16
Manual RS8FM602 © Danfoss 02-2016
EKC
326A
List of literature
Instructions RI8NG (extract from this manual).
Here you can see how controllers are mounted and
programmed.
Installation guide for extended operation
RC8AC
Here you can see how a data communication
connection to ADAP-KOOL® Refrigeration control
systems can be established.
AD
AP
-K
OOL®
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed.
All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Installation considerations
Accidental damage, poor installation, or site conditions, can give
rise to malfunctions of the control system, and ultimately lead to a
plant breakdown.
Every possible safeguard is incorporated into our products to
prevent this. However, a wrong installation, for example, could still
present problems. Electronic controls are no substitute for normal,
good engineering practice.
Danfoss will not be responsible for any goods, or plant compo-
nents, damaged as a result of the above defects. It is the installer's
responsibility to check the installation thoroughly, and to fit the
necessary safety devices.
Error
Alarm message
ICMTS action (Vhp)
ETS action (Vgbp)
EKC supply interrupted
none
EKC AO remains 0 V – ICMT closes if ICMTS has
battery back-up
No change in opening degree
EKC Standby – Main
Switch OFF
A45 – Standby mode
ICMTS closes
ETS closes to 'Vgbp OD Min' setting
Sgc interrupted
E15 – Sgc o.c.
ICMTS regulates with “Emergency cooling”
No change – ETS control attempts to maintain
Prec
Sgc short circuited
E16 – Sgc s.c.
ICMTS regulates with “Emergency cooling”
No change – ETS control attempts to maintain
Prec
Pgc transmitter error
E20 – Pgc input err
ICMTS regulates with “Emergency cooling”
No change – ETS control attempts to maintain
Prec
Prec transmitter error
E39 – Prec input err
No change – ICMTS control continues
ETS regulates with “Emergency cooling”
StepMotor error
A43 – Step motor err
No change – ICMTS control continues
ETS closes to 'Vgbp OD Min' setting
Pgc Max limit exceeded
A82 – PgcMax alarm
No change – ICMTS control attempts to lower
Pgc
No change – ETS control attempts to maintain
Prec
Pgc Min limit exceeded
A83 – PgcMin alarm
No change – ICMTS control attempts to raise Pgc
No change – ETS control attempts to maintain
Prec
Prec Min limit exceeded
A84 – PrecMin alarm
No change – ICMTS control attempts to maintain
Pgc
No change – ETS control attempts to raise Prec
PgcRef Alarm
A94 – PgcRef alarm
No change – ICMTS control attempts to maintain
Pgc
No change – ETS control attempts to raise Prec
PrecRef Alarm
A95 – PrecRef alarm
No change – ICMTS control attempts to maintain
Pgc
No Change – ETS control attempts to raise Prec
EKC HW error
E1 – Controller fault
No change – ICMTS control continues
No change – ETS control continues
"Emergency cooling"
The valve's average opening degree for the last six hours is
regularly saved. This opening degree is used if there is a need for
emergency cooling.
Valve function in alarm situations