FCM 300 PROFIBUS / VLT 2800 PROFIBUS
Parameters
Description of selections:
The order of the subindexes corresponds to the order
of the PCD’s in the PPO, i.e. subindex 1
≈
PCD 1,
subindex 2
≈
PCD 2 and so on. Each subindex can
hold the number of any of the FC motor / VLT 2800
parameters, but it is only possible to read 2 byte
values (least significant bytes) from parameters with 4
byte data values as 1 PCD consists of only 2 bytes.
917 Activate spontaneous messages
(SPONT. MES)
Selections:
✭
Off (OFF)
[0]
On (ON)
[1]
Function:
The spontaneous messages function can be switched
on if it is desired to make the FC motor / VLT 2800 issue
a message when a warning or an alarm comes up.
Unread spontaneous messages will be stored
in a 16 elements FIFO buffer.
Description of selections:
-
OFF
: The FC motor / VLT 2800 will not issue
spontaneous messages or event notification in
case of a warning or an alarm.
-
ON
: The FC motor / VLT 2800 will issue a
spontaneous message when warnings or alarms
are coming up.
918 Station address (STATION ADDR)
Selections:
1-126
✭
0
Function:
All stations connected to the same bus must have a
unique address. The station address can be set in
parameter 918.
Change parameter 918 is executed at next
power up and if parameter 800 is updated.
✭
Factory setting
915 PCD config. write (PCD IN WR-)
Selections:
Sub index 1 (PCD1)
Parameter #
Sub index 2
Parameter #
Sub index 3
Parameter #
Sub index 4
Parameter #
Sub index 5
Parameter #
Sub index 6
Parameter #
Sub index 7
Parameter #
Sub index 8
Parameter #
Function:
Different parameters can be assigned to PCD 1-8 of
the PPO’s (the number of PCD’s depends on the PPO
type). The values in PCD 1-8 will be written to the
selected parameters as data values.
Write
access
via PROFIBUS or standard RS 485.
Description of selections:
The order of the subindexes corresponds to the order
of the PCD’s in the PPO, i.e. subindex 1
≈
PCD 1,
subindex 2
≈
PCD 2 and so on. Each subindex can
hold the number of the FC motor / VLT 2800
parameters with write access, but it is only possible
to write 2 byte values (least significant bytes) to
parameters with 4 byte data values because 1 PCD
consists of only 2 bytes.
916 PCD config. read (PCD IN RD-)
Selections:
Sub index 1 (PCD 1)
Parameter #
Sub index 2
Parameter #
Sub index 3
Parameter #
Sub index 4
Parameter #
Sub index 5
Parameter #
Sub index 6
Parameter #
Sub index 7
Parameter #
Sub index 8
Parameter #
Function:
Different parameters can be assigned to PCD 1-8 of
the PPO’s (the number of PCD’s depends on the PPO
type). PCD 1-8 will hold the actual data value of the
selected parameters.
Write
access
via Profibus or standard RS 485.