RI5AK222 - 520H0146

Connections

Wiring

 

CAUTION: Disconnect power supply before 
wiring connections are made to avoid possible 
electrical shock or damage to equipment.

All wiring should conform to the National
Electrical Code and local regulations.

SPDT
Controls with low pressure (LP) signal

Terminal block

CAUTION: Use terminal screws furnished in the 
contact block.
Use tightening torque 20 lb. in (2.3 Nm).
Use copper wire only.

Low pressure (LP) side:
A-C close on LP rise
A-C open on LP drop

High pressure (HP) side.
A-C open on HP rise
A-C close on HP drop

LP signal option:
A-B close on LP drop

See label for current wiring inside cover

 

Controls with low pressure (LP) and high 
pressure (HP) signal)

KP 15 and KP 17W. Only code nos.:
060-2024 060-2027  060-2030
060-2026 060-2029  060-2031
(stamped on top of control)

Terminal block

CAUTION: Use terminal screws furnished in 
the contact block.
Use tightening torque 20 lb. in (2.3 Nm).
Use copper wire only.

Low pressure (LP) side:
A-C close on LP rise
A-C open on LP drop

High pressure (HP) side.
A-C open on HP rise
A-C close on HP drop

LP signal option:
A-B close on LP drop

HP signal option:
A-D close on HP rise

Contact load ratings

See label inside cover

Function

Note!
 

M

 =  Load

 

x

 =  Signal option

   

  =  Bellows movement on pressure rise

 ¬

  =  Bellows movement on pressure  

 

     drop

120 V a.c.

16 FLA, 96 LRA

240 V a.c.

8 FLA, 48 LRA

240 V d.c.

12 W pilot duty

Содержание KP 15

Страница 1: ...P reset KP 15 KP 17B auto LP man HP reset KP 15 KP 17W KP 25 auto LP auto HP reset Ambient temperatures Test pressure pTEST ptest max 505 psig 35 bar pe ptest max 285 psig 20 bar pe t1 min KP 15 KP 25 40 F 40 C KP 17W KP 17B 13 F 25 C t1 max 150 F 65 C CAUTION Do not mount the control in a position where dirt sediment or oil will affect the operation of the control Enclosure CAUTION The mounting pa...

Страница 2: ...n LP drop See label for current wiring inside cover Controls with low pressure LP and high pressure HP signal KP 15 and KP 17W Only code nos 060 2024060 2027 060 2030 060 2026060 2029 060 2031 stamped on top of control Terminal block CAUTION Use terminal screws furnished in the contact block Use tightening torque 20 lb in 2 3 Nm Use copper wire only Low pressure LP side A C close on LP rise A C op...

Страница 3: ...cut out push man reset knob as indicated Note LP man reset is possible only after system pressure has risen above cut in value HP man reset is possible only after system pressure has dropped below cut out value Convertible reset KP 15 code nos 060 2025 060 2028 Reset options Turn plate to desired LP man LP auto LP auto LP man reset configuration HP man HP man HP auto HP auto Adjustment spindle s lo...

Страница 4: ...TIAL DIFF 2 DIFFERENTIAL DIFF spindle to desired is fixed is fixed DIFFERENTIAL Value printed on Value printed on DIFF value scale plate scale plate CUT IN minus DIFFERENTIAL equals CUT IN equals CUT OUT plus CUT OUT minus DIFFERENTIAL equals CUT OUT DIFFERENTIAL CUT IN Example Example Example CUT IN DIFF CUT OUT CUT OUT DIFF CUT IN CUT OUT DIFF CUT IN 30 psig 10 psi 20 psig 12 psig 10 psi 22 psig 2...

Отзывы: