DKRCC.PI.CD0.F1.22 / 520H6076  

© Danfoss A/S (AC-MCI / jmn), 2012-12

IMPORTANT: 

The scale plate is only for reference  

and for more precise setting  

a pressure gauge should be used.

IMPORTANT: 

After installing and adjusting pressure control run  

the controlled equipment several times 

(at least three cycles) at normal operating conditions.

Adjustment:  

Low Pressure Control 

Cut out on pressure fall  

with automatic reset.

Scale plate directly indicates  

the Cut In and the Differential  

set points.

1. 

Set Cut In by adjusting range screw.  

Turn the screw clockwise to lower the set point.

2.

 Then set Differential by adjusting differential screw. 

Turn the screw clockwise to increase the Differential.

3. 

The Cut Out setting equals the Cut In  

less the Differential: CUT OUT = CUT IN - DIFFERENTIAL

NOTE: 

Cut Out set point must be above absolute vacuum!  

If the Differential is set too high then the control  

will not stop the compressor. 

Adjustment:  

Condenser Fan Cycling

Scale plate directly indicates  

the Cut In and the Differential  

set points.

1. 

Set Cut In by adjusting range screw.  

Turn the screw clockwise to lower the set point.

2.

 Then set Differential by adjusting differential screw. 

Turn the screw clockwise to increase the Differential.

3.

The Cut Out setting equals the Cut In less  

the Differential: CUT OUT = CUT IN - DIFFERENTIAL

Adjustment:  

Low Pressure Control 

Cut out on pressure fall  

with manual reset.

Scale plate directly indicates the Cut 

Out set point. There is no

pointer for the Differential.

The Differential pressure value is fixed 

and printed on the scale plate.

1. 

Set Cut Out by adjusting range screw.  

Turn the screw clockwise to lower the set point.

2.

 The Cut In setting equals the Cut Out plus  

the Differential: CUT IN = CUT OUT + 10 psi

Adjustment:  

High Pressure Control 

Cut Out on pressure  

rise with automatic reset.

Scale plate directly indicates  

the Cut Out and the Differential  

set points.

1. 

Set Cut Out by adjusting range screw.  

Turn the screw clockwise to lower the set point.

2.

 Then set Differential by adjusting differential screw. 

Turn the screw clockwise to decrease the Differential.

3. 

The Cut In setting equals the Cut Out  

less the Differential: CUT IN = CUT OUT - DIFFERENTIAL

Adjustment:  

High Pressure Control

Cut Out on pressure  

rise with manual reset.

Scale plate directly indicates  

the Cut Out set point.

There is no pointer for the Differential.

The Differential pressure value is fixed 

and printed on the scale plate.

1. 

Set Cut Out by adjusting range screw.  

Turn the screw clockwise to lower the set point.

2.

 The Cut In setting equals the Cut Out  

less the Differential: CUT IN = CUT OUT - 60 psi

Содержание KPU 1

Страница 1: ...always be located on the top side of the refrigerant line This reduces the possibility of oil liquids or sediment collecting in the bellows which could cause the control malfunction IMPORTANT Ensure the ambient temperature for the pressure control is higher than the refrigeration line as that will prevent liquid migration and accumulation in the bellows Product Specification Application Type Code ...

Страница 2: ...re nut on the pressure control One wrench should support the connector while the second wrench is used to tighten the nut 8 Do not over tighten flare nuts as it may damage the threadscausing leaks 9 Protect the capillary tube from damage caused by vibrations from compressor when the control unit is mounted directly on the compressor the capillary must be secured to the compressor so that everythin...

Страница 3: ...Pg16 screwed cable entry NOTE While operating the manual trip on KPU controls with manual reset it is necessary to push the reset knob NOTE Adjust the pressure control with settings specified by the manufacturer of the controlled quipment Do not exceed the pressure ratings of the controlled equipment or any of its components when checking pressure control operation or operating the controlled equi...

Страница 4: ...e to increase the Differential 3 The Cut Out setting equals the Cut In less the Differential CUT OUT CUT IN DIFFERENTIAL Adjustment Low Pressure Control Cut out on pressure fall with manual reset Scale plate directly indicates the Cut Out set point There is no pointer for the Differential The Differential pressure value is fixed and printed on the scale plate 1 Set Cut Out by adjusting range screw...

Отзывы: