RI5AK222 - 520H0146 

Manual tripping

 

(Electrical contacts/wiring test)

   

LP side 

HP side

TRIP

use FINGERS
ONLY!
(Do NOT use
screwdriver)

Note:
On controls with LP and/or HP man. reset, push 
corresponding LP and/or HP man. reset knob during 
tripping.

Manual tripping

 

To resume control operation after safety cut-
out, push man. reset knob as indicated.

Note:
LP man. reset is possible only after system 
pressure has risen above cut-in value.

HP man. reset is possible only after system 
pressure has dropped below cut-out value.

Convertible reset

 

KP 15, code nos.: 060-2025, 060-2028

  

Reset options

Turn plate to desired 

LP man. 

LP-auto. 

LP-auto. 

LP-man.

reset confi guration 

HP-man. HP-man.  HP-auto.  HP-auto.

Adjustment spindle(s) location

KP 15 

KP 15, KP 17B 

KP 15, KP 17W, KP 25 

 

A. MAN./MAN. RESET 

B. AUTO/MAN. RESET 

C. AUTO./AUTO. RESET

Содержание KP 15

Страница 1: ...P reset KP 15 KP 17B auto LP man HP reset KP 15 KP 17W KP 25 auto LP auto HP reset Ambient temperatures Test pressure pTEST ptest max 505 psig 35 bar pe ptest max 285 psig 20 bar pe t1 min KP 15 KP 25 40 F 40 C KP 17W KP 17B 13 F 25 C t1 max 150 F 65 C CAUTION Do not mount the control in a position where dirt sediment or oil will affect the operation of the control Enclosure CAUTION The mounting pa...

Страница 2: ...n LP drop See label for current wiring inside cover Controls with low pressure LP and high pressure HP signal KP 15 and KP 17W Only code nos 060 2024060 2027 060 2030 060 2026060 2029 060 2031 stamped on top of control Terminal block CAUTION Use terminal screws furnished in the contact block Use tightening torque 20 lb in 2 3 Nm Use copper wire only Low pressure LP side A C close on LP rise A C op...

Страница 3: ...cut out push man reset knob as indicated Note LP man reset is possible only after system pressure has risen above cut in value HP man reset is possible only after system pressure has dropped below cut out value Convertible reset KP 15 code nos 060 2025 060 2028 Reset options Turn plate to desired LP man LP auto LP auto LP man reset configuration HP man HP man HP auto HP auto Adjustment spindle s lo...

Страница 4: ...TIAL DIFF 2 DIFFERENTIAL DIFF spindle to desired is fixed is fixed DIFFERENTIAL Value printed on Value printed on DIFF value scale plate scale plate CUT IN minus DIFFERENTIAL equals CUT IN equals CUT OUT plus CUT OUT minus DIFFERENTIAL equals CUT OUT DIFFERENTIAL CUT IN Example Example Example CUT IN DIFF CUT OUT CUT OUT DIFF CUT IN CUT OUT DIFF CUT IN 30 psig 10 psi 20 psig 12 psig 10 psi 22 psig 2...

Отзывы: