12

V

VMIFI102

6.4 

Connecting hot water sensor

Connect the hot water sensor to the designated terminal 
block. The sensor should be positioned a third way up 
from the bottom in the water heater which is supplied with 
incoming cold water. 
See separate manual for the control system.

6.5 

Connecting sensor for system supply 
temperature

The system supply sensor must always be installed on the 
system’s supply pipe after the auxiliary heater. The sensor 
must be positioned so that the heated water has been able 
to mix properly. 
See separate manual for the control system.

6.6 

Connecting external start brine pump 
(passive cooling option)

Potential free connection between terminal blocks 127-
128 that start the brine pump. This function can be used 
for passive cooling from the brine circuit. Connect to the 
incoming brine pipe. 
See separate manual for the control system.

6.7 

Connecting exchange valve for hot 
water

See separate manual for the control system.

6.8 

Connecting room sensor (option)

•  Remove the front cover from the heat pump.
•  Route the room sensor’s connecting cable through the 

opening in the rear piece up to the connecting block.

•  Connect the sensor to the designated terminal block.

 

See separate manual for the control system.

 

 

Note that the room sensor’s connecting voltage is 

extra low protection voltage. Also note that this is an 
active sensor supplied with 24 VAC.

 

 

24 VAC 1 must not be connected together with:

  

• 24 VAC 2

  

• 24 VDC

  

• Other equipment that uses 0-10V control signal

  

• Signal ground GND

 

 

24 VAC 2 must only be used as power supply to:

  

• External equipment that requires 0-10V control

 

   

signal

  

• Auxiliary modules

 

 

The two separate 24 VAC circuits must never be con-

nected to each other or to protective ground.

 

 

The total power load on 24 VAC 1 respectively 24 

VAC 2 must not exceed 50VA.

6.9 

Connecting pressure and/or flow 
switch (option)

Connect the pressure and/or flow switch for the brine side 
to the intended terminal block 123-124 at the same time 
as removing the bridge. When using both the pressure and 
flow switch. these must be connected in series. 
See separate manual for the control system.

6.10  Connecting start/stop auxiliary heater

Start/stop auxiliary heating connected to terminal block 
133-134 (24 VAC) 
See separate manual for the control system.

6.11  Connecting external buzzer

Active alarm produces 24 VAC out on terminal block 135-
136. 
See separate manual for the control system.

6.12  Connecting system pump

Start/stop of the house system pump 24 VAC. 
See separate manual for the control system.

6.13  Connecting control signal for  auxiliary 

heater

See separate manual for the control system.

 

 

24 VAC 1 must not be connected together with:

  

• 24 VAC 2

  

• 24 VDC

  

• Other equipment that uses 0-10V control signal

  

• Signal ground GND

 

 

24 VAC 2 must only be used as power supply to:

  

• External equipment that requires 0-10V control

 

   

signal

  

• Auxiliary modules

 

 

The two separate 24 VAC circuits must never be con-

nected to each other or to protective ground.

 

 

The total power load on 24 VAC 1 respectively 24 

VAC 2 must not exceed 50VA.

Sensor room 0-10 V 

(option)

Exchange valve

Any passive cooling 

brine pump

Any external 

buzzer 24 VAC

Any Start/

stop auxiliary 

heater

Any Pressure 

switch brine 

Flow switch 

(option)

System pump

Analogue control 

signal for auxiliary 

heater

NOTE! Bridge 
removed at pres-
sure switch brine 
Flow switch
Bridged at delivery

Hot water sensor

PT1000

Sensor system sup-

ply temperature

PT1000

Содержание DHP-R Eco

Страница 1: ...VMIFI102 Installation instructions Danfoss heat pump DHP R Eco...

Страница 2: ...anty if these instructions are not adhered to during installation or service The English language is used for the original instructions Other languages are a translation of the original instructions D...

Страница 3: ...ng hot water sensor 12 6 5 Connecting sensor for system supply temperature 12 6 6 Connecting external start brine pump passive cooling option 12 6 7 Connecting exchange valve for hot water 12 6 8 Conn...

Страница 4: ......

Страница 5: ...ion because of lack of oxy gen Spaces in which heavy vapour can collect below the level of the air must therefore be well ventilated Refrigerant exposed to a naked flame creates a poi sonous irritatin...

Страница 6: ...al connection must be adhered to the inside of the door Electrical current The terminal blocks are live and can be highly dan gerous due to the risk of electric shock The power supply must be isolated...

Страница 7: ...ead in for communication cable 8 Lead in for incoming supply and sensor 9 Supply pipe sensor 10 Condenser with draining for prim side 11 Return sensor 13 Compressor 14 Instrument panel 15 Electrical c...

Страница 8: ...gas exchanger 4 Supply line hot gas exchanger 5 Heat supply supply line 6 Coolant in to HP 2 3 Required service space To facilitate installation and later tests and maintenance there must be sufficien...

Страница 9: ...es 2 are centred in the insert pipes 1 so that the insulation is distributed equally on all sides Seal the insert pipes 1 with a suitable sealant foam 4 4 Unpacking and installation The heat pump is p...

Страница 10: ...e must be routed in a continuous incline A continuous upwards slope means that the pipe must not slope downwards from the horizontal at any point 5 2 Heating system supply pipe and return pipe Install...

Страница 11: ...erheating protection compressor F3 Control fuse condensation pump F100 Fuse 24 VAC 1 F101 Fuse 24 VDC F102 Fuse 24 VAC 2 X1 Terminal blocks for incoming supply and tempera ture sensor as well as termi...

Страница 12: ...liary modules The two separate 24 VAC circuits must never be con nected to each other or to protective ground The total power load on 24 VAC 1 respectively 24 VAC 2 must not exceed 50VA 6 9 Connecting...

Страница 13: ...n vessel for the coolant is sized according to the manufacturer s instructions Max operating pressure heat source see manufacturer s plate Max 6 bar 7 2 Filling the coolant system WARNING Ethylene gly...

Страница 14: ...ly done by setting switch S2 to manual There is an indicator lamp under the cover of the coolant pump connection terminal box which lights when the rotation direction is correct Check that all connect...

Страница 15: ...ing carried out by As user please ensure that the installer fills in the following information to facilitate servicing PIPE INSTALLATION Date Company Name Tel No ELECTRICAL INSTALLATION Date Company N...

Страница 16: ...refrigerant No refilling of drai ned medium Blocked or filled drying filter in the cooling circuit Measure the temperature difference of the filter max 2 C HIGH PRESS ERROR High pressure error The co...

Страница 17: ...eat transfer fluid bar bar 6 6 6 6 6 6 6 6 Min max temperature5 Cooling circuit C 20 10 20 10 20 10 20 10 Heating circuit6 C 65 20 65 20 65 20 65 20 Pressure switches Low pressure Operating MPa MPa 0...

Страница 18: ......

Страница 19: ......

Страница 20: ...umps AB Box 950 SE 671 29 Arvika www danfoss com If these instructions are not followed during installation operation and maintenance Danfoss Heat Pumps liability according to the applicable warranty...

Отзывы: