 EKC 202A, B, C 

Instructions  RI8JV352  ©  Danfoss  07/2005 

5

Start-up:

Regulation starts when the voltage is on.

1 Go through the survey of factory settings. Make any necessary changes in the respective parameters.
2 For network. Set the address in o03 and then transmit it to the gateway/system unit with setting o04.

English

The buttons

Set menu

1. Push the upper button until a parameter 

is shown

2. Push the upper or the lower button and 

find that parameter you want to change

3. Push the middle button until the 

parameter value is shown

4. Push the upper or the lower button and 

select the new value

5. Push the middle button again to enter 

the value.

Set temperature

1. Push the middle button until the 

temperature value is shown

2. Push the upper or the lower button and 

select the new value

3. Push the middle button to select the 

setting.

Reading the temperature at sensor S5

• Push briefly the lower button

Manuel start or stop of a defrost

• Push the lower button for four 
seconds.

 

Light emmiting diode

 = refrigeration

 = defrost
 = fan running

Flashes fast at alarm

Cutout alarm relay / see alarm code 

• Push briefly the upper button

SW = 1.1x

Parameters

Controller

Min.-

value

Max.-
value

Factory 

setting

Actual 

setting

Function

 Codes

EKC 

202A

EKC 

202B

EKC 

202C

Normal operation

Temperature (set point)

---

-50°C

50°C

2°C

Thermostat

Differential

r01

0,1 K

20 K

2 K

Max. limitation of setpoint setting

r02

-49°C

50°C

50°C

Min. limitation of setpoint setting

r03

-50°C

49°C

-50°C

Adjustment of temperature indication

r04

-20 K

20 K

0.0 K

Temperature unit (°C/°F)

r05

°C

°F

°C

Correction of the signal from Sair

r09

-10 K

10 K

0 K

Manual service(-1), stop regulation(0), start regulation (1)

r12

-1

1

1

Displacement of reference during night operation

r13

-10 K

10 K

0 K

Activation of reference displacement r40

r39

OFF

on

OFF

Value of reference displacement

r40

-50 K

50 K

0 K

Alarm

Delay for temperature alarm

A03

0 min

240 min

30 min

Delay for door alarm

A04

0 min

240 min

60 min

Delay for temperature alarm after defrost

A12

0 min

240 min

90 min

High alarm limit

A13

-50°C

50°C

8°C

Low alarm limit

A14

-50°C

50°C

-30°C

Alarm delay DI1

A27

0 min

240 min

30 min

High alarm limit for condenser temperature (o69)

A37

0°C

99°C

50°C

Compressor

Min. ON-time

c01

0 min

30 min

0 min

Min. OFF-time

c02

0 min

30 min

0 min

Compressor relay must cutin and out inversely (NC-function)

c30

0 / OFF

1 / on

0 / OFF

Defrost

Defrost method (none/EL)

d01

no

EL

EL

Defrost stop temperature

d02

0°C

25°C

6°C

Interval between defrost starts

d03

0 hours

48 hours

8 hours

Max. defrost duration

d04

0 min

180 min

45 min

Displacement of time on cutin of defrost at start-up

d05

0 min

240 min

0 min

Drip off time

d06

0 min

60 min

0 min

Delay for fan start after defrost

d07

0 min

60 min

0 min

Fan start temperature

d08

-15°C

0°C

-5°C

Fan cutin during defrost

d09

no

yes

yes

Defrost sensor (0=time, 1=S5, 2=Sair)

d10

0

2

0

Max. aggregate refrigeration time between two defrosts

d18

0 hours

48 hours

0 hours

Defrost on demand - S5 temperature’s permitted variation during frost build-up. On 
central plant choose 20 K (=off)

d19

0 K

20 K

20 K

Fans

Fan stop at cutout compressor

F01

no

yes

no

Delay of fan stop

F02

0 min

30 min

0 min

Fan stop temperature (S5)

F04

-50°C

50°C

50°C

Real time clock

Six start times for defrost. 
Setting of hours. 
0=OFF

t01-t06

0 hours

23 hours

0 hours

Six start times for defrost.
Setting of minutes.
0=OFF

t11-t16

0 min

59 min

0 min

Clock - Setting of hours

t07

0 hours

23 hours

0 hours

Clock - Setting of minute

t08

0 min

59 min

0 min

Clock - Setting of date

t45

1

31

1

Clock - Setting of month

t46

1

12

1

Clock - Setting of year

t47

0

99

0

Содержание EKC 202A

Страница 1: ...nication LON RS 485 Type Pt 1000 1000 0 C Ptc 1000 1000 25 C NTC M2020 5000 25 C o06 10 V U 256 V DO1 Imax AC 1 10 A Derated 16 A relay DO2 Imax AC 15 6 A DO3 Imax AC 1 6 A Derated 8 A relay Imax AC 1...

Страница 2: ...2 Instructions RI8JV352 Danfoss 07 2005 EKC 202A B C EKC 202A EKC 202C EKC 202B AU Guld Gold or Oro l max 15 m AU Guld Gold or Oro l max 15 m AU Guld Gold or Oro l max 15 m...

Страница 3: ...r13 10 K 10 K 0 K Aktivering af referenceforskydningen r40 r39 OFF on OFF V rdi for referenceforskydning r40 50 K 50 K 0 K Alarm Forsinkelse p temperaturalarm A03 0 min 240 min 30 min Forsinkelse p d...

Страница 4: ...Pt f ler o15 no yes no Max holdetid efter koordineret afrimning o16 0 min 60 min 20 Kon guration af lysfunktionen rel 4 1 ON under natdrift 2 ON OFF via datakommunikation 3 ON f lger DI funktionen n...

Страница 5: ...ring night operation r13 10 K 10 K 0 K Activation of reference displacement r40 r39 OFF on OFF Value of reference displacement r40 50 K 50 K 0 K Alarm Delay for temperature alarm A03 0 min 240 min 30...

Страница 6: ...for relay 4 1 defrost light 2 alarm o72 defrost Alarm Light Alarm 1 2 2 Service Temperature measured with S5 sensor u09 Status on DI1 input on 1 closed u10 Status on night operation on or o 1 closed...

Страница 7: ...wischen zwei Abtauungen d18 0 hours 48 hours 0 hours Bedarfsgesteuerte Abtauung die S5 Temperatur erlaubt variation bei Eis aufbauung An Centralanlagen w hle 20 K o d19 0 K 20 K 20 K L fter L fterstop...

Страница 8: ...l o02 0 10 0 Netzwerkadresse o03 0 119 0 On O Wechselschalter Service Pin Mitteilung o04 OFF ON OFF Zugangskode 1 s mtliche Einstellungen o05 0 100 0 Angewandter F hlertyp Pt PTC NTC o06 Pt ntc Pt Dis...

Страница 9: ...0 0 2 0 Temps de refroidissement total maxi entre deux d givrages d18 0 hours 48 hours 0 hours D givrage sur demande variation admissible de la temp rature S5 en cas de formation de givre Pour les ins...

Страница 10: ...e u10 Etat du r gime de nuit tout ou rien 1 enclench u13 A chage de la r f rence de r gulation actuelle u28 Etat du relais de refroidissement La commande manuelle est possible mais condition que r12...

Страница 11: ...EKC 202A B C Instructions RI8JV352 Danfoss 07 2005 11...

Страница 12: ...12 Instructions RI8JV352 Danfoss 07 2005 EKC 202A B C...

Отзывы: