Danfoss Link Hydronic Controller Скачать руководство пользователя страница 5

Installation Guide  Danfoss Link™ HC

6

06/2013 

VIFZL402 

        Danfoss Heating Solutions 

4.5 

Input for Heating and Cooling

• 

Connect an external ON/OFF switch to the terminals for Heating and Cooling (Input 3)  

 

(fig. 13). With the switch closed (ON), the system will switch from heating to cooling   

 mode. 

• 

Fix the cable (fig. 14).

Note! 

With the system in cooling mode, the actuator output will be activated (ON for NC actua-

tors/OFF for NO actuators), when the temperature in a room exceeds the set point.

When the system is in cooling mode a dew-point sensor should be installed.

4.6 

Wiring

L N

9

10

8

7

5

4

3

2

1

230 V~

50 Hz

L N

4.7 

Power Supply

!

Connect all actuators (TWA), before mains powering the unit!

Then, connect the Danfoss Link™ HC power supply plug to a 230 V power supply, when all 

actuators, pump and boiler controls and other inputs are installed. The Danfoss Link™ HC is 

now ready to be added to the Danfoss Link™ CC.

Note! 

If the power supply plug is removed from the power supply cable during installation, 

ensure that the connection is made according to existing law/legislation.

4.8 

CF-EA External Antenna

The CF-EA is installed as diverter when there is no transmission possible through a large 

building, heavy construction or metal barrier, e.g. if the Danfoss Link™ HC is located in a 

metal cabinet/box.

• 

Remove the plastic cover from the antenna connection on the Danfoss Link™ HC              

 

(fig. 15).

• 

Connect the CF-EA (fig. 16).

• 

Place the CF-EA on the other side of the transmission barrier away from the                  

 

Danfoss Link™ HC. 

5.  Configuration

5.1 

Adding Danfoss Link™ HC to the system

Note!

 Adding Danfoss Link

 HC to a system is made from the Danfoss Link

 CC. 

For further information, see separate instruction.

• 

Remove the front cover of the Danfoss Link™ CC by   

 

gently pulling it off, pull near the edges of the cover. 

• 

Press the 

SETUP

 pin for 3 seconds to enter the service  

 area.

Important!

• 

The Danfoss Link™ HC must be added to the network as a 

service device

. For further    

  instructions on network inclusion, see more information in the Danfoss Link™ CC  

 

  Installation Guide.

• 

Add any dedicated repeater units (CF-RU) BEFORE adding the Danfoss Link™ HC to the    

  wireless network.

Input

Relays

Actuator outputs

External 

antenna

Input 1
Input 2
Input 3

Max. 3 m

Содержание Link Hydronic Controller

Страница 1: ...VIFZL402 Danfoss A S Indoor Climate Solutions Ulvehavevej 61 7100 Vejle Denmark Phone 45 7488 8500 Fax 45 7488 8501 Email heating solutions danfoss com www heating danfoss com Installation Guide Danfo...

Страница 2: ...5 4 5 Input for Heating and Cooling 6 4 6 Wiring 6 4 7 Power Supply 6 4 8 CF EA External Antenna 6 5 Configuration 6 5 1 Adding Danfoss Link HC to the system 6 5 2 Configuring Danfoss Link HC 7 5 3 Cr...

Страница 3: ...Pump relay Actuator connections Install Link Test External antenna connection Front cover release Not in use Input 1 Away Function Input 2 external ON OFF switch Input for heating cooling Input 3 exte...

Страница 4: ...Mount DIN rail parts fig 4 Click on DIN rail fig 5 Release from DIN rail fig 6 Important Complete all the installations on the Danfoss Link HC as described below before connecting to a 230 V power su...

Страница 5: ...the connection is made according to existing law legislation 4 8 CF EA External Antenna The CF EA is installed as diverter when there is no transmission possible through a large building heavy constr...

Страница 6: ...s made from the Danfoss Link CC For further information see separate instruction 1 2 3 Configuring outputs 1 2 3 Configuring inputs 1 2 3 Service Options Rooms and Devices Rooms and Devices Manage Dev...

Страница 7: ...5 5 Configuring a room 1 2 Forecasting method By activation of the fore cast method the system will automatically predict the heating start up time necessary to reach desired room temperature at de si...

Страница 8: ...etwork test is running smoothly there will be no need for further interaction If the network test is per forming slow the Danfoss Link CC guides through troubleshooting and gives useful tips for speed...

Страница 9: ...emperature 0 50 C IP class 30 8 Troubleshooting Error indication Possible Causes Impossible to add devices to the Danfoss Link CC system The distance between the Danfoss Link CC and the Danfoss Link H...

Страница 10: ...Installation Guide Danfoss Link HC Danfoss Heating Solutions VIFZL402 06 2013 11...

Страница 11: ...Guide Danfoss Link HC 12 06 2013 VIFZL402 Danfoss Heating Solutions A1 Fig 1 Fig 2 Fig 3 Danfoss Link HC Danfoss Link RS Danfoss Link HC Danfoss Link CC Danfoss Link CC Metal Metal Danfoss Link RS Dan...

Страница 12: ...Installation Guide Danfoss Link HC Danfoss Heating Solutions VIFZL402 06 2013 13 A2 Fig 4 Fig 5 Fig 6 Fig 7 Fig 8 Fig 9 Fig 10 Fig 11 Fig 12 Fig 13 Fig 14 Fig 15 Fig 16...

Страница 13: ...VIFZL402 Danfoss A S Indoor Climate Solutions Ulvehavevej 61 7100 Vejle Denmark Phone 45 7488 8500 Fax 45 7488 8501 Email heating solutions danfoss com www heating danfoss com Installation Guide Danfo...

Отзывы: