10  Troubleshooting 

Alarm

In the event of an error message try restarting the installation using the reset button on the control panel.
If restarting the heat pump does not help try rectifying the problem using the table below.

Message

Meaning

Cause

Remedy

LOW PRESS 
ERROR

Low pressure 
error - The com-
pressor stops 
and there is no 
hot water pro-
duction.

Not enough anti-freeze in the 
coolant system. Air in the brine 
system. Blocked filter in the 
brine system.

Fill the refrigerant with the correct 
percentage of anti-freeze and bleed 
using the safety valve on the volume 
container. Check if the strainer needs 
cleaning.

Coolant pump has stopped or 
is running at slow speed.

Take temperature difference 
readings between incoming and 
outgoing coolant. The difference 
should be between approximately 
3-5°C. 

Ice build up in the coolant 
system.

Measure the amount of anti-freeze 
in %, wait until the ice melts, which 
affects the low pressure switch not 
contacting the wiring.

Underfilled cooling system or 

any leaks.

Drain and leak trace as well as filling 
new refrigerant. No refilling of drai-
ned medium.

Blocked or filled drying filter in 
the cooling circuit.

Measure the temperature difference 
of the filter – max 2°C.

HIGH PRESS 
ERROR

High pressure 
error - The com-
pressor stops 
and there is no 
hot water pro-
duction.

Insufficiently opened radiator/
floor loop thermostats. Air in 
the heating system. Blocked 
strainer in the heating system, 
located in the heat pump 
return.

Open radiator / floor loop thermo-
stats. Fill and bleed the heating 
system. Measure delta over the 
heat pump supply and return lines. 
Temperature difference.

Overfilled refrigerant circuit.

Draining the refrigerant circuit and 
refilling with new refrigerant, accor-
ding to the instructions.

Heat transfer fluid pump has 
stopped or is running at slow 
speed.

Check the heart transfer fluid pump.

MOTOR P 
ERROR

Motor protec-
tion error - (Over 
current relay 
compressor or 
brine pump). 
The compressor 
stops and there 
is no hot water 
production.

Phase drop or blown fuse.

Check the fuses and cable terminals 
(power supply to the compressor or 
brine pump).

Poorly tightened electrical 
connections.

Check the electrical connections.

Too low network voltage.

Measure the voltage to the heat 
pump’s electrical connection.

Other alarms;  

See separate manual for the control system.

Содержание DHP-R Eco

Страница 1: ...VMIFI102 Installation instructions Danfoss heat pump DHP R Eco...

Страница 2: ...anty if these instructions are not adhered to during installation or service The English language is used for the original instructions Other languages are a translation of the original instructions D...

Страница 3: ...ng hot water sensor 12 6 5 Connecting sensor for system supply temperature 12 6 6 Connecting external start brine pump passive cooling option 12 6 7 Connecting exchange valve for hot water 12 6 8 Conn...

Страница 4: ......

Страница 5: ...ion because of lack of oxy gen Spaces in which heavy vapour can collect below the level of the air must therefore be well ventilated Refrigerant exposed to a naked flame creates a poi sonous irritatin...

Страница 6: ...al connection must be adhered to the inside of the door Electrical current The terminal blocks are live and can be highly dan gerous due to the risk of electric shock The power supply must be isolated...

Страница 7: ...ead in for communication cable 8 Lead in for incoming supply and sensor 9 Supply pipe sensor 10 Condenser with draining for prim side 11 Return sensor 13 Compressor 14 Instrument panel 15 Electrical c...

Страница 8: ...gas exchanger 4 Supply line hot gas exchanger 5 Heat supply supply line 6 Coolant in to HP 2 3 Required service space To facilitate installation and later tests and maintenance there must be sufficien...

Страница 9: ...es 2 are centred in the insert pipes 1 so that the insulation is distributed equally on all sides Seal the insert pipes 1 with a suitable sealant foam 4 4 Unpacking and installation The heat pump is p...

Страница 10: ...e must be routed in a continuous incline A continuous upwards slope means that the pipe must not slope downwards from the horizontal at any point 5 2 Heating system supply pipe and return pipe Install...

Страница 11: ...erheating protection compressor F3 Control fuse condensation pump F100 Fuse 24 VAC 1 F101 Fuse 24 VDC F102 Fuse 24 VAC 2 X1 Terminal blocks for incoming supply and tempera ture sensor as well as termi...

Страница 12: ...liary modules The two separate 24 VAC circuits must never be con nected to each other or to protective ground The total power load on 24 VAC 1 respectively 24 VAC 2 must not exceed 50VA 6 9 Connecting...

Страница 13: ...n vessel for the coolant is sized according to the manufacturer s instructions Max operating pressure heat source see manufacturer s plate Max 6 bar 7 2 Filling the coolant system WARNING Ethylene gly...

Страница 14: ...ly done by setting switch S2 to manual There is an indicator lamp under the cover of the coolant pump connection terminal box which lights when the rotation direction is correct Check that all connect...

Страница 15: ...ing carried out by As user please ensure that the installer fills in the following information to facilitate servicing PIPE INSTALLATION Date Company Name Tel No ELECTRICAL INSTALLATION Date Company N...

Страница 16: ...refrigerant No refilling of drai ned medium Blocked or filled drying filter in the cooling circuit Measure the temperature difference of the filter max 2 C HIGH PRESS ERROR High pressure error The co...

Страница 17: ...eat transfer fluid bar bar 6 6 6 6 6 6 6 6 Min max temperature5 Cooling circuit C 20 10 20 10 20 10 20 10 Heating circuit6 C 65 20 65 20 65 20 65 20 Pressure switches Low pressure Operating MPa MPa 0...

Страница 18: ......

Страница 19: ......

Страница 20: ...umps AB Box 950 SE 671 29 Arvika www danfoss com If these instructions are not followed during installation operation and maintenance Danfoss Heat Pumps liability according to the applicable warranty...

Отзывы: