Service parameter(s) 22-24
Service parameter(s) 141
32g
23 Valve exercise
Circuit
Setting range
Factory setting
I
ON / OFF
OFF
Exercises the valve to avoid blocking in periods without heat
demand.
ON:
The valve receives a signal to open and close
every third day around noon.
OFF:
The valve exercise is not active.
22 Pump exercise
Circuit
Setting range
Factory setting
I
ON / OFF
ON
Exercises the pump to avoid blocking in periods without heat
demand.
ON:
The pump is switched ON for 1 minute every
third day around noon.
OFF:
The pump exercise is not active.
141 Override input selection
Circuit
Setting range
Factory setting
I
OFF / 1 ... 6
OFF
Choose an unused temperature sensor input for overriding the
schedule for circuit I and / or circuit II.
The override can be activated for comfort or setback mode.
For override the controller's mode must be in 'scheduled
operation'!
OFF: The controller's schedule is not overridden.
1 ... 6:
Select an unused sensor input S1 ... S6 for
the override of the circuit in question.
Connection example
If the override switch has gold-plated contacts, you can
choose one of the following solutions:
Closed switch:
Comfort temperature
Closed switch:
Setback temperature
Changeover switch:
Setback or comfort temperature
Connection example with ECA 9010
(used if the override switch does not have gold-plated
contacts).
16 - Brown
15 - Red
Green (S1 ... S6)
The ECA 9010 module is powered by the system device bus, which
means that the bus must be active. The bus is activated by setting
the controller address to 15 (line 199).