Technical leaflet 

Liquid level transmittter, type AKS 41 / 41U

Calibration of the 

AKS 41 / 41U

(Continued)

Min. calibration when minimum refrigerant 

level must be different from 4 mA:

1.  

Bring the refrigerant liquid level to desired  

 

  minimum level.

Press the calibration pushbutton and keep it  

 

  activated in approx. 5 seconds, until green LED    

  stopps flashing.

3. 

Activate, within the next 10 seconds, the  

  calibration pushbutton once and keep it 

  activated.

 (If calibration pushbutton is not 

  activated within 10 seconds, it will  

  automatically leave calibration mode and 

  return to normal operation)

4. 

 Observe the output mA signal increasing fast    

  starting at 4 mA.

5. 

Release the calibration pushbutton when the  

  output signal is approx. 0.5 mA from the  

 

  desired point.

6. All the next activations will increase the output  

  signal by approx. 0.05 mA

7. Approx. 10 seconds after the latest activation   

  the LED starts flashing

8. Output now corresponds to the value  

 

  measured at the latest activation.

Max. calibration when maximum refri-gerant 

level must be different from 20 mA:

1. 

Bring the refrigerant liquid level to desired  

 

  maximum level.

Press the calibration pushbutton and keep it  

 

  activated in approx. 5 seconds, until green LED 

  stopps flashing.

3. 

Activate, within the next 10 seconds, the  

  calibration pushbutton twice and keep it 

  activated.

 (If calibration pushbutton is not 

  activated within 10 seconds, it will

  automatically leave calibration mode and 

  return to normal operation)

4. 

Observe the output mA signal decreasing fast    

  starting at 20 mA.

5. 

Release the calibration pushbutton when the  

  output signal is approx. 0.5 mA from the 

  desired point.

6. All the next activations will decrease the  

 

  output signal by approx. 0.05 mA

7. Approx. 10 seconds after the latest activation   

  the LED starts flashing

8. Output now corresponds to the value 

  measured at the latest activation.

Reset to factory setting

AKS 41 / 41U can always be reset to factory 

setting regardless of any revised calibration 

values.

1. 

Press the calibration pushbutton and keep it  

 

activated in min. 20 seconds, until green LED    

 

starts flashing.

Release the calibration pushbutton.

3.   When LED starts flashing, reset to factory 

  setting is completed.

AKS 41 / 41U is now operating according to the 

factory settings.

When voltage is applied the LED will flash rapidly 

as many times as it has been calibrated through 

its lifetime.

Please note:

  The current mA output is activated

 

as soon as the flashing sequence    

 

has changed from rapid to slowly   

 

flashing.

Normal operation:

At normal operation the Green LED will be 

flashing slowly.

Generally the Green LED is ON every time 

calibration pushbutton is activated. 

Calibration mode

In calibration mode (

Press the calibration 

pushbutton and keep it activated in approx. 5 

seconds

) the Green LED is OFF.

Green LED indication

Change of refrigerant

In refrigeration mode setting (

Push the calibration 

pushbutton and keep it pressed while 24 V a.c. is 

connected and then release the pushbutton

) the 

green LED is OFF until the pushbutton is released. 
After this the green LED will flash according to 

the type of refrigerant.
When the refrigerant has been selected, the  

green LED is constantly ON.

Содержание AKS 41

Страница 1: ...Liquid level transmitter Type AKS 41 41U Technical leaflet REFRIGERATION AND AIR CONDITIONING DIVISION ...

Страница 2: ...U Contents Page Introduction 3 Special features 3 Technical data 3 Design 4 Function and factory setting 5 Setting of the AKS 41 41U 5 Signal damping 6 Calibration of the AKS 41 41U 6 Reset to factory setting 7 Green LED indication 7 Ordering AKS 41 8 Accessories AKS 41 41U 8 AKS 41U 8 Dimensions and weights AKS 41 9 AKS 41U 9 ...

Страница 3: ...Min Calibration must be carried out after 1 week of operation Subsequently only a Min Calibration once a year is needed Pressure range The AKS 41 41U is designed for Max working pressure 100 bar g 1450 psig Connection Pipe thread ISO 228 1 G 1A or 3 4 NPT Max load resistance 500 ohm Ambient temperature During operation 25 to 55 C 13 131 F During transport 40 to 70 C 40 158 F Enclosure IP65 Connect...

Страница 4: ...tter type AKS 41 41U Design Electronic head and sensor tube can be separated without emptying the standpipe Plug Plug can be mounted in 4 different positions 1 Inner pipe 2 Outer pipe 3 DIN connection 4 Green LED 5 Calibration cover 6 Calibration pushbutton 7 OPTION LED Bargraph for indication of liquid level ...

Страница 5: ...n the refrigeration mode setting push the calibration pushbutton and keep it pressed while 24 V a c is connected and then release the pushbutton NOTE This sequence must be observed If the supply voltage is connected before the calibration pushbutton is activated the signal damping will be changed 2 Release the calibration pushbutton Observe the present refrigerant setting and measure the 4 20 mA o...

Страница 6: ... min calibration point is chosen to be 4 mA and the max calibration point to be 20 mA but it is also possible to calibrate the transmitter at other calibration points This opportunity can be useful when cali brating on a plant with no possibility of bringing the level to the limit points Adjusting the min max calibration points Min calibration 1 Bring the refrigerant liquid level to desired minimu...

Страница 7: ...ormal operation 4 Observe the output mA signal decreasing fast starting at 20 mA 5 Release the calibration pushbutton when the output signal is approx 0 5 mA from the desired point 6 All the next activations will decrease the output signal by approx 0 05 mA 7 Approx 10 seconds after the latest activation the LED starts flashing 8 Output now corresponds to the value measured at the latest activatio...

Страница 8: ...ion 027F1010 AKS 41 and AKS 41U Without Bargraph indication Code no With Bargraph indication Code no Electronic top part 1 084H4150 084H4151 1 Must always be calibrated when mounted on actual sensor rod Type Length in Length mm Measuring range in Measuring range mm AKS 41U without Bargraph Code no AKS 41U with Bargraph Code no AKS 41U 6 6 152 3 13 79 084H4100 084H4101 AKS 41U 8 8 203 5 13 130 084H...

Страница 9: ... 41 15 1500 mm 59 06 3 5 7 7 AKS 41 17 1700 mm 66 93 3 8 8 4 AKS 41 22 2200 mm 86 61 4 6 10 1 AKS 41 30 3000 mm 118 10 5 8 12 8 Type Insertion length Weight lb kg AKS 41U 6 6 152 mm 2 9 1 32 AKS 41U 8 8 203 mm 3 1 1 41 AKS 41U 12 12 305 mm 3 4 1 55 AKS 41U 15 3 15 3 389 mm 3 8 1 72 AKS 41U 19 2 19 2 488 mm 4 0 1 82 AKS 41U 23 1 23 1 587 mm 4 3 1 96 AKS 41U 30 30 762 mm 4 9 2 22 AKS 41U 35 35 889 m...

Страница 10: ...10 RD8AA502 DKRCI PD SC0 A1 02 520H0092 Danfoss A S AC DSL MWA 04 2006 Technical leaflet Liquid level transmittter type AKS 41 41U ...

Страница 11: ... Danfoss A S AC DSL MWA 04 2006 RD8AA502 DKRCI PD SC0 A1 02 520H0092 11 Technical leaflet Liquid level transmittter type AKS 41 41U ...

Страница 12: ...12 RD8AA502 DKRCI PD SC0 A1 02 520H0092 Danfoss A S AC DSL MWA 04 2006 Technical leaflet Liquid level transmittter type AKS 41 41U ...

Отзывы: