3

TECHNICAL DATA

SPECIFICATIONS

SUPPLY VOLTAGE

9 (minimum) to 32 (maximum) Vdc

SUPPLY CURRENT

0.3 amps, maximum, plus valve current

ANALOG INPUTS (two available)

0 to 5 Vdc range of signal

100 kilohm effective input impedence

10 bit resolution

PULSE TIMING INPUT OR SWITCH (one available)

Pulse input: 4 Vdc minimum (20 to 15,000 Hz range)

Switch input: high (greater than 4 volts) to actuate

VALVE DRIVE (two available)

LOW CURRENT OUTPUTS

180  ma  maximum  current  source  (7.0  volt  maximum

available)

Uni-directional configuration, high-side switched

HIGH CURRENT OUTPUTS

3 amp maximum current, PWM and on/off

High side switched or low side switched

Uni-directional

The choice of valve type is done in software through

Hidden Access.

SENSOR POWER SUPPLY

(Three common output pins available)

5

±

.25 Vdc regulated

500 ma maximum total current

CAN CONNECTION

Two wire shielded cable (Consult Danfoss)

ENVIRONMENTAL

OPERATING TEMPERATURE

-40

°

 to 70

°

 C (-40

°

 to 158

°

 F)

MOISTURE

Protected against 95% relative humidity. Packaged to

withstand high pressure washdowns

VIBRATION

Withstands a random vibration spectrum from 50 to 2000

Hz representative of the construction environment

SHOCK

50 Gs

DIMENSION

See the Dimensions drawing

The control console is protected against reverse polarity.

Static discharge, EMI and RFI, electrical transients, including

load dumps, are resisted by the controller.

Pulse timing inputs are protected for short circuits to positive

battery or ground. Analog inputs and sensor power supply

are protected for short circuits to ground.

Valve drive outputs are protected against shorts to positive

battery  or  ground.  Opens  or  shorts  can  be  detected  and

diagnosed.

ELECTRICAL

The Controller should be removed if any welding is done to

the machine.

The controller has internal fault detection and confinement to

minimize inappropriate output activity.

Содержание KGS

Страница 1: ...es or proportional solenoid valves Fault recognition with diagnostics Full electrical and environmental protection Fewerelectricalaccessoriesandreducedmachine wiring possible SYSTEM CONFIGURATION The...

Страница 2: ...uto mode from manual mode the prior setpoint is not saved but must be reset by the operator The motion interlocks are disabled with this option Controller Outputs 5 Solenoid valve or servovalve high s...

Страница 3: ...l current CAN CONNECTION Two wire shielded cable Consult Danfoss ENVIRONMENTAL OPERATING TEMPERATURE 40 to 70 C 40 to 158 F MOISTURE Protected against 95 relative humidity Packaged to withstand high p...

Страница 4: ...4 DIMENSIONS Dimensions of the KGS in Millimeters Inches 1961...

Страница 5: ...s The mating connector assembly for the KGS console must be ordered separately The Danfoss part number is K18169 which is composed of 28 pins 8 seal plugs 1 connector and 3 connector keys 9 8 7 6 5 4...

Страница 6: ...rmined by built in software and by instructions received from the operator s use of switches Continuous operating information is provided to the operator with displays which are continuously monitorin...

Страница 7: ...effective reference point Both setpoint and actual displays are changed simultaneously Holding this switch and pushing the null setpoint switch will alternately zero the display offset or zero the dis...

Страница 8: ...variables to a particular hidden access level is accomplished with the special configuration section of the ordering code Consult Danfoss The foreman level is accessed with the sensitivity switch and...

Страница 9: ...m Interlock travel speed Machine speed to turn control 0 0 to 20 0 ft min or 0 to 7 0m min 10 0 ft min Dealer on or off Switch interlock delay Time delay after forward motion 0 0 to 10 0 sec 10 0 sec...

Страница 10: ...repair or evaluation include a description of the problem and what work you believe needs to be done along with your name address and telephone number RETURN TO Danfoss US Company Return Goods Departm...

Отзывы: