3

Wiring Option A:

– Low Pressure Control Cut Out on pressure fall

– Condenser Fan Cycling

Contact function test (Manual trip)

When the electrical leads are connected the contact function 

can be manually tested regardless of pressure condition in 

the system. The manual trip lever is located in the left side 

of the KPU. It must be operated with fingers only. Do not use 

screwdriver as it will damage the control.

Wiring Option B:

– High Pressure Control Cut Out on pressure rise

Wire dimensions: 10 AWG max.

Cable entry: 

7

/

8

 in. cable entry for ½ in. male pipe thread connection 

(conduit boss) or similar (Pg13.5 or Pg16) screwed cable entry.

NOTE: 

While operating the manual trip on KPU  

controls with manual reset it is necessary  

to push the reset knob.

NOTE: 

Adjust the pressure control with settings specified 

by the manufacturer of the controlled quipment. 

Do not exceed the pressure ratings of the controlled 

equipment or any of its components when checking 

pressure control operation or operating the 

controlled equipment.

Do not adjust pointers beyond the highest or lowest 

indicator marks on the scale plate, as this may cause

inaccurate control operation.

A: 

Manual trip. Press the lever up. USE FINGERS ONLy!

B: 

Manual reset button  

(available only for contols with manual reset function)

C: 

Terminal block

D: 

Grounding screw

A:

 Differential adjusting screw

B: 

Locking plate

C:

 Range adjusting screw

D:

 Cover screw

Adjustment

Before adjustment, loosen the locking plate.

For setting use the Universal Refrigeration Wrench.

Содержание KPU 1

Страница 1: ...always be located on the top side of the refrigerant line This reduces the possibility of oil liquids or sediment collecting in the bellows which could cause the control malfunction IMPORTANT Ensure the ambient temperature for the pressure control is higher than the refrigeration line as that will prevent liquid migration and accumulation in the bellows Product Specification Application Type Code ...

Страница 2: ...re nut on the pressure control One wrench should support the connector while the second wrench is used to tighten the nut 8 Do not over tighten flare nuts as it may damage the threadscausing leaks 9 Protect the capillary tube from damage caused by vibrations from compressor when the control unit is mounted directly on the compressor the capillary must be secured to the compressor so that everythin...

Страница 3: ...Pg16 screwed cable entry NOTE While operating the manual trip on KPU controls with manual reset it is necessary to push the reset knob NOTE Adjust the pressure control with settings specified by the manufacturer of the controlled quipment Do not exceed the pressure ratings of the controlled equipment or any of its components when checking pressure control operation or operating the controlled equi...

Страница 4: ...e to increase the Differential 3 The Cut Out setting equals the Cut In less the Differential CUT OUT CUT IN DIFFERENTIAL Adjustment Low Pressure Control Cut out on pressure fall with manual reset Scale plate directly indicates the Cut Out set point There is no pointer for the Differential The Differential pressure value is fixed and printed on the scale plate 1 Set Cut Out by adjusting range screw...

Отзывы: