Connecting cable lug
7. Cut piece of shrink tube and shrink it over the cable lug and braid screen as shown in Figure below.
This is done to keep the braid screen in place and for extra insulation.
The shrink tube must be specified for operating temperature range from -40 ºC to 150 ºC.
Self gluing shrink tube is recommended.
Shrink tube
8. Insert the cable through the corresponding hole in the connection box and connect the cable lug to
the connection point. Use spring washer between the cable lug and the connection screw or nut.
Example of the connection is shown in Figure below. Do not tighten the connection at this point to
ensure fitting of the cable gland.
Make sure that there is at least 10 mm air gap between the cable lug and other metallic
structures including the braid of the cable. If the air gap is smaller, use extra insulation
shrink tube to cover the lug.