© Danfoss | DCS (rm) | 2020.02
Loosen screws 1 (Fig. 6) and remove the front cover. Route the wire through Cable entry 1 (Fig. 7); connect contacts to the corresponding
terminals 2. Connect the earth wire to the corresponding terminal (Fig. 7). Put the protective cover on the switch housing and tighten the
screws 1. Fig. 6. Fasten the temperature housing to a flat surface using the supplied bracket.
When mounted on a wall bracket, the permissible vibration of the switch housing is within the range of 0–1,000 Hz, 4 g. Install the capillary
tube in the air duct, or in any other area where temperature control is required, using the supplied mounting plastic corners. The minimum
length of the capillary tube in thermal contact with a controlled environment is as follows:
1
Danf
os
s
60-601.10
1
2
Danf
os
s
60-600.10
Capillary Tube Length, m
Min. Length |АВ|, m
1
0.2
2
0.25
3
0.28
4
0.35
6
0.43
11.5
0.63
Switch Version
Danf
oss
60-603
Safety Warning
Temperature switches must be used strictly for their intended purpose indicated in the technical documentation. Only personnel who have
studied the design and safety regulations may service the device.
Acceptance and Testing
The products specified in this manual are manufactured, tested and accepted in accordance with the applicable technical documentation of
the manufacturer.
Warranty
The supplying manufacturer guarantees the compliance of KP temperature switches with the technical requirements, provided that the
consumer observes the conditions for handling, storage and operation. The warranty period for the operation and storage of KP temperature
switches is 12 months from the date of shipment from the warehouse of the manufacturer or seller.
Scope of Supply
The scope of supply includes: KP 61 temperature switch, wall bracket with screws, plastic fasteners for the capillary tube with screws, user
guide.
Marking and Packaging
Information on the manufacturer’s trademark, product designation, code number, date of manufacture and main technical characteristics are
provided on the product’s housing and/or packaging.
Maintenance and Service
Product maintenance involves compliance with the regulations for the operation, storage and handling specified in this guide, and routine
inspections that must be carried out in the manner established by the operating facility at least twice a year and must include visual
examination and inspection of its functioning. It is prohibited to operate a damaged or malfunctioning product. For information about
repairs, please contact the Danfoss service department: https://www.danfoss.com/en/contact-us/
Fig. 6
Fig. 7
AN33432347566101-000101 | 3