] No
to use the 24 V DC supply of the drive.
[1]*
Yes
Select
[1] Yes
if a 24 V DC external supply is used to power the option. Inputs/outputs are galvanically isolated from the
drive when operated from an external supply.
4.5 16-** Data Readouts
4.5.1 16-6* Inputs and Outputs
Table 43: Parameter 16-60 Digital Input
Range
Function
0*
[0–63]
View the signal states from the active digital inputs. Example: Input 18 corresponds to bit number 5; 0 = no signal; 1
= connected signal. Bit 6 works in the opposite way; 0 = on; 1 = off (safe stop input).
Bit 0
Digital input term. 33
Bit 1
Digital input term. 32
Bit 2
Digital input term. 29
Bit 3
Digital input term. 27
Bit 4
Digital input term. 19
Bit 5
Digital input term. 18
Bit 6
Digital input term. 37
Bit 7
Digital input GP I/O term. X30/4
Bit 8
Digital input GP I/O term. X30/3
Bit 9
Digital input GP I/O term. C30/2
Bits 10–63
Reserved for future terminals.
Parameter Setup
Operating Guide | VLT® Extended Relay Card MCB 113
AQ322553864968en-000101 / 130R0353| 47