Danfoss EKC 326A Скачать руководство пользователя страница 11

EKC 

326A 

Manual RS8FM602 © Danfoss 02-2016 

11

Necessary connections

Terminals:

25-26  Supply voltage 24 V a.c.

18-19  Pt 1000 sensor at gas cooler outlet (Sgc)

14,15,16 Pressure transmitter AKS 2050, -1 to 159 bar

 

To register the correct pressure it must be mounted as    

 

close as possible to the gas cooler.

5-6 

Voltage output to control the ICMTS valve.

Connections

Application dependent connections

Terminals:

1-2 

DI-input to either:

External main switch (see o02 and r12)

OR

 

Contact function for increasing capacity (optimised COP 

operation stopped).  (see o02)

 

Open connection = optimised COP operation

 

Closed connection = extra capacity.

12-13   Alarm relay

There is connection between 12 and 13 in alarm situa tions 

14,16,17 Optional. A pressure transmitter can be connected so 

that the pressure in the receiver can be monitored. The 

pressure transmitter must be an AKS 2050, -1 to 59 bar.

21-24  If receiver pressure is to be controlled, a CCM or  ETS valve 

should be connected.

18-20  Heat recovery. A voltage signal between 2 and 10 V will 

increase the gas pressure reference.

3-4  

Data communication

 

Mount only, if a data communication module has been 

mounted.

It is important that the installation of the data communi-

cation cable be done correctly. Cf. separate literature No. 

RC8AC...

Factory setting

If you need to return to the factory-set values, it can be done in this way:

- Cut out the supply voltage to the controller

- Keep both buttons depressed at the same time as you recon nect the supply voltage

0 V = valve closed

10 V = valve open

Cable connection

060G1034

14 = black

15 = brown

16 = blue

AKS 11: Max. 100°C

AKS 21: Max. 180°C

*) This setting will only be possible if a data communication module has been installed in the 
controller.

See also next page 

Miscellaneous
Digital input signal - DI 

0: The input is not used

1: External main switch

2: additional cooling capacity

o02

0

2

0

Controller’s address

o03*

0

240

-

ON/OFF switch (service-pin message)

o04*

-

-

-

Set supply voltage frequency

o12

50Hz 

(0)

60 Hz 

(1)

0

Pressure transmitter range Pgc - min.

o20

-1 bar 5 bar

-1

Pressure transmitter range Pgc - max.

o21

6 bar

199 bar 159

Pressure transmitter range Prec - min.

o47

-1 bar 5 bar

-1

Pressure transmitter range Prec - max.

o48

6 bar

199 bar 59

Service

Signal on AI the input

u07

V

Read status of input DI

u10

on/off

Read ETS/CCM valves opening degree

u24

%

Calculated reference for regulation (desired pres-

sure in the gas cooler)

U03

bar

The output signal to the ICMTS valve converted 

into opening degree

U04

%

The temperature in the gas cooler. Measured 

using temperature sensor Sgc.

U05

°C

The pressure in the gas cooler. Measured using 

pressure transmitter Pgc.

U06

bar

The pressure in the receiver. Measured using 

pressure transmitter Prec, but only if it is 

mounted.

U07

bar

High pressure valve

Vhp

Gas bypass valve

Vgbp

8 VA

Importan

t

PGC and Sgc must b

e mount

-

ed near the gas c

ooler outlet 

to produc

e a correc

t signal.

Содержание EKC 326A

Страница 1: ...Controller to regulate CO2 gas pressure EKC 326A User Guide ADAP KOOL Refrigeration control systems...

Страница 2: ...reading Heat recovery with adjustable reference pressure 0 10 V Optimum heat pump operation System The pressure in the gas cooler is controlled by the valve Regula tion must have inputs from both a pr...

Страница 3: ...nput signal of 0 10 V as follows A signal of 1 5 V or above can activate the function and increase the reference to Pgc HR Min If a variable reference is required then a signal between 2 10 V can be c...

Страница 4: ...4 Manual RS8FM602 Danfoss 02 2016 EKC 326A Examples Simple heat recovery system Partial heat recovery system Heat recovery system or heat pump system...

Страница 5: ...s a signal The function is activated by a voltage signal between 0 10 V Between 0 2 V it is regulated normally At 2 V the reference changes to the setting Pc HR Min At 10 V the reference will increase...

Страница 6: ...correspondingly n32 Vhp OD Max Minimum opening degree The closing degree of the ICMTS valve can be limited here Limitation takes place by increasing the lower part of the voltage signal that is sent...

Страница 7: ...c Ctrl Receiver reference The reference for receiver control is set here n91 Prec Ref Maximum opening degree The ETS CCM valve s opening degree can be limited here The setting is expressed as a percen...

Страница 8: ...the gateway when the menu is set in pos ON The setting will automatically change back to Off after a few seconds o04 Frequency Set the net frequency o12 50 60 Hz 50 0 60 1 Pressure transmitter definit...

Страница 9: ...apacity through displacement of the pressure reference 43 Alarms E1 Fault in controller Controller fault E15 Cut out Sgc sensor Sgc o c E16 Short circuited Sgc sensor Sgc S C E20 Fault on the signal f...

Страница 10: ...efly will display Prec bar Start stop Start stop of regulation r12 OFF 0 On 1 On 1 Ramp for reference after heat recovery r65 0 1 20 1 Displacement of the Pgc minimum reference n89 during heat recover...

Страница 11: ...done in this way Cut out the supply voltage to the controller Keep both buttons depressed at the same time as you recon nect the supply voltage 0 V valve closed 10 V valve open Cable connection 060G1...

Страница 12: ...een EKC 326A and the ETS CCM CCMT valve exceeds 5 m a filter must be mounted to obtain the correct valve function The filter must be placed close to EKC 326A L 5 m 5 m L 50 m Dimensions Connection Typ...

Страница 13: ...m Signal range 2 10 V Sensor input 1 pcs Pt 1000 ohm Alarm relay 1 pcs SPST 250 V a c AC 1 4 A ohmic AC 15 3 A inductive Actuator ICAD mounted on ICMTS Voltage signal 0 10 mA ETS CCM or CCMT 2 8 Step...

Страница 14: ...ure plus set p band As such gas can still be sent through the valve Receiver pressure s min limit A minimum receiver pressure limit can be set If the controller register receiver pressure below the se...

Страница 15: ...EKC 326A Manual RS8FM602 Danfoss 02 2016 15 Functions for regulation reference...

Страница 16: ...rupted none EKC AO remains 0 V ICMT closes if ICMTS has battery back up No change in opening degree EKC Standby Main Switch OFF A45 Standby mode ICMTS closes ETS closes to Vgbp OD Min setting Sgc inte...

Отзывы: