background image

Instructions

6 | © Danfoss | DCS (CC) | 2018.11

FRCC.PI.052.A2.02

1 – Introduction 

This instruction applies to fan-cooled 

condensing units for the refrigerants stated 

page 3-4.

2 – Versions

Version N0/A00

Version, for solder connection, has a nitrogen 

holding charge. The units are designed for use 

in refrigeration systems with capillary tube and 

are to be treated as compressors concerning 

evacuation and refrigerant charge.

Version N1

Version, which is supplied without refrigerant 

receiver but with one stop valves and a nitrogen 

holding charge, is designed for use in 

refrigeration systems with capillary tube. The 

units are to be treated as compressors 

concerning evacuation and refrigerant charge.

Version N2

Version, which is supplied without refrigerant 

receiver but with two stop valves and a nitrogen 

holding charge, is designed for use in 

refrigeration systems with capillary tube. The 

units are to be treated as compressors 

concerning evacuation and refrigerant charge.

Version T2/A01 without pressure control

Version without pressure control, which is 

supplied with refrigerant receiver, two stop 

valves and  a nitrogen holding charge, is 

designed for use in refrigeration systems with 

expansion valve.

The refrigerant receiver is approved for max. 32 

bar operating pressure (see receiver label) and 

is HP marked.

Units according to British Standard 1608 

and approved by UL (UL identifiable through 

additional label) are supplied with a fusible 

plug.

In the event of fire, the fuse will melt before the 

temperature reaches 150°C.

Version T2/A04 with pressure control

Version with pressure control is supplied with 

refrigerant receiver, two stop valves and a 

nitrogen holding charge.

The refrigerant receiver is approved for max. 32 

bar operating pressure (see receiver label) and 

is HP marked.

The units are delivered with a combined high 

and low pressure control type KP17W, KP17WB 

or with a high pressure control type KP7W.

The pressure controls KP17W/KP17WB and 

KP7W are in compliance with the safety 

standard EN 378-2.

The high pressure controls are set to cut out at 

18 bar / R134a and 27 bar /R404A and R452A.

The low pressure control cuts out at 0 bar 

(factory presetting). Indications in bar 

overpressure (P

e

).

Version T0 without pressure control

Version without pressure control is supplied with 

refrigerant receiver and a nitrogen holding 

charge; it is designed for use in refrigeration 

systems with expansion valve and is to be 

completely soldered. The refrigerant receiver is 

approved for max. 32 bar operating pressure 

(see receiver label) and is HP marked.

Units according to British Standard 1608 and 

approved by UL (UL identifiable through 

additional label) are supplied with a fusible 

plug.

In the event of fire, the fuse will melt before the 

temperature reaches 150°C.

Version T0 with pressure control

Version with pressure control is supplied with 

refrigerant receiver and a nitrogen holding 

charge. It is designed for use in refrigeration 

systems with expansion valve and is to be 

completely soldered. These units are supplied 

with a high pressure control type CC.

Version T1

Version without pressure control is supplied with 

refrigerant receiver and a nitrogen holding 

charge; it is designed for use in refrigeration 

systems with expansion valve and is to be 

completely soldered. 

3 – Installation

Installation, maintenance and commissioning 

must be carried out by qualified specialists only!

All connections, i.e. solderings and flare joints, 

are to be made professionally.

Protect the surroundings against admittance of 

unauthorised persons. Pay attention to sufficient 

ventilation.

Remove transport safety devices, if any.

Mount the condensing unit horizontally. Use 

the correct tube diameters.

Prevent any vibrations. Avoid smoking and 

open fire.

Refrigerant is to be removed and disposed of 

professionally.

Assembly of the condensing units

Prepare the tube connections from the 

evaporator.

It is recommended to use a drier with 3Å 

molecular sieves, e.g. Danfoss type DML.

Use only dry components and avoid moisture 

entering the system.

The system components must not contain any 

chlorine, mineral oil, or other oily substances.

Maximum test pressure must not exceed 32 bar.

4 – Refrigerant charging

Refrigerant charging (N0, N1, N2, T0, T1, T2, 

A00, A01 and A04)

Fig. 2. The process descriptions below are based 

on the equipment shown.

  1.  Suction stop valve

  2.  Discharge stop valve

  3.  Connection to suction side

  4.  Shut-off valve to vacuum pump

  5.  Shut-off valve to charging cylinder

  6.  Connection to discharge side

  7.  Shut-off valve to discharge side

  8.  Shut-off valve to suction side

  9.  Connection to vacuum pump

 10. Connection to charging cylinder

When a vacuum of  0.5 mbar or lower has been 

reached, shut off the connection to the vacuum 

pump by closing all manifold valves.

Repeat the evacuating process once or twice if 

necessary and then close all manifold valves. 

Close the service connector of the suction stop 

valve (1) by turning the spindle „anticlockwise“ 

to the rear stop.

Refrigerant charging must take place from 

equipment not contaminated with refrigerants 

containing chlorine.

For units with stop valves the rule is that 

refrigerant should always be charged in liquid 

form through the discharge stop valve of the 

unit in order to avoid liquid hammer when the 

unit is started. If this rule cannot be observed 

the compressor is not to be started until the 

pressure and the temperature of the 

refrigerating  system have been equalized.

Open valves (5) and (7) of the valve manifold 

while keeping the other valves closed.

When all liquid has been transferred to the 

discharge side of the unit close the service 

connector of the  discharge valve (2) by turning 

the spindle „anticlockwise“ to the rear stop. 

Remove all hose connections.

Fit the union nuts with blind caps on pressure 

gauge connectors (1) and (2).

Fit and tighten up caps on the valve spindles.

5 – Evacuation

Evacuation (N2, T2, A01 and A04)

Fig. 2. The process descriptions below are based 

on the equipment shown.

  1.  Suction stop valve

  2.  Discharge stop valve

  3.  Connection to suction side

  4.  Shut-off valve to vacuum pump

  5.  Shut-off valve to charging cylinder

  6.  Connection to discharge side

  7.  Shut-off valve to discharge side

  8.  Shut-off valve to suction side

  9.  Connection to vacuum pump

 10. Connection to charging cylinder

Connect the discharge line to the suction stop 

valve (1) of the unit.

Connect the suction line, via the filter drier, to 

the discharge stop valve (2).

Make the connection (3) between the manifold 

and the service connector of the suction stop 

valve (1).

Make the connection (6) between the manifold 

and the service connector of the discharge stop 

valve (2).

Make the connection (9) between the vacuum 

pump and the manifold (4).

Make the connection (10) between the 

charging cylinder and the manifold (5).

Remove the protective caps from the spindles 

of both stop valves (1) and (2).

Open valves (4), (7) and (8). Open stop valves (1) 

and (2) to mid position. Start the vacuum pump.

Vacuum pumps, which are normally used for 

refrigerants containing chlorine, cannot be  

used with R134a, R404A/R507 and R452A.  

Only a vacuum pump with special Polyolester 

oil may be used for systems with refrigerant 

containing FCKW, HFCKW and HFKW.  

(Contact the pump supplier.)

Evacuation (T0, A00)

Evacuation takes place through the compressor 

then process connector after complete 

connection in the refrigerating circuit.

Plan sufficient time for the evacuation as it 

takes place from the low pressure side only,

unless additional measures were taken to speed 

up the evacuation.

Vacuum pumps normally used for refrigerants 

containing chlorine must not be used with 

R134aand R404A/R507. Only a vacuum pump 

with special Polyolester oil may be used for 

systems with refrigerant containing FCKW, 

HFCKW and HFKW. (Contact the pump supplier.)

6 – Electrical connections

Prepare the electrical connections while 

evacuation is taking place. Do not start the 

compressor until the  vacuum has been broken. 

Remove the cover over the terminal board. 

Connect the leads.

It is impossible to start the unit without a 

thermostat (1H) being connected or a lead 

between 1 or 2, respectively, and L has been 

established (fig. 4-7).

Fig. 4. Wiring diagram for the compressor 

series: P, T, N, F, S.

Fig. 5. Wiring diagram for the compressor 

series: SC with CSR (starting and operating 

capacitor).

Fig. 6. Wiring diagram for the compressor 

series: TL, FR and SC condensing units with 

pressure control.

Fig. 7. Wiring diagram for the compressor 

series: SC condensing units with combined high 

and low pressure control and CSR (starting and 

operating capacitor).

Fig. 8. Wiring diagram for the compressor 

series: MP & ML condensing units.

1A. Main  winding

 1B.  Start  winding

 1C. Start  relay

 1D. Winding  protector

 1E.  Start  capacitor

 1F.  Bleeder  resistance

 1G. Run  capacitor

 1H. Thermostat

 1J.  Fan 

 1K.  Pressure  control

Fit the terminal board cover.

Keep away flammables from the electrical 

equipment.

7 – Declaration of conformity

  •   All our condensing units are complied with 

low voltage directive  2014/35/EU and must 

be incorporated during installation.

 •  Low Voltage Directive 2014/35/EU 

EN 60335-1:2012 + A11:2014- Household and 

similar electrical appliances-Safety-Part 1: 

General requirements-for all above mentioned 

condensing units with compressor platforms 

FR, GS, L, P, NF, NL, PL, SC and TL.

 •  Eco-design DIRECTIVE 2009/125/

EC, establishing a framework for the setting 

Содержание FF10G

Страница 1: ...sing units fractional range Danfoss DCS CC 2018 11 FRCC PI 052 A2 ML 1 English English p 6 Dansk Danish p 8 Deutsch German p 10 Fran ais French p 12 Espa ol Spanish p 14 Svenska Swedish p 16 Nederland...

Страница 2: ...1G 1F 1E 1J 1H 7133 1 8 4 3 9 10 7 5 6 2 1 8 4 3 9 10 7 5 6 1 2 7132 1 1 3 4 6 5 7 8 2 220 V for R452A R134a R404A R507 UL and none UL 115 V for R134a R404A R507 UL and none UL 1 2 N L L N 2 1 2 1 3...

Страница 3: ...er volume cm3 Kompressorit Maks sallittu kylm ainet ytt g Lauhdutinryhm Lauhdutin tilavuus cm3 Varaaja tilavuus cm3 TL3G TL4G TL5G 400 BG1 130 800 TL5G BG2 240 NL8 4MF 600 FR6G FR7 5G FR8 5G FR10G 900...

Страница 4: ...900 Maximum refrigerant charges Fig 10 Units without receiver N0 N2 A00 R134a R513A R404A R507 Compressors Max permissible refrigerant charge g Group of condenser Condenser volume cm3 Kompressorer Ma...

Страница 5: ...For R404A models Factory setting HP bar MBP 28 8 LBP 28 3 LP bar Instructions Danfoss DCS CC 2018 11 5 FRCC PI 052 A2 ML...

Страница 6: ...valve to suction side 9 Connection to vacuum pump 10 Connection to charging cylinder When a vacuum of 0 5 mbar or lower has been reached shut off the connection to the vacuum pump by closing all manif...

Страница 7: ...ver See fig 9 Units without receiver See fig 10 The refrigerants stated on page 3 and 4 must be used It is recommended that only the right quantity of refrigerants necessary for correct function of th...

Страница 8: ...dningscylinder 6 Tilslutning til trykside 7 Afsp rringsventil til trykside 8 Afsp rringsventil til sugeside 9 Tilslutning til vakuumpumpe 10 Tilslutning til p fyldningscylinder N r et vakuum p 0 5 mba...

Страница 9: ...et monteres integreres i skal v re i overensstemmelse med PED 9 Maksimale k lemiddelfyldninger Aggregater med receiver Se fig 9 Aggregater uden receiver Se fig 10 De k lemidler der er angivet p side 3...

Страница 10: ...ystem gelangt Die Systemkomponenten d rfen weder Chlor Mineral l oder andere lige Stoffe enthalten Der maximale Pr fdruck darf 32 Bar nicht berschreiten 4 K ltemittelbef llung K ltemittelbef llung N0...

Страница 11: ...lten wird Wenn eine Zwangsbel ftung erforderlich ist muss dies deutlich angezeigt sein z B mit einem Aufkleber Nicht in aggressiver feuchter oder staubiger Umgebung installieren Nicht in R umen die en...

Страница 12: ...composants secs et propres et emp cher toute humidit ext rieure d entrer dans le syst me Les composants du syst me ne doivent pas contenir de chlore d huile min rale ou d autres substances grasses La...

Страница 13: ...ulement et aspiration sont compl tement ouvertes S assurer que la norme EN 378 est bien respect e Si une ventilation forc e est n cessaire ceci doit appara tre clairement e g au moyen d une tiquette N...

Страница 14: ...ga de refrigerante Carga de refrigerante N0 N1 N2 T0 T1 T2 A00 A01 y A04 Fig 2 Las siguientes descripciones de proceso se basan en el equipo mostrado 1 V lvula de cierre en aspiraci n 2 V lvula de cie...

Страница 15: ...tornos agresivos h medos o polvorientos No instale o arranque la unidad en c maras que contengan gases inflamables o en instalaciones que funcionan con ellos PED Directiva sobre equipos a presi n 97 2...

Страница 16: ...til till utsl ppssida 8 Avst ngningsventil till sugsida 9 Anslutning till vakuumpump 10 Anslutning till laddningscylinder N r ett vakuum p 0 5 mbar eller l gre har uppn tts ska du st nga av anslutning...

Страница 17: ...e uppfylla kraven i PED 9 Maximal k ldmediefyllning Aggregat med k ldmediemottagare Se fig 9 Aggregat utan k ldmediemottagare Se fig 10 De k ldmedier som anges p sidan 3 och 4 m ste anv ndas Vi rekomm...

Страница 18: ...vatten De maximale testdruk mag niet hoger zijn dan 32 bar 4 Vullen met koudemiddel Vullen met koudemiddel N0 N1 N2 T0 T1 T2 A00 A01 en A04 Fig 2 De onderstaande procesbeschrijvingen zijn gebaseerd op...

Страница 19: ...ige omgeving Niet installeren of starten in ruimtes met ontvlambare gassen of in installaties die daarmee werken PED Richtlijn drukapparatuur 97 23 EG Koelgroepen zijn geen units volgens de PED De uni...

Страница 20: ...Alla olevat prosessin kuvaukset koskevat kuvassa n kyv laitetta 1 Imupuolen sulkuventtiili 2 Painepuolen sulkuventtiili 3 Liit nt imupuolelle 4 Sulkuventtiili tyhj pumppuun 5 Sulkuventtiili t ytt syl...

Страница 21: ...simit yt t Varaajalla varustetut yksik t Katso kuva 9 Yksik t ilman varaajaa Katso kuva 10 On k ytett v sivuilla 3 ja 4 mainittuja j hdytysaineita On suositeltavaa lis t j hdytysaineita ainoastaan sop...

Страница 22: ...32 4 A04 A01 A00 T2 T1 T0 N2 N1 N0 2 1 2 3 4 5 6 7 8 9 10 0 5 1 7 5 2 2 1 5 A04 A01 T2 N2 2 1 2 3 4 5 6 7 8 9 10 1 2 3 1 6 2 4 9 5 10 2 1 2 1 8 7 4 R404A R507 R134a R452A HFKW HFCKW FCKW A00 T0 R404A...

Страница 23: ...CC PI 052 A2 38 EN 13771 2 2007 LCJE BEAB Demko Nemko IEC 79 15 IEC 335 2 89 EN 60 335 2 24 8 EN 378 97 23EC PED PED PED 9 9 10 4 3 T0 A04 A02 A01 T2 T0 3 2 192H2095 35 FR TL 192H2096 55 SC 10 10 11 5...

Страница 24: ...17 KP 15A t1 min KP 15 40 F 40 C KP 17 25 C 13 F t1 max 65 C 150 F ptest max 35 bar 505 psig ptest max 20 bar 285 psig Type Range PB MWP KP 15 LP 0 2 7 5 bar 17 bar 250 psi HP 8 32 bar 35 bar 505 psi...

Страница 25: ...le reset Austauschbares Reset R armement convertible KP 15 LP HP convertible KP17WB HP convertible LP man LP auto LP auto LP man HP man HP man HP auto HP auto LP aut reset LP man reset HP AC1 16 A DC...

Страница 26: ...nfoss reserves the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in...

Отзывы: