See or change the start (‘Start2’) of the next comfort period.
$#QQQQNaMQQaaQ
3 13<;BF::
See or change the next start / stop periods, if necessary.
$#QQQQNaMQQaaQ
3./<<<F::
The schedule has always two comfort periods a day. The start and stop times can be set in
half-hourly intervals (30 min.).
2 sec.
Enter the maintenance menus.
Date - time
1000
It is only necessary to set the correct date and time in connection with the first use of the
ECL Comfort 110 controller or after a power break of more than 36 hours (see the chapter
on
Adapting the ECL Comfort 110 controller).
Flow temp. (flow temperature control)
2000
Temp. min. (flow temp. limit, min.)
2177
Setting range
Factory setting
-20 ... 110 °C
10 °C
Set the allowed min. flow temperature for your system. Adjust the factory setting, if
required.
Temp. max. (flow temp. limit, max.)
2178
Setting range
Factory setting
10 ... 150 °C
90 °C
Set the allowed max. flow temperature for your system. Adjust the factory setting, if
required.
The setting for ‘Temp. max.’ has higher priority than ‘Temp. min.’.