Strengregulator ASV-PV, ASV-PV+ anvendes 

sam-men med afspærrings- og måleventil 

ASV-M til regulering af differenstryk i 

stigstrenge med radiatorventiler med 

forindstilling. 

ASV-PV, ASV-PV+ anvendes sam-men med 

indreguleringsventil ASV-I, til regulering 

af differenstryk og flow i stig-strenge 

med radiatorventiler uden for-indstilling 

(P/Q - regulering) (fig. 1). ASV-PV, ASV-PV+ 

holder differenstrykket over stig- strenge 

konstant.

Maks. arbejdstryk: ..................................... 16 bar 

Differenstryk

over ventilen ............. 0,1-1,5 bar (10-150 kPa)

Maks. gennemstrøm-

ningstemperatur ....................................... 120 °C

Ventil-

størrelser

Indvendigt

gevind

Udvendigt

gevind

DN 15

Rp ½

G ¾ A

DN 20

Rp ¾

G 1 A

DN 25

Rp 1

G 1¼ A

DN 32

Rp 1¼

G 1½ A

DN 40

Rp 1½

G 1¾ A

DN 50

-

G 2½

Impulsledning: G 1⁄16

Montering

ASV-PV, ASV-PV+ monteres i strengens 

returled-ning med flow’et strømmende i 

den ind-støbte pils retning (fig. 3).

Det anbefales at montere et FV filter i 

installationens fremløb. 

Impulsledningen monteres på strengens 

fremløb fx via en ASV-I eller en ASV-M ventil 

og gennemskylles inden den monteres på 

ASV-PV, ASV-PV+ regula til-slutning 

(fig. 2).

ASV-PV, ASV-PV+ monteres iøvrigt efter 

forhol-dene.

For at undgå lækage, skal ventiler med 

nippel/omløber efterspændes når 

anlægget er kommet i drift.

Afspærring

ASV-PV, ASV-PV+ kan afspærre strengen 

ved at dreje håndtaget (1, fig. 2) med uret 

til stop.

Trykprøvning

Maks. prøvetryk:  ........................................ 25 bar

Bemærk:

 Under trykprøvning skal sikres, 

at det statiske tryk er ens på begge sider af 

membranen. Det betyder, at impulsledningen 

skal tilsluttes og eventuel nåleventil skal 

være åben. Hvis ASV‑P/PV eller ASV‑PV+ 

er installeret i forbindelse med ASV‑M, kan 

begge ventiler være åbne eller lukkede 

(begge ventiler skal være i samme possition). 

Hvis ASV‑P/PV eller ASV‑PV+ er installeret 

i forbindelse med ASV‑I, skal begge 

ventiler være åbne. Hvis denne instruktion 

ikke overholdes, vil membranen på den 

automatiske balanceventil ødelægges.

Indstilling

 

ASV-PV kan indstilles til at regulere 

differenstryk mellem 0,05 og 0,25 bar  

(5 og 25 kPa), ASV-PV+ mellem  

0,2 og 0,4 bar (20 og 40 kPa). ASV-PV er ved 

leveringen indstillet på 0,1 bar (10 kPa), 

ASV-PV+ på 0,3 bar (30 kPa). Indstil-lingen 

kan ændres med 0,01 bar (1 kPa) ved at 

dreje indstillingsspindlen (2, fig. 2) 

1 omgang. Drejes spindlen med uret øges 

indstillingen og omvendt.

Hvis indstillingen ikke kendes, drejes 

spindlen med uret til stop. Regulatoren er 

nu indstillet på ASV-PV 0,25 bar 

(25 kPa), på ASV-PV+ 0,4 bar (40 kPa). 

Herefter drejes spindlen mod uret “n”

antal omgange indtil onsket indstilling, 

fig. 6.

Bemærk:

 

Spindeln må ikke drejes mere end 

20 omgange tilbage, idet den ellers går ud af 

indgreb.

Aftapning og påfyldning af vand kan fo-

retages gennem aftapningshanen (luk-ket 

fig. 4-1, åben fig. 4-2)

Opstart

Når der fyldes vand på systemet, skal 

afspærringsventilen i fremløbet (ASV-M/I) 

være lukket. Systemet kan fyldes ved 

at åbne afspærringsventilen i ASV-P/

PV/PV+ i returledningen, eller gennem 

aftapningshanen på ASV-P/PV/PV+. 

Systemet skal udluftes på det højeste sted.

NB. Hvis denne procedure ikke følges, kan 

ASV-PV, ASV-PV+ blive stående i lukke 

position.

Fejlfinding 

Kontroller følgende hvis streng-regulatoren 

ikke fungerer korrekt:
1.  Er flowretningen gennem ventilen 

korrekt?

2.  Er impulsledningen monteret korrekt 

og evt. nåleventiler åbne?

3.  Er regulatorens afspærring åben?

Tilbehør .....................................................

Best. nr.

Impulsledning, 1,5 m  ..................... 

003L8152

Impulsledning, 5 m  ......................... 

003L8153

Målestuds for

aftapningshane  ................................ 

003L8143

Isolering

Den styroporemballage som ventilen er 

leveret i, kan anvendes som isolerings-

kappe ved temperaturer op til 80 °C.

Automatic balancing valves ASV-PV and 

ASV-PV+ are used together with shut-off 

and measuring valve ASV-M to control the 

differential pressure in risers where the 

radiator valves have presetting facilities. 

ASV-PV, ASV-PV+ are also used together 

with adjustment valve ASV-I to control 

the differential pressure and flow in 

risers where the radiator valves have no 

presetting facilities (P/Q control), (fig. 1).

ASV-PV, ASV-PV+ maintain constant 

differential pressure across the riser.

Max. working pressure  ........................... 16 bar 

Differential pressure

across valve ............. 0.1 - 1.5 bar (10-150 kPa) 

Max. flow temperature ............................ 120 °C

Valve size

Internal 

thread

External 

thread

DN 15

Rp ½

G ¾ A

DN 20

Rp ¾

G 1 A

DN 25

Rp 1

G 1¼ A

DN 32

Rp 1¼

G 1½ A

DN 40

Rp 1½

G 1¾ A

DN 50

-

G 2½

Impulse line: G 1⁄16

Installation 

ASV-PV and ASV-PV+ must be installed in 

the return pipe. The flow must be in the 

direction of the cast-in arrow (fig. 3).

It is recommended that an FV filter be 

installed in the system supply pipe. The 

impulse tube must be fitted on the flow 

pipe, e.g. via an ASV-I or an ASV-M valve.

The tube must be flushed through before 

being fitted on the + connection of the 

ASV-PV or ASV-PV+ automatic balancing 

valves (fig. 2).

ASV-PV or ASV-PV+ must in addition be 

installed as determined by installation 

conditions. When the system has been in 

use for some time, the connections with 

external threads should be tightened once 

again to minimize the risk for leakage.

Shut-off 

Turning the ASV-PV or ASV-PV+ knob fully 

clockwise will shut off the riser (1, fig. 2).

Pressure testing

Max. test pressure  ...................................  25 bar

Note:

 

When pressure testing you must secure 

that both sides of the membrane have the 

same static pressure. That means the impulse 

tube must be connected and any needle 

valves must be open. If ASV‑P/PV or ASV‑PV+ 

is installed in combination with ASV‑M both 

valves can be open or closed (both valves 

must be in the same position!). If ASV‑P/PV or 

ASV‑PV+ is installed in combination with ASV‑

I both valves must be open. If this instruction 

is ignored, the membrane of the automatic 

balancing valve might be damaged.

Setting/adjustment

 

ASV-PV can be set to control the differential 

pressure between 0.05 and 0.25 bar (5 and 

25 kPa), while ASV-PV+ between 0.2 and 0.4 

bar (20 and 40 kPa). ASV-PV is factory-set at 

0.1 bar (10 kPa), while ASV-PV+ at 0.3 bar 

(30 kPa). The setting can be changed by 

0.01 bar (1 kPa) by turning the setting 

spindle (2, fig. 2) one full turn. Turning the 

spindle clockwise increases the setting; 

turning it counterclockwise reduces the 

setting.

If the setting is not known, turn the spindle 

fully clockwise. The setting on ASV-PV is 

now 0.25 bar (25 kPa) and on ASV-PV+ 

0.4 bar (40 kPa). Now turn the spindle a 

number of times (“n”) until the required 

setting is obtained (fig. 6). 

Note:

 

Do not turn the spindle more than 20 

turns as it will become disengaged.

The cock (closed, fig. 4‑1 ‑ open, fig. 4‑2) can 

be used for water tapping and filling.

DANSK

ENGLISH

Содержание ASV-PV

Страница 1: ...0 35 0 65 0 90 6 0 19 0 34 0 63 0 88 7 0 18 0 33 0 61 0 86 8 0 17 0 32 0 59 0 84 9 0 16 0 31 0 57 0 82 10 0 15 0 30 0 55 0 80 11 0 14 0 29 0 53 0 78 12 0 13 0 28 0 51 0 76 13 0 12 0 27 0 49 0 74 14 0...

Страница 2: ...eng regulatoren ikke fungerer korrekt 1 Er flowretningen gennem ventilen korrekt 2 Er impulsledningen monteret korrekt og evt n leventiler bne 3 Er regulatorens afsp rring ben Tilbeh r Best nr Impulsl...

Страница 3: ...kPa ASV PV 0 2 und 0 4 bar 20 bis 40 kPa eingestellt werden ASV PV ist bei Lieferung auf 0 1 bar 10 kPa ASV PV 0 3 bar 30 kPa eingestellt Die Einstellung wird pro Umdrehung der Einstellspindel 2 Abb 2...

Страница 4: ...tillsammans med avst ngningsventit ASV M eller inregleringsventil ASV I f r reglering av differenstrycket i stammar med radiatorventiler fig 1 ASV PV ASV PV konstanth ller differenstrycket verstammen...

Страница 5: ...iilit t ysin auki 3 Onko s timen sulkulaite auki Tarvikkeet Tilausnro Impulssijohto 1 5 m 003L8152 Impulssijohto 5 m 003L8153 Mittayhde tyhjennyshanaan 003L8143 Eristys Venttiilin styrox pakkausta voi...

Страница 6: ...wskaz wek zegara 1 rys 2 Pr ba ci nieniowa Maks ci nienie pr bne 25 bar w Uwaga Podczas pr by ci nieniowej nale y sprawdzi czy ci nienie statyczne po obu stronach membrany jest takie samo Oznacza to...

Страница 7: ...lnou ot ku Ot en v etene ve sm ru hodinov ch ru i ek zvy uje nastaveni ot en proti sm ru hodinov ch ru i ek nastaven sni uje Nen li nastaven zn mo vyto te v eteno upln ve sm ru hodinov ch ru i ek V t...

Страница 8: ...te el muelle en sentido de las agujas del reloj El ajuste en ASV PV es ahora 0 25 bar 25 kPa y en ASVPV 0 4 bar 4 kPa Gire ahora el muelle un n mer de vuelta n hasta ontener el ajuste requerido Nota N...

Страница 9: ...t interior Filet exterior DN 15 Rp G A DN 20 Rp G 1 A DN 25 Rp 1 G 1 A DN 32 Rp 1 G 1 A DN 40 Rp 1 G 1 A DN 50 G 2 Tubul de impuls G 1 16 Montare Robinetele ASV PV i ASV PV trebuie instalate pe retur...

Страница 10: ...10 VI A1 I2 1T Danfoss 12 2007 73693410 DH SMT SI DN50 G 2 1 2...

Страница 11: ......

Страница 12: ......

Отзывы: