background image

4 | © Danfoss | 2016.10

VI.HU.K1.0E

AME 55 QM

ENGLISH

Safety Note

To avoid injury of persons and damages 
to the device, it is absolutely necessary to 
read and observe these instructions 

carefully.

Necessary assembly, start-up, and maintenance 
work must be performed by qualified and 
authorized personnel only.

Prior to assembly and depressurizing the system.

Please comply with the instructions of the system 
manufacturer or system operator.

Do not remove the cover before the 

power supply is fully switched off.

Disposal instruction

This product should be dismantled 

and its components sorted, if possible, 

in various groups before recycling or 

disposal. 

Always follow the local disposal regulations.

Mounting 

Fix the actuator on the valve 

Wiring 

Do not touch anything on the PCB!

Switch off the power line before wire 

the actuator! Lethal voltage!

Wire the actuator according to the wiring 

diagram.

Control signal

Control signal from the controller must be 

connected to terminals Y (input signal) and SN 

(common) on the AME printed board.

Output signal
Output signal from the terminal X can be 

used for indication of the current position. 

Range depends on the DIP switch settings.
Supply voltage

Supply voltage (24 V~ -15 to +10%, 50 Hz) must be 

connected to the terminals SN and SP.

DIP switch settings 

U

I

2 V_--- V

0 V_--- V

Direct

Inverse

---

Sequential

0(2)_5(6) V

5(6)_10 V

Proportional

3 point/RL

LOG. flow

LIN. flow

100 % k

VS

RED. k

VS

Reset

Reset

 Factory settings:

ALL switches are on OFF position!

 

 

Note:

 

All combinations of DIP switches are 

allowed. All functions that are selected are added 

consecutively. There is only one logic override of 

functionalities i.e. the switch No.6 Proportional/3 

point, which sets actuator to ignore control signal 

and works as a “simple” 3-point actuator.

SW 1: U/I 

 

Factory setting:

voltage control signal (0-10 V).

SW 2: 2-10 V/0-10 V 

 

Factory setting is: 

2-10 V.

SW 3: Direct/Inverse 

 

Factory setting is:

 

DIRECT

SW 4: ---/Sequential 

❹ ④

 

Two actuators can be set to work parallel with one 

control signal. If the SEQUENTIAL is set than an 

actuator responds to split control signal (see 0(2) V 

… 5(6 V) / 6(6) V … 10 V).

 

Note:

 

This combination works in combination 

with switch No.5: 0(2) V … 5(6 V) / 6(6) V … 10 V

SW 5: 0(2) V … 5(6 V)/6(6) V … 10 V 

❹ ⑤

  

 

Note:

 

This function is available if switch No.4:  

--- / Sequential is set.  

SW 6: Proportional/3 point 

❹ ⑥

 

When DIP 6 is OFF:

actuator needs to perform self 

stroking prior changing DIP 6 to ON.

Output signal depends on DIP 2, 3&5 setting.

Actuator can operate in modulating (DIP 6 to OFF) 
or in “simple” 3-point mode, if the 3-point function 
is selected (DIP 6 to ON). 

Connect power supply on terminals SN and SP 
terminals.

DIP 6 factory setting is OFF for modulating 
operation.

Actuator’s stem will run to its totally extended 
or retracted position by bridging SN signal to 
terminals 1 or 3 and will remain in this position as 
long as potential is present. 

Set DIP 6 to ON for operating actuator in 3 point 
mode.

Look carefully wiring diagram as wiring is different 
for controllers with triac output (ECL) in caparison 
to controllers with relay output.

 

Note: 

If 3 point function is selected actuator 

does not respond to any control signal on port Y. It 

only rises and lowers spindle if power is supplied on 

port 1 or 3.

SW 7: LOG flow/LIN flow 

❹ ⑦

 

Large AB-QM valve has linear characteristic.  

With setting switch to LIN flow the characteristic 

remains linear. With setting switch to LOG flow the 

characteristic of actuator is modified the way that 

actuator and valve work together as valve with LOG 

characteristic.

 

Factory setting:

LOG. Flow (characteristic of valve is unchanged)

SW 8: 100% K

VS

/RED. K

VS 

❹ ⑧

 

To be set on OFF position.

SW 9: Reset

 

❹ ⑨

 

After the actuator has been connected to power 

supply, the actuator will start the self-adjustment 

procedure. The indicator LED flashes until self 

adjustment is finished. The duration depends 

on the spindle travel and will normally last a few 

minutes. The stroke length of the valve is stored 

in the memory after self adjustment has been 

completed. To restart self adjustment, change the 

position of RESET switch  (switch No.9). If the supply 

voltage is switched off or falls below 80% in more 

than 0.1s, the current valve position will be stored 

in the memory and all data remain saved in the 

memory also after a power supply cut-out.

Function test

The indicator light shows whether the positioner is 

in operation or not. Moreover, the indicator shows 

the control status and faults.

Constant light

-  normal operation

No light 

-  no operation or no power supply

Intermittent light (1 Hz)  

-  self adjusting-mode

Intermittent light (3 Hz): 

-  power supply too low

-  insufficient valve stroke (<20 s)

-  end-position cannot be reached.

Part Name

Hazardous Substances Table

Lead (Pb)

Mercury (Hg)

Cadmium

 (Cd)

Hexavalent Chromium 

(Cr(VI))

Polybrominated biphenyls 

(PBB)

Polybrominated diphenyl ethers 

(PBDE)

Reducer guide

X

O

O

O

O

O

Holder nut

X

O

O

O

O

O

Position indicator

X

O

O

O

O

O

Bush spring

X

O

O

O

O

O

Limiters

X

O

O

O

O

O

Gears

X

O

O

O

O

O

O:  Indicates that this hazardous substance contained in all of the homogeneous material for this part is below the limit requirement in GB/T 26572;
X:  Indicates that this hazardous substance contained in at least one of the homogeneous material for this part is above the limit requirementw in GB/T 26572;

Содержание AME 55QM

Страница 1: ...NGLISH AME 55 QM www danfoss com Page 4 DEUTSCH AME 55 QM www danfoss de Seite 5 FRAN AIS AME 55 QM www danfoss fr Page 6 AME 55 QM www danfoss ru 7 AME 55 QM www danfoss com cn 8 AME 55 QM Operating...

Страница 2: ...m 1 2x 2x 5 95 RH no condensing MAINTENANCE FREE SN 0 V Neutral SP 24 VAC Power supply Y 0 2 10 V Input 0 4 20 mA 1 0 V Input 3 X 0 2 10 V Output Proportional 3 point RL 2 AUTO 4 6mm 1mm 13 mm 4 mm 12...

Страница 3: ...Danfoss 2016 10 3 VI HU K1 0E AME 55 QM SN 0 V Neutral SP 24 VAC Power supply Y 0 2 10 V Input 0 4 20 mA 1 24 VAC Input 3 X 0 2 10 VDC Output Proportional 3 point RL 2...

Страница 4: ...ON Connect power supply on terminals SN and SP terminals DIP 6 factory setting is OFF for modulating operation Actuator s stem will run to its totally extended or retracted position by bridging SN sig...

Страница 5: ...nweis Diese Funktion steht zur Verf gung wenn Schalter Nr 4 auf Sequential eingestellt ist SW 6 Proportional 3 Punkt WennderDIP 6istAUFStellmotor mussVentilhubvordem ndernder DIP6aufON Ausgangssignali...

Страница 6: ...tion est disponible si la commande 4 S quentiel est r gl e SW 6 Proportionnel 3 points LorsqueleDIP6estDEActuateurdoit ex cuterautor gulationavantleDIP enperp tuelle volution6surON Signaldesortied pen...

Страница 7: ...2 V_5 6 V 5 6 V_10 V 3 RL 100 Kvs Red Kvs OFF DIP 6 SW1 U I 0 10 B SW2 2 10B 0 10 B 2 10 B SW3 SW 4 0 2 5 6 6 6 10 5 0 2 5 6 6 6 10 SW 5 0 2 V 5 6 V 6 6 V 10 V 4 SW 6 DIP 6 DIP 2 35 DIP6 6 OFF 3 3 6...

Страница 8: ...anies Danfoss and the Danfoss logotype are trademarks of Danfoss A S All rights reserved AME 55 QM AME55 56 PCB AME Y SN X SN 24V 15 10 50Hz SN SP 24 V AC 24 V Connect via safety isolating transformer...

Отзывы: