Installation Guide
ECA 30 / 31 for ECL Comfort 210 / 210B / 310 / 310B
ECA MENU > ECA factory > ECA clear apps.
Erase all apps. (Erase all applications)
Erase all applications which are in the ECA 30 / 31.
After erasing, the application can be uploaded again.
NO:
The erase procedure is not done.
YES:
The erase procedure is done (await 5 sec.).
After the erase procedure, a pop-up in the display indicates "Copy
application". Choose "Yes".
Hereafter the application is uploaded from the ECL controller. An
upload bar is shown.
ECA MENU > ECA factory > ECA default
Restore factory
The ECA 30 / 31 is set back to factory settings.
Affected settings by the restore procedure:
• Room T offset
• RH offset (ECA 31)
• Backlight
• Contrast
• Use as remote
• Slave addr.
• Connection addr.
• Override addr.
• Override circuit
• Override mode
• Override mode end time
NO:
The restore procedure is not done.
YES:
The restore procedure is done.
ECA MENU > ECA factory > Reset ECL addr.
Reset ECL addr. (Reset ECL address)
If none of the connected ECL Comfort controllers has the address
15, the ECA 30 / 31 can set all connected ECL controllers on the
ECL 485 bus back to address 15.
NO:
The reset procedure is not done.
YES:
The reset procedure is done (await 10 sec.).
The ECL 485 bus related address of the ECL controller is found:
MENU > 'Common controller settings' > 'System' > 'Communication' >
'ECL 485 addr.'
The "Reset ECL addr." cannot be activated if one or more of the
connected ECL Comfort controllers has the address 15.