Survey of functions

Function

Para- 

meter

Parameter by operation via 

data communication

Normal display
The normal display shows the pressure in the gas cooler. The pressure is measured 

using Pgc. The measurement can also be seen in menu U06.

The control reference can be viewed by pressing both buttons.

If a pressure transmitter is mounted to display the receiver pressure, the measure-

ment can be brought up on the display by pressing the lower button. The measure-

ment can also be seen in menu U07.

U06

U07

Pgc bar

Prec bar

Gas pressure control

Gas cooler control

Defining the reference line

Set the end point for the reference line in the transcritical range. Set the desired tem-

perature value at 100 bar.

n99

T100

The reference

The reference is pre-programmed to follow the optimal COP from the pressure/en-

thalpy chart. See the illustration on page 2.

The current reference can be read off in menu U03.

U03

Pgc Ref

Start/stop of regulation

This setting can be used to start and stop regulation. 

Stopping regulation will always cause the valve will close at the value set in "n87" and 

"n93".

The function in o02 requires that it has been defined.

r12

Main Switch

Max. opening degree

The ICMTS-valve’s opening degree can be limited here. 

Limitation takes place by limiting the voltage signal that is sent to the valve actuator.

The setting is expressed as a % of the total opening degree. The voltage signal of 0-10 

V on the output will be limited correspondingly.

n32

Vhp OD Max

Minimum opening degree

The closing degree of the ICMTS valve can be limited here. 

Limitation takes place by increasing the lower part of the voltage signal that is sent to 

the valve actuator.

The setting is expressed as a percentage of the total opening degree. The output volt-

age signal of 0-10 V will be limited correspondingly.

n87

Vhp OD Min

The gas cooler’s max. pressure

This is where you define the maximum pressure permitted in the gas cooler. If the 

pressure reaches this value, the valve is open as set in "n32 OD max".

n69

Pgc Max

P-band to force open the valve from normal regulation

P-band under “n69, Pgc Max lim”, where the valve is forced open so that the valve is 

fully open if the pressure reaches “n69, Pgc Max lim”.

The pressure is not critical, so opening of the valve will take place under controlled 

conditions.

n70

Pgc P-band

The gas cooler’s min. pressure

This is where you define the minimum pressure permitted in the gas cooler.

n81

Pgc Min

Subcooling is required to be regulated according to temperature

Set the desired subcooling in K.

n79

dT Subcool

P: Amplification factor Kp

If the Kp value is reduced the regulation becomes slower.

n04

Kp Gascool

I: Integration time Tn

If the Tn value is increased the regulation becomes slower

n05

Tn Gascool

Increasing refrigeration capacity

This function increases the gas pressure reference. Control moves from optimum 

COP control to maximum refrigeration control. (The pressure increases, temperature 

remains unchanged and the total heat content increases.) 

Set the pressure increase value. 

The function is activated by closing the switch function on terminals 1 and 2. (see 

o02)

n88

Pgc Cap Offset

Содержание EKC 326A

Страница 1: ...Controller to regulate CO2 gas pressure EKC 326A User Guide ADAP KOOL Refrigeration control systems...

Страница 2: ...reading Heat recovery with adjustable reference pressure 0 10 V Optimum heat pump operation System The pressure in the gas cooler is controlled by the valve Regula tion must have inputs from both a pr...

Страница 3: ...nput signal of 0 10 V as follows A signal of 1 5 V or above can activate the function and increase the reference to Pgc HR Min If a variable reference is required then a signal between 2 10 V can be c...

Страница 4: ...4 Manual RS8FM602 Danfoss 02 2016 EKC 326A Examples Simple heat recovery system Partial heat recovery system Heat recovery system or heat pump system...

Страница 5: ...s a signal The function is activated by a voltage signal between 0 10 V Between 0 2 V it is regulated normally At 2 V the reference changes to the setting Pc HR Min At 10 V the reference will increase...

Страница 6: ...correspondingly n32 Vhp OD Max Minimum opening degree The closing degree of the ICMTS valve can be limited here Limitation takes place by increasing the lower part of the voltage signal that is sent...

Страница 7: ...c Ctrl Receiver reference The reference for receiver control is set here n91 Prec Ref Maximum opening degree The ETS CCM valve s opening degree can be limited here The setting is expressed as a percen...

Страница 8: ...the gateway when the menu is set in pos ON The setting will automatically change back to Off after a few seconds o04 Frequency Set the net frequency o12 50 60 Hz 50 0 60 1 Pressure transmitter definit...

Страница 9: ...apacity through displacement of the pressure reference 43 Alarms E1 Fault in controller Controller fault E15 Cut out Sgc sensor Sgc o c E16 Short circuited Sgc sensor Sgc S C E20 Fault on the signal f...

Страница 10: ...efly will display Prec bar Start stop Start stop of regulation r12 OFF 0 On 1 On 1 Ramp for reference after heat recovery r65 0 1 20 1 Displacement of the Pgc minimum reference n89 during heat recover...

Страница 11: ...done in this way Cut out the supply voltage to the controller Keep both buttons depressed at the same time as you recon nect the supply voltage 0 V valve closed 10 V valve open Cable connection 060G1...

Страница 12: ...een EKC 326A and the ETS CCM CCMT valve exceeds 5 m a filter must be mounted to obtain the correct valve function The filter must be placed close to EKC 326A L 5 m 5 m L 50 m Dimensions Connection Typ...

Страница 13: ...m Signal range 2 10 V Sensor input 1 pcs Pt 1000 ohm Alarm relay 1 pcs SPST 250 V a c AC 1 4 A ohmic AC 15 3 A inductive Actuator ICAD mounted on ICMTS Voltage signal 0 10 mA ETS CCM or CCMT 2 8 Step...

Страница 14: ...ure plus set p band As such gas can still be sent through the valve Receiver pressure s min limit A minimum receiver pressure limit can be set If the controller register receiver pressure below the se...

Страница 15: ...EKC 326A Manual RS8FM602 Danfoss 02 2016 15 Functions for regulation reference...

Страница 16: ...rupted none EKC AO remains 0 V ICMT closes if ICMTS has battery back up No change in opening degree EKC Standby Main Switch OFF A45 Standby mode ICMTS closes ETS closes to Vgbp OD Min setting Sgc inte...