5-13 Terminal 29 Digital Input
Same options and functions as par. 5-1*.
Option:
Function:
[68]
Timed Actions Disabled
[69]
Constant OFF Actions
[70]
Constant ON Actions
[78]
Reset Maint. Word
[120]
Lead Pump Start
[121]
Lead Pump Alternation
[130]
Pump 1 Interlock
[131]
Pump 2 Interlock
[132]
Pump 3 Interlock
5-14 Terminal 32 Digital Input
Option:
Function:
[0]
*
No Operation Same options and functions as par. 5-1*
Digital Inputs
, except for
Pulse input
.
5-15 Terminal 33 Digital Input
Option:
Function:
[0]
*
No Operation Same options and functions as par. 5-1*
Digital Inputs
.
5-40 Function Relay
Array [8]
(Relay 1 [0], Relay 2 [1]
Option MCB 105: Relay 7 [6], Relay 8 [7] and Relay 9 [8]).
Select options to define the function of the relays.
The selection of each mechanical relay is realised in an array
parameter.
Option:
Function:
[0]
*
No operation
[1]
Control ready
[2]
Drive ready
[3]
Drive rdy/rem ctrl
[4]
Standby / no warning
[5]
*
Running
Default setting for relay 2.
[6]
Running / no warning
[8]
Run on ref/no warn
[9]
*
Alarm
Default setting for relay 1.
[10]
Alarm or warning
[11]
At torque limit
[12]
Out of current range
[13]
Below current, low
[14]
Above current, high
[15]
Out of speed range
[16]
Below speed, low
[17]
Above speed, high
[18]
Out of feedb. range
[19]
Below feedback, low
[20]
Above feedback, high
[21]
Thermal warning
[25]
Reverse
[26]
Bus OK
5-40 Function Relay
Array [8]
(Relay 1 [0], Relay 2 [1]
Option MCB 105: Relay 7 [6], Relay 8 [7] and Relay 9 [8]).
Select options to define the function of the relays.
The selection of each mechanical relay is realised in an array
parameter.
Option:
Function:
[27]
Torque limit & stop
[28]
Brake, no brake war
[29]
Brake ready, no fault
[30]
Brake fault (IGBT)
[35]
External Interlock
[36]
Control word bit 11
[37]
Control word bit 12
[40]
Out of ref range
[41]
Below reference, low
[42]
Above ref, high
[45]
Bus ctrl.
[46]
Bus ctrl, 1 if timeout
[47]
Bus ctrl, 0 if timeout
[60]
Comparator 0
[61]
Comparator 1
[62]
Comparator 2
[63]
Comparator 3
[64]
Comparator 4
[65]
Comparator 5
[70]
Logic rule 0
[71]
Logic rule 1
[72]
Logic rule 2
[73]
Logic rule 3
[74]
Logic rule 4
[75]
Logic rule 5
[80]
SL digital output A
[81]
SL digital output B
[82]
SL digital output C
[83]
SL digital output D
[84]
SL digital output E
[85]
SL digital output F
[160]
No alarm
[161]
Running reverse
[165]
Local ref active
[166]
Remote ref active
[167]
Start command act.
[168]
Hand / Off
[169]
Auto mode
[180]
Clock Fault
[181]
Prev. Maintenance
[190]
No-Flow
[191]
Dry Pump
[192]
End Of Curve
[193]
Sleep Mode
[194]
Broken Belt
[195]
Bypass Valve Control
How to Programme the Frequ...
VLT
®
HVAC Drive Operating Instructions
78
MG.11.AD.02 - VLT
®