Installation and Operation Guide | DGS Modbus
© Danfoss | ADAP-KOOL® | 2016.12
20 | RS8HJ102 |
Service
Read out of refrigerant (Gas) for the DGS is used for
Value according to "Danfoss standard list".
1
42
N
-
Refrigerant
Gas Full scale in ppm
0
32000
0
ppm
Fullscale ppm
Hours since last calibration
0
32000
0
hours
Burning hours
Status of the sensor warm up period
0 =Ready
1 = Warming Up
0
1
0
-
Startup flag
When cleared, clears calibration due alarm and resets the
burning hours parameter
0 = Calibration valid
1 = Calibration due
0
1
0
-
Reset cal
Failsafe operation of the Relay
0 = Not failsafe
1 = Failsafe
0
1
0
-
Relay failsafe
Enables Manual control of Relays.
Automatically falls back to Off after 10 min.
0
1
0
-
Maunal Control
Status of the high alarm relay
0 = No alarm signal
1 = alarm signal
0
1
0
-
Alarm Relay
Status of the buzzer
0 = inactive
1 = active
0
1
0
-
Sounder
Status of the red LED
0 = off
1 = on
0
1
0
-
Red LED
Status of the green LED
0 = off
1 = on
0
1
0
-
Green LED
Alarms
Limit alarm
0 = Alarm not active
1 = Alarm, gas limit exceeded
0
1
0
-
Limit alarm
Sensor saturated
0 = OK
1 = Fault. Out of range under test
0
1
0
-
Sensor saturated
Sensor out
0 = OK, sensor in place
1 = Fault, Sensor out or removed
0
1
0
-
Sensor out
Calibrate sensor
0 = OP, Sensor not due for calibration
1 = Warning, Due for calibration
0
1
0
-
Calibrate sensor
Warning limit alarm
0 = OK, Gas level below warning level
1 = Warning, Gas level above warning level and delay expired
0
1
0
-
Warning limit al.