manualshive.com logo in svg
background image

© Danfoss | DCS (rm) | 2020.02

Operation Principle

When the temperature exceeds the set value (RANGE scale), contacts 

1–4 make and contacts 1–2 break (point I, Fig. 3). The contacts return to 

their initial position when the temperature drops below the value which 

is equal to the set point value (RANGE scale) minus the differential value 

(DIFF scale) (point II, Fig. 3)*.

A

 - set point

B

 - differential

C

 - set point minus differential

1

2

4

1

2

4

1

2

4

A

B

C

Contact Changeover Scheme

Frost Protection

Connect terminals 1 and 4. The switch has the following factory settings: set point (RANGE) 7°C;  differential (DIFF) 2°C. When the temperature 

drops below 5°C, contacts 1–4 break and contacts 1–2 make (signal contacts).  The contacts return to the initial position automatically when 
the temperature rises above 7°C. 

Overheating Protection

Connect terminals 1 and 2. When the temperature exceeds the set value, contacts 1–2 break and contacts 1–4 make (signal contacts). The 

contacts return to the initial position automatically when the temperature drops below the set value minus differential*.

* Please note that the division value of the DIFF scale for differential adjustment does not fully correspond to 1°C over the entire range and 

varies depending on the selected control range. If you need to adjust the temperature switch to switching points other than the factory 

settings, use the nomogram below and the example of settings in Fig. 4.

Setting

1. Using Scale B, determine the desired value for the lower switching 
point of 3°C and draw a straight line up.
2. Using Scale A, determine the upper switching point. In this example, 
it is 8°C. Set this value on the RANGE scale (set point). Draw a horizontal 
line on the nomogram to determine the differential value.
3. The intersection point of the differential curves determines its value 
on the scale of the device. In this case, the lines intersect on the curve 
corresponding to the mark “6” on the differential scale. Set this value on 
the DIFF scale.

Example

The device needs to be activated when  the temperature drops below 3°C. When the temperature rises to 8°C, the contacts must return to 

their initial position.

Important
Temperature switches are not measuring instruments. If you require high-precision  
temperature control, configure the switch using a certified measuring instrument - 
a thermometer or a temperature sensor.

°C °C

2   4   6   8  10

°C

DIFF

RANGE

Switch Setting Nomogram

Using a screwdriver, loosen Screw 1 and remove Locking plate 2 and Adjustment 
knob 3 (Fig. 5). Adjust the set point (RANGE) and the differential (DIFF) on the 
corresponding scales. Reinstall and secure the Locking plate and Adjustment knob 3 
with Screw 1. (If Locking plate 2 is not removed, a slight change in the setting in the 
range of 3–4°C is allowed).

Danf

os

s

60-602.10

A

B

1

3

2

     

Mounting and Setup Instructions

General safety requirements must be observed when mounting the device.
Mounting may only be performed by qualified personnel in compliance with the 
applicable standards. Do not touch moving parts with your fingers or any tools. 
Mount and adjust the temperature switch in the absence of electrical voltage 
only. The temperature of the switch housing must be at least 2°C higher than the 
sensor temperature.

Increasing

Decreasing

Decreasing

Increasing

Set Point Setting Scale

Differential Setting Scale

A

 - 

set point scale

B

 - 

differential scale

Fig. 3

Fig. 4

Fig. 5

AN33432347566101-000101 | 2

Отзывы: