Connecting
⚠
⚠
⚠
Note! The maximum load may not exceed 50 VA.
Cooling module
The cooling module is mounted in the electric cabinet on the intended rail . If there is no room, the module can be installed
in an external, enclosed cabinet and connected with a longer modular cable.
⚠
• Connect a modular cable between HP CRM Exp.out and HPC CM Exp.in
Cooling module connections:
Temperature input, T1: Sensor, cooling tank
Temperature input, T2: Sensor, coolant cooler
Temperature input, T3: Sensor, cooling tank outlet
Temperature input, T4: Sensor, cooling circuit
Analogue input 0-10 V, AI1: Signal from dew point sensor, room temperature 0 - 50°C
Analogue input 0-10 V, AI2: Signal from dew point sensor, relative humidity 0-100%
Analogue output 0-10 V, AO1: Signal to cooling circuit pilot valve
Analogue output 0-10 V, AO2: Signal to cooling fans
Relay 24 VAC, DO1: Signal to reversing valve against cooling tank (passive cold)
Exp.in
Exp.out
G
GND
G
0
Y
1
DO1
G0
G0
DO2
G0
DO3
G0
DO4
G0
DO5
G0
24V
AC
T1
AO1
AI2
GND
T2
GND
T3
GND
T4
GND
AI1
GND
GND
GND
AO2
GND
HPC CM
24 VAC
0-10V
0-10V
M
24 VAC
M
24 VAC
24 VAC
24 VAC
24 V
AC 2.1
24 V
AC 2.2
24 VAC 2.1
24 VAC 2.2
G G
0
Y
1
GND
Y
1
24 VAC 2.1
24 V
AC 2.1
24 V
AC 2.2
AO1
24 VAC 2.2
24 VAC 2.1
DO1,2,4
24 VAC 2.2
Pilot valve,
cooling circuit
Pilot valve,
alternative connection
of cooling circuit
Circ . pump,
coolant cooler
Reversing valve,
surplus heat
Reversing valve,
cooling agent return
cooling tank
Alternative connection with
constant voltage feed for
2-point 24 VAC reversing valve.
Circ . pump,
coolant circuit
Dew point sensor
Cooling fans
From Exp.out
Sensor, cooling tank
Sensor, surplus cooler
Sensor, cooling tank outlet
Sensor, cooling circuit
Room temperature
Relative air humidity