Actuator Electrical Settings 

Prior to commissioning, the settings for the 
input und output signals and for the final 
positions must be carried out.  
Prior to any settings, dismount the 
cover 

.

Switch Designations

 Pushbutton S1

 Switch S2

Switches 5, 6 

Switch 5 must be on “OFF”.
Switch 6 has no function.

Setting the Output Signal

The output signal is proportional to the 
actuating stroke.
Setting of the switch 

S2

, see 

⓮①

.

Setting the Input Signal

Connecting the lines to the terminal strip 
determines the “current” or “voltage” 
input signal, see “Electrical Connection 
Diagram”, 

Setting of 0 or 4 mA, 0 or 2 V, see 

⓮②

.

Setting the Final Positions

When the stroke is set (see 

), the 

final positions “Valve OPEN” and “Valve 
CLOSED” must be equalized with current 
and voltage values 0(4) - 20 mA, 0(2) - 10 V.

Valves VFG.., AFQM 6

Setting the final position “Valve 
CLOSED” 

  Set switches 1 and 2 

  Press pushbutton 

 until the valve 

 

is completely closed and the direction 
indicator 

 stops.

  Press pushbutton 

 The final position “Valve CLOSED” is set.

Setting the final position “Valve 
OPEN” 

  Set switches 1 and 2 

.

  Press pushbutton 

 until the valve 

 

is completely open and the direction 
indicator 

 stops. 

  Press pushbutton 

 The final position “Valve OPEN” is set. 

  Set switch 1 to standard mode 

.

  Unscrew the stroke limiting screw 

 by 

one turn. 

 The setting of the final positions for the 

valves VFG.., AFQM 6 is completed.

  Set the assignment of the effective 

direction for the input and output 
signals, see 

Setting the Final Positions for 
valves VFU 2 

In contrary to the valves VFG .., AFQM6, the 
valve VFU 2 

 has a reversed closing 

direction. 
The valve VFU 2 is opened by the safety 
return function.

Setting the final position “Valve 
OPEN” (VFU 2) 

  Set switches 1 and 2 

  Press pushbutton 

 until the valve 

 

is completely open and the direction 
indicator 

 stops. 

  Press pushbutton 

 The final position “Valve OPEN” (VFU 2) 

is set.

Setting the final position “Valve 
CLOSED” (VFU 2) 

  Set switches 1 and 2 

  Press pushbutton 

 until the valve 

 

is completely closed and the direction 
indicator 

 stops. 

  Press pushbutton 

 The final position “Valve OPEN” is set. 

  Set switch 1 

 The setting of the final positions for the 

valves VFU 2 is completed.

  Set the assignment of the effective 

direction for the input and output 
signals, see 

Assignment of the effective 
direction for the input and output 
signals 

Setting of switch 2 

Then, remount cap nut and cover.

Dismounting of Valve and 
Actuator 

21

Danger
Danger of injury by steam or hot water! 

Valve without actuator is open 

, sealing 

 is in the actuator.

It is absolutely necessary to depressurize 
system prior to dismounting.
Carry out dismounting in reverse order as 
mounting.

Installation Guide 

AME 410, AME 413

DEN-SMT/SI 

VI.AA.R4.6Z 

Danfoss Heating 

Содержание AME 410

Страница 1: ...danfoss com Page 5 DEUTSCH Elektrischer Stellantrieb AME 410 413 www iwk danfoss de Page 7 FRANCAIS Servomoteur lectrique AME 410 413 www danfoss fr Page 9 POLSKI Si ownik elektryczny AME 410 413 www...

Страница 2: ...32 40 50 65 80 VFG VFU 2 L mm 130 250 260 280 200 230 290 310 VFG 2 VFG 21 VFG 25 VFGS 2 B 212 212 238 238 240 240 275 275 kg 7 9 10 13 17 22 33 41 VFU 2 B mm 95 95 106 106 123 123 135 135 C 311 311...

Страница 3: ...switches 0 4 20 mA 0 2 10 V Output controller Power supply 3 mm 15 20 25 32 40 50 65 80 VFG 2 VFG 21 VFG 25 mm 6 6 6 8 8 12 12 18 AFQM 12 18 AFQM 6 8 12 VFU 2 8 8 8 10 10 14 14 20 21 ON OFF 5 6 20 mA...

Страница 4: ...OFF 2 1 ON OFF 2 1 ON OFF 1 ON OFF 2 1 VFG AFQM 6 VFG AFQM 6 VFU 2 VFU 2 ON OFF 2 ON OFF 2 ON OFF 2 ON OFF 2 20 mA 10 V 0 2 4 0 100 Stroke Hub Course Skok 20 mA 10 V 0 2 4 0 100 Stroke Hub Course Sko...

Страница 5: ...swise in 3 steps up to the maximum torque Actuator and Valve Installation The actuator must only be mounted with the stem retracted Stroke indicator must be in position On delivery the stem is retract...

Страница 6: ...he stroke limiting screw by one turn The setting of the final positions for the valves VFG AFQM 6 is completed Set the assignment of the effective direction for the input and output signals see Settin...

Страница 7: ...h use beachten Flansche in der Rohr leitung m ssen parallel Dichtfl chen sauber und ohne Besch digung sein Ventil einbauen Schrauben ber Kreuz in 3 Stufen bis zum max Drehmoment anziehen Montage Stell...

Страница 8: ...e zum Stillstand kommt Taster dr cken Endlage Ventil Endlage Ventil AUF einstellen Schalter 1 und 2 einstellen Taster dr cken bis das Ventil ganz ge ffnet ist und die Laufrichtungsanzeige zum Stillsta...

Страница 9: ...n croix jusqu au couple de rotation max Montage moteur et vanne Uniquement monter le moteur avec la tige r tract e L indication de course doit tre en position Lors de la livraison la tige est r tract...

Страница 10: ...ce que la vanne soit totalement ouverte et l indicateur de sens de fonctionnement soit arr t Presser la touche La position fin de course vanne ouverte est r gl e Positionner l interrupteur 1 sur r gl...

Страница 11: ...ie pod uszczelki czyste i bez uszkodze Zamontowa zaw r Dokr ca przeciwleg e nakr tki w 3 krokach do osi gni cia maksymalnego momentu Monta si ownika i zaworu Aby si ownik m g by zamontowany musi mie c...

Страница 12: ...ozycji kra cowej Zaw r otwarty Ustaw prze cznik 1i 2 Naciska przycisk do ca kowitego otwarcia zaworu i zatrzymania wska nika poziomu Nacisn przycisk Pozycja kra cowa Zaw r otwarty zosta a nastawiona N...

Страница 13: ...ME 41 15 80 120 C 15 80 120 C VFGS 2 3 100 STB STW SDB AME 413 Input controller Output stroke Power supply Valve closed VFU2 Open VFU2 End switsches Valve Open VFU2 closed VFU2 Installation Guide AME...

Страница 14: ...S1 S2 5 6 5 6 S2 0 4 0 2 0 4 20 0 2 10 VFG AFQM 6 1 2 1 2 1 VFG AFQM 6 VFU 2 VFG AFQM6 VFU 2 VFU 2 VFU 2 1 2 VFU 2 VFU 2 1 2 1 VFU 2 2 21 Installation Guide AME 410 AME 413 DEN SMT SI VI AA R4 6Z Danf...

Страница 15: ...0 C DN 15 80 120 C VFGS 2 2 100Nm STB STW SDB AME 413 Input controller Output stroke Power supply Valve closed VFU2 Open VFU2 End switsches Valve Open VFU2 closed VFU2 VFU 2 Valve stroke S1 S2 5 6 5 O...

Страница 16: ...10V VFG AFQM 6 1 1 2 2 3 1 1 1 2 2 3 4 1 5 VFG AFQM 6 VFU 2 VFG AFQM6 2 VFU2 VFU 2 VFU2 1 1 2 2 3 VFU2 VFU 2 1 1 2 2 3 4 1 VFU2 5 2 Stroke 21 Installation Guide AME 410 AME 413 DEN SMT SI VI AA R4 6Z...

Страница 17: ...17 17 Installation Guide AME 410 AME 413 Danfoss Heating VI AA R4 6Z DEN SMT SI...

Страница 18: ...18 Installation Guide AME 410 AME 413 DEN SMT SI VI AA R4 6Z Danfoss Heating...

Страница 19: ...19 19 Installation Guide AME 410 AME 413 Danfoss Heating VI AA R4 6Z DEN SMT SI...

Страница 20: ...Installation Guide AME 410 AME 413 73696010 VI AA R4 6Z Produced by Danfoss A S 05 2011...

Отзывы: