0-20 Display Line 1.1 Small
Option:
Function:
[1603]
Status Word
Present status word
[1605]
Main Actual
Value [%]
View the two-byte word sent with the
Status word to the bus Master reporting
the Main Actual Value.
[1609]
Custom
Readout
View the user-defined readouts as
defined in par. 0-30
Custom Readout Unit
,
par. 0-31
Custom Readout Min Value
and
par. 0-32
Custom Readout Max Value
.
[1610]
Power [kW]
Actual power consumed by the motor in
kW.
[1611]
Power [hp]
Actual power consumed by the motor in
HP.
[1612]
Motor Voltage
Voltage supplied to the motor.
[1613]
Frequency
Motor frequency, i.e. the output frequen-
cy from the frequency converter in Hz.
[1614]
Motor Current
Phase current of the motor measured as
effective value.
[1615]
Frequency [%]
Motor frequency, i.e. the output frequen-
cy from the frequency converter in
percent.
[1616]
Torque [Nm]
Present motor load as a percentage of
the rated motor torque.
[1617]
Speed [RPM]
Motor speed reference. Actual speed will
depend on slip compensation being
used (compensation set in par. 1-62
Slip
Compensation
). If not used, actual speed
will be the value read in the display
minus motor slip.
[1618]
Motor Thermal
Thermal load on the motor, calculated
by the ETR function. See also parameter
group 1-9* Motor Temperature.
[1622]
Torque [%]
Shows the actual torque produced, in
percentage.
[1626]
Power Filtered
[kW]
[1627]
Power Filtered
[hp]
[1630]
DC Link
Voltage
Intermediate circuit voltage in the
frequency converter.
[1632]
Brake Energy /s Present brake power transferred to an
external brake resistor.
Stated as an instantaneous value.
[1633]
Brake Energy /
2 min
Brake power transferred to an external
brake resistor. The mean power is
calculated continuously for the most
recent 120 seconds.
[1634]
Heatsink Temp. Present heat sink temperature of the
frequency converter. The cut-out limit is
0-20 Display Line 1.1 Small
Option:
Function:
95 ± 5
°
C; cutting back in occurs at 70
±
5
°
C.
[1635]
Inverter
Thermal
Percentage load of the inverters
[1636]
Inv. Nom.
Current
Nominal current of the frequency
converter
[1637]
Inv. Max.
Current
Maximum current of the frequency
converter
[1638]
SL Controller
State
State of the event executed by the
control
[1639]
Control Card
Temp.
Temperature of the control card.
[1643]
Timed Actions
Status
[1650]
External
Reference
Sum of the external reference as a
percentage, i.e. the sum of analog/pulse/
bus.
[1652]
Feedback
[Unit]
Reference value from programmed
digital input(s).
[1653]
Digi Pot
Reference
View the contribution of the digital
potentiometer to the actual reference
Feedback.
[1654]
Feedback 1
[Unit]
View the value of Feedback 1. See also
par. 20-0*.
[1655]
Feedback 2
[Unit]
View the value of Feedback 2. See also
par. 20-0*.
[1656]
Feedback 3
[Unit]
View the value of Feedback 3. See also
par. 20-0*.
[1658]
PID Output [%] Returns the Drive Closed Loop PID
controller output value in percent.
[1660]
Digital Input
Displays the status of the digital inputs.
Signal low = 0; Signal high = 1.
Regarding order, see par. 16-60
Digital
Input
. Bit 0 is at the extreme right.
[1661]
Terminal 53
Switch Setting
Setting of input terminal 53. Current = 0;
Voltage = 1.
[1662]
Analog Input
53
Actual value at input 53 either as a
reference or protection value.
[1663]
Terminal 54
Switch Setting
Setting of input terminal 54. Current = 0;
Voltage = 1.
[1664]
Analog Input
54
Actual value at input 54 either as
reference or protection value.
[1665]
Analog Output
42 [mA]
Actual value at output 42 in mA. Use
par. 6-50
Terminal 42 Output
to select the
variable to be represented by output 42.
[1666]
Digital Output
[bin]
Binary value of all digital outputs.
How to Programme the Frequ...
VLT
®
HVAC Drive Operating Instructions
66
MG.11.AD.02 - VLT
®