4. Mounting and Installation Procedure (Sequential)
The wireless systems transmission range is sufficient for most applications; however, wire-
less signals are weakened on the way from the Danfoss Link™ to the Room Thermostats
and each building has different obstacles.
Checklist for optimal installation and best wireless signal strength (fig. 1):
•
No metal objects between the Danfoss Link™ HC and the Room Thermostats.
•
Wireless signal through walls on shortest possible diagonal distance.
•
Optimise the wireless signal by installing a RU Repeater Unit.
Note!
Danfoss recommends that an installation plan is made before beginning the actual
installation (fig. 1).
4.1
Danfoss Link™ HC
Mount the Danfoss Link™ HC in an horizontal upright position.
Wall:
•
Remove the front and side covers (fig. 3).
•
Mount with screws and wall plugs (fig. 3).
DIN-Rail:
•
Mount DIN-rail parts (fig. 4).
•
Click on DIN-rail (fig. 5).
•
Release from DIN-rail (fig. 6).
Important!
Complete all the installations on the Danfoss Link
™
HC as described below, before
connecting to a 230 V power supply!
4.2
24 V Actuators
•
Connect the two actuator wires to an output (fig. 7).
•
Fix the cable (fig. 8).
Note!
If NC (normally closed) actuators are installed for ON/OFF regulation, no further actuator
output configuration is needed.
4.3
Relays for Pump and Boiler Control
•
Connect wires for pump and boiler controls to their respective output (fig. 9).
•
Fix the cable (fig. 10).
Note!
The relays for pump and boiler are potential free contacts and can therefore NOT be used
as direct power supply. Max. load is 230 V and 8 A/2 A!
4.4
Input for Away Function
•
Connect an external ON/OFF switch to the terminals for Away Function (Input 2). When
this switch is closed (ON) the system will override all room thermostat set points and
change the temperature to 15 °C (fig. 11).
•
Fix the cable (fig. 12).
Note!
The Away Function ensures a set room temperature fixed at 15 °C for all room thermo-
stats, but it can be changed with the Danfoss Link
™
CC.