ECL Card settings
(circuit I)
30a
A
Time and date
Section 17
B
System information
Sections 18 & 19
C
Heat curve
Section 20
Setting ranges
Factory settings
Your settings
Slope
0.2 ... 3.4
2.+
See section 20
Parallel displacement
-9 ... 9 K
0 K
See section 20
1
Limit for heating cut-out
10 ... 30 °C
20 °C
See section 21
2
Flow temperature, min. / max. limits
10 ... 150 °C
min. 10, max. 90 °C
See section 22
3
Room temperature influence
0 ... 99 / -99 ... 0
min. 0, max. -40
See section 23
4
Proportional band, Xp
1 ... 250 K
80 K
See section 26
5
Integration time constant, Tn
5 ... 999 sec.
30 sec.
See section 26
6
Running time of the motorized control
valve
5 ... 250 sec.
35 sec.
See section 26
7
Neutral zone, Nz
0 ... 9 K
3 K
See section 26
ECL Card settings
(circuit II)
30b
A
Time and date
Section 17
B
System information
Sections 18 & 19
C
Setting ranges
Factory settings
Your settings
1
Primary storage tank temperature
difference
1 ... 30 K
6 K
See section 27
2
Return temperature difference
1 ... 30 K
4 K
See section 27
3
Max. charging time, M3
5 ... 250 min.
40 min.
4
5
Acceptable temperature deviation
below desired flow temperature
OFF / 1 ... 30 K
5 K
See section 27
6
Acceptable temperature deviation
above the desired flow temperature
1 ... 30 K
5 K
See section 27
7
Time interval before closing M3
1 ... 99 min.
10 min.
See section 27