Danfoss EKC 202A Скачать руководство пользователя страница 6

Instructions  RI8JV352  ©  Danfoss  07/2005 

   EKC 202A, B, C

Miscellaneous

Delay of output signals after start-up

o01

0 s

600 s

5 s

Input signal on DI1. Function:
0=not used. 1=status on DI1. 2=door function with alarm when open. 3=door alarm 
when open. 4=defrost start (pulse-pressure).  5=ext.main switch. 6=night operation 
7=switch to thermostat band 2. 8=alarm function when closed. 9=alarm function when 
open. 10=case cleaning (pulse pressure).

o02

0

10

0

Network address

o03

0

119

0

On/Off switch (Service Pin message)

o04

OFF

ON

OFF

Access code 1 (all settings)

o05

0

100

0

Used sensor type (Pt /PTC/NTC)

o06

Pt

ntc

Pt

Display step = 0.5 (normal 0.1 at Pt sensor)

o15

no

yes

no

Max hold time after coordinated defrost

o16

0 min

60 min

20

Configuration of light function (relay 4)
1=ON during night operation. 2=ON / OFF via data communication. 3=ON follows the 
DI-function, when DI is selected to door function or to door alarm

o38

1

3

1

Activation of light relay (only if o38=2)

o39

OFF

ON

OFF

Case cleaning. 0=no case cleaning. 1=Fans only. 2=All output Off.

o46

0

2

0

Access code 2 (partly access)

o64

0

100

0

Save the controllers present settings to the programming key. Select your own number. 

o65

0

25

0

Load a set of settings from the programming key (previously saved via o65 function) Can 
only be set when regulation is stopped (r12=0)

o66

0

25

0

Replace the controllers factory settings with the present settings

o67

OFF

On

OFF

Select application for S5 sensor (0=defrost sensor, 1= product sensor, 2=condenser sen-

sor with alarm)

o70

0

2

0

Select application for relay 4: 1=defrost/light, 2= alarm

o72

defrost /
Alarm

Light /
Alarm

1

2

2

Service

Temperature measured with S5 sensor

u09

Status on DI1 input. on/1=closed

u10

Status on night operation (on or off) 1=closed

u13

Read the present regulation reference

u28

Status on relay for cooling (Can be controlled manually, but only when r12=-1)

u58

Status on relay for fans (Can be controlled manually, but only when r12=-1)

u59

Status on relay for defrost. (Can be controlled manually, but only when r12=-1)

u60

Temperature measured with Sair sensor

u69

Status on relay 4 (alarm, defrost, light).(Can be controlled manually, but only when 
r12=-1)

u71

Fault code display

Alarm code display

Status code display

E1

Fault in controller

A 1

High temperature alarm

S0

Regulating

E6

Change b check clock

A 2

Low  temperature alarm

S1

Waiting for end of the coordinated defrost

E 27

S5 sensor error

A 4

Door alarm

S2

ON-time Compressor

E 29

Sair sensor error

A 5

Max. Hold time

S3

OFF-time Compressor

A 15

DI 1 alarm

S4

Drip-off time

A 45

Standby mode

S10

Refrigeration stopped by main switch

A 59

Case cleasning

S11

Refrigeration stopped by thermostat

A 61

Condenser alarm

S14

Defrost sequence. Defrosting

S15

Defrost sequence. Fan delay

S17

Door open (open DI input)

S20

Emergency cooling

S25

Manual control of outputs

S29

Case cleaning

S32

Delay of output at start-up

non

The defrost temperature cannot be dis-
played. There is stop based on time

-d-

Defrost in progress / First cooling after 
defrost

PS

Password required. Set password 

Factory setting
If you need to return to the factory-set values, it can be done in this way:
- Cut out the supply voltage to the controller
- Keep upper and lower button depressed at the same time as you reconnect the supply voltage

Содержание EKC 202A

Страница 1: ...nication LON RS 485 Type Pt 1000 1000 0 C Ptc 1000 1000 25 C NTC M2020 5000 25 C o06 10 V U 256 V DO1 Imax AC 1 10 A Derated 16 A relay DO2 Imax AC 15 6 A DO3 Imax AC 1 6 A Derated 8 A relay Imax AC 1...

Страница 2: ...2 Instructions RI8JV352 Danfoss 07 2005 EKC 202A B C EKC 202A EKC 202C EKC 202B AU Guld Gold or Oro l max 15 m AU Guld Gold or Oro l max 15 m AU Guld Gold or Oro l max 15 m...

Страница 3: ...r13 10 K 10 K 0 K Aktivering af referenceforskydningen r40 r39 OFF on OFF V rdi for referenceforskydning r40 50 K 50 K 0 K Alarm Forsinkelse p temperaturalarm A03 0 min 240 min 30 min Forsinkelse p d...

Страница 4: ...Pt f ler o15 no yes no Max holdetid efter koordineret afrimning o16 0 min 60 min 20 Kon guration af lysfunktionen rel 4 1 ON under natdrift 2 ON OFF via datakommunikation 3 ON f lger DI funktionen n...

Страница 5: ...ring night operation r13 10 K 10 K 0 K Activation of reference displacement r40 r39 OFF on OFF Value of reference displacement r40 50 K 50 K 0 K Alarm Delay for temperature alarm A03 0 min 240 min 30...

Страница 6: ...for relay 4 1 defrost light 2 alarm o72 defrost Alarm Light Alarm 1 2 2 Service Temperature measured with S5 sensor u09 Status on DI1 input on 1 closed u10 Status on night operation on or o 1 closed...

Страница 7: ...wischen zwei Abtauungen d18 0 hours 48 hours 0 hours Bedarfsgesteuerte Abtauung die S5 Temperatur erlaubt variation bei Eis aufbauung An Centralanlagen w hle 20 K o d19 0 K 20 K 20 K L fter L fterstop...

Страница 8: ...l o02 0 10 0 Netzwerkadresse o03 0 119 0 On O Wechselschalter Service Pin Mitteilung o04 OFF ON OFF Zugangskode 1 s mtliche Einstellungen o05 0 100 0 Angewandter F hlertyp Pt PTC NTC o06 Pt ntc Pt Dis...

Страница 9: ...0 0 2 0 Temps de refroidissement total maxi entre deux d givrages d18 0 hours 48 hours 0 hours D givrage sur demande variation admissible de la temp rature S5 en cas de formation de givre Pour les ins...

Страница 10: ...e u10 Etat du r gime de nuit tout ou rien 1 enclench u13 A chage de la r f rence de r gulation actuelle u28 Etat du relais de refroidissement La commande manuelle est possible mais condition que r12...

Страница 11: ...EKC 202A B C Instructions RI8JV352 Danfoss 07 2005 11...

Страница 12: ...12 Instructions RI8JV352 Danfoss 07 2005 EKC 202A B C...

Отзывы: