VMBQI102

VMILF102  

Danfoss – 13

Connecting

Note! The maximum load may not exceed 50 VA.

Cooling module

The cooling module is mounted in the electric cabinet on the intended rail . If there is no room, the module can be installed 

in an external, enclosed cabinet and connected with a longer modular cable.

• Connect a modular cable between HP CRM Exp.out and HPC CM Exp.in

Cooling module connections:

Temperature input, T1: Sensor, cooling tank
Temperature input, T2: Sensor, coolant cooler
Temperature input, T3: Sensor, cooling tank outlet
Temperature input, T4: Sensor, cooling circuit

Analogue input 0-10 V, AI1: Signal from dew point sensor, room temperature 0 - 50°C
Analogue input 0-10 V, AI2: Signal from dew point sensor, relative humidity 0-100%

Analogue output 0-10 V, AO1: Signal to cooling circuit pilot valve
Analogue output 0-10 V, AO2: Signal to cooling fans
Relay 24 VAC, DO1: Signal to reversing valve against cooling tank (passive cold)

Exp.in

Exp.out

G

GND

G

0

Y

1

DO1

G0

G0

DO2

G0

DO3

G0

DO4

G0

DO5

G0

24V

AC

T1

AO1

AI2

GND

T2

GND

T3

GND

T4

GND

AI1

GND

GND

GND

AO2

GND

HPC CM

24 VAC

0-10V

0-10V

M

24 VAC

M

24 VAC

24 VAC

24 VAC

24 V

AC 2.1

24 V

AC 2.2

24 VAC 2.1
24 VAC 2.2

G G

0

Y

1

GND

Y

1

24 VAC 2.1

24 V

AC 2.1

24 V

AC 2.2

AO1

24 VAC 2.2

24 VAC 2.1

DO1,2,4

24 VAC 2.2

Pilot valve, 

cooling circuit

Pilot valve,  

alternative connection 

of cooling circuit

Circ . pump,  

coolant cooler

Reversing valve, 

surplus heat

Reversing valve,

 

cooling agent return

cooling tank

Alternative  connection  with 
constant  voltage  feed  for 

2-point 24 VAC reversing valve.

Circ . pump,  

coolant circuit

Dew point sensor

Cooling fans

From Exp.out

Sensor, cooling tank

Sensor, surplus cooler

Sensor, cooling tank outlet

Sensor, cooling circuit

Room temperature

Relative air humidity

Содержание DHP-R 7UA HPC EM

Страница 1: ...VMILF102 DHP R DP Installation instructions Expansion module HPC EM Cooling module HPC CM...

Страница 2: ...VMILF102 2 Danfoss...

Страница 3: ...must not be connected together with 24 VAC 2 24 VDC Other equipment that uses 0 10V control signal Signal ground GND 24 VAC 2 must only be used as power supply to External equipment that requires 0 10...

Страница 4: ...o 086U4229 Connection block item no 086U5121 Other accessories Pilot valve VVL 2 way heat exchanger tap water vvx circulation pump System image Heat exchanger A heat exchanger is connected between the...

Страница 5: ...mp no potential closure maximum 6 A Exp in Connection from HPC RM Exp out Connection to possible additional module Submersible sensor Connect to T1 and GND Circulation pump Connect to DO1 1 to 24 VAC...

Страница 6: ...ter One of the following modular cables Modular cable 0 3 m item no 086U4227 Modular cable 1 1 m item no 086U4228 Modular cable 10 0 m item no 086U4229 Connection block item no 086U5121 System image S...

Страница 7: ...Temperature input T1 Sensor water heater Temperature input T2 Transmitter hot water return Analogue output 0 10 V AO1 Relay DO1 Signal to electric cartridge hot water no potential closure maximum 6A E...

Страница 8: ...les Modular cable 0 3 m item no 086U4227 Modular cable 1 1 m item no 086U4228 Modular cable 10 0 m item no 086U4229 Connection block item no 086U5121 Other accessories Shunt valve circulation pump Sys...

Страница 9: ...tial closure maximum 6A Exp in Connection from HPC RM Exp out Connection to possible additional module Sensor shunt temperature Connect to T1 and GND Circulation pump Connect to DO1 1 to 24 VAC 2 1 Co...

Страница 10: ...e inputs Input Shunt TWC WCS T1 Shunt temperature HW heater temp WCS temperature T2 HW return temp Analogue outputs Outputs Shunt TWC WCS AO1 Control signal Control signal Relay outputs Outputs Shunt...

Страница 11: ...to rise more heat pumps are started The valve for active cooling changes its mode and disconnects the drill hole Therefore the cooling agent only circulates through the cooling tank and heat pump so t...

Страница 12: ...rn line of the cooling tank Transmitter coolant cooler A strap on temperature detector is connected on the return line from the coolant cooler as close to the cooler as pos sible Heat circuit Cooling...

Страница 13: ...ooling circuit pilot valve Analogue output 0 10 V AO2 Signal to cooling fans Relay 24 VAC DO1 Signal to reversing valve against cooling tank passive cold Exp in Exp out G GND G0 Y1 DO1 G0 G0 DO2 G0 DO...

Страница 14: ...the pilot valve terminal G to 24 VAC 2 1 Connect the pilot valve terminal G0 to 24 VAC 2 2 Cooling fans Connect AO2 to the signal input of the cooling fan Connect GND to the cooling fan GND Voltage fe...

Страница 15: ...ircuit 0 to 100 C Analogue inputs Input Use AI1 Room temperature 0 to 50 C AI2 Relative humidity 0 to 100 Analogue outputs Outputs Use AO1 Control valve cooling circuit AO2 Cooling fans Relay outputs...

Страница 16: ...VMILF102...

Отзывы: