6
Piping installation
Caution
To prevent leaks, ensure that there are no stresses in the connecting
lines
Caution
Pipe installation must be carried out by an authorised installer
Caution
Ensure that the pipe installation is carried out in accordance with the
dimensions and connection diagrams
Caution
Bleed valves should be fitted if necessary
6.1
Safety valves
Warning
Radiator systems with a closed expansion tank must also be equipped
with an approved manometer and safety valve. The safety valve
should be to a minimum of DN 20 and have a maximum of 6 bar open-
ing pressure, or according to country-specific requirements.
Warning
The overflow pipes from the safety valve must not be closed off. The
pipes should discharge into an outlet in a frost-free area.
Warning
The connecting pipe between the expansion tank and the safety valve
must slope continuously upwards. A continuous upwards slope means
that the pipe must not slope downwards from the horizontal at any
point.
Caution
Cold and hot water pipes and overflow pipes from safety valves must
be made of heat-resistant and corrosion-resistant material, e.g. cop-
per.
Installation Guide
DHP-M
Danfoss Heating Solutions
VIJSW102
17
Содержание DHP-M
Страница 1: ...MAKING MODERN LIVING POSSIBLE Installation Guide DHP M www heating danfoss com...
Страница 32: ...Installation Guide DHP M VIJSW102 Danfoss Heating Solutions 32...
Страница 33: ...Installation Guide DHP M Danfoss Heating Solutions VIJSW102 33...
Страница 34: ...Installation Guide DHP M VIJSW102 Danfoss Heating Solutions 34...
Страница 35: ...Installation Guide DHP M Danfoss Heating Solutions VIJSW102 35...