 AK-RC 101 / 103 

Instructions 

RI8NN35K

  ©  Danfoss  01/2010 

5

English

Operating

Function

Press

View set point

 

Change set point

 + 

 / 

"Change" menu ("ro"............."tEu")

 + 

 (4 seconds)

Return

 + 

 (4 seconds)

"Set-up" menu ("AC" ............. "reL" )

 + 

 + 

 (4 seconds)

Return

 + 

 (4 seconds)

List of Level 1 variables (User Level)

Variables Explanation

Default

r0

Differential 

above main SETPOINT

0.2 - 10K

2K

d0

Defrost interval (hours)

0 - 24 hours

4 hours

d2

End-of-defrost setpoint.

Defrosting stops when the defrost sensor exceeds 
the value, 

-35 - 45 °C

15 °C

d3

Max defrost duration

1 - 240 min

25 min

d7

Drip duration

At the end of defrost, the compressor and fans remain 

at standstill for time d7 and the defrost LED on the 

front panel flashes.

0 - 10 min

0 min

F5

Fan pause 

after defrost (minutes)

Allows fans to be kept at standstill for time F5 after 

dripping. This time begins at the end of dripping. If no 

dripping has been set, the fan pause starts directly at 

the end of defrost.

0 - 10 min

0 min

A1

Maximum temperature alarm

Allows user to define a maximum temperature for 

the room being refrigerated. Above value A2 an 

alarm trips: the alarm LED flashes, the displayed 

temperature flashes and the buzzer sounds to 

indicate the problem.

-45 °C

A2

Maximum temperature alarm

Allows user to define a maximum temperature for 

the room being refrigerated. Above value A2 an 

alarm trips: the alarm LED flashes, the displayed 

temperature flashes and the buzzer sounds to 

indicate the problem.

+45 °C

tEu

Evaporator sensor temperature display

(displays nothing if 

dE =1)

(read only)

-

List of Level 2 variables (Installer Level)

AC 

Door switch status

0  =  normally open,  1 = normally closed

0

F3

Fan status with compressor off

0  =  fans run continuously

1  =  fans only run when compressor is working

1

F4

Fan pause during defrost

0  =  fans run during defrost

1  =  fans do not run during defrost

1

dE   

Sensor presence

0  =  evaporator sensor present

1  =  no evaporator sensor

0

d1 

Defrost type

1=hot gas, 0=electric

0

Ad

Not to be used

Ald

Minimum and maximum temperature alarm 

1...240 min

120 min

C1

Minimum time between shutdown and 

subsequent switching on of the compressor. 

0...15 min

0 min

CAL

Correction of sensor signal

-10...+10

0

Pc

Compressor protection contact status

0=NO, 1=NC

0 = NO

doC

Compressor safety time for door switch

0...5 minutes

0

tdo

Restart time, if the door remains open

0... 240 min. (0=no function)

0

Fst

FAN shutdown TEMPERATURE

-45...+45 °C

+45 °C

Fd

Fan differential below Fst

0...+10K

2K

LSE

Min. limit of set point setting

-45...HSE

-45°C

HSE

Max. limit of set point setting

45... LSE

45°C

tA

NO – NC 

alarm relay switching

0  =  activates when alarm is on 

1  =  deactivates when alarm is on

1

AU

Auxiliary/alarm relay control

  

0  =  alarm relay

1  =  manual auxiliary relay controlled via AUX key

2  =  automatic auxiliary relay managed by StA temp. 

setting with 2°C differential

3  =  not used

4  =  pump-down function (see manual)

5  =  free voltage contact for  

 

 

 condensing unit (AUX relay and compressor relay in 

parallel)

6=Relay used to control a heating element in the 

crankcase. The relay is on when the compressor is 

stopped.

7=not used

0

StA

Temp. setting for aux. relay

-45...+45 °C

0

In1

Man in cold room alarm

0  =  compressor protection

1  =  man-in-room alarm

0

P1

Password type of protection

( active when PA does not equal 0)

0  =  display set point only

1  =  display set point, AUX, light access

2  =  access to programming not permitted

3  =  access to second level programming not 

permitted

3

PA

Password

(see P1 for the type of protection), 0...999, 0=not 

active

0

reL

Software version 

(Read only)

-

See manual for further information

Содержание AK-RC 103

Страница 1: ...lslutninger Connections Anschl sse Raccordements Conexi n Anslutningar AK RC 101 AK RC 103 Se ogs manual RS8FD RS8FE See also manual Siehe auch Manual Voir aussi manuel Ver tambi n manual Se ocks manu...

Страница 2: ...V lvula solenoide Kriwan Kriwan Kriwan Kriwan Kriwan Pressure Pressostat HT LT Druckschalter Pressostat Control de pr sion Pump down Pump down Pump down Pump down Pump down Pump d mode Pump down mode...

Страница 3: ...or slukket 0 ventilatorerne k rer kontinuerligt 1 ventilatorerne k rer kun n r kompressoren arbejder 1 F4 Ventilatorpause under afrimning 0 ventilatorerne k rer under afrimning 1 ventilatorerne k rer...

Страница 4: ...registreret en EEPROM hukommelses alarm Alle udgange bortset fra alarmen deaktiveres Sluk enheden og t nd den igen E8 Person i k lerum alarm Nulstil alarmindgangen i k lerummet Ec Kompressorbeskyttel...

Страница 5: ...un continuously 1 fans only run when compressor is working 1 F4 Fan pause during defrost 0 fans run during defrost 1 fans do not run during defrost 1 dE Sensor presence 0 evaporator sensor present 1 n...

Страница 6: ...OM memory alarm has been detected All outputs except the alarm are deactivated Switch unit off and back on again E8 Man in cold room alarm Reset the alarm input inside the cold room Ec Compressor prot...

Страница 7: ...enn der Verdichter in Betrieb ist 1 F4 L fterstopp w hrend des Abtauens 0 L fter laufen beim Abtauen 1 L fter laufen beim Abtauen nicht 1 dE F hler 0 Abtauf hler vorhanden 1 kein Abtauf hler 0 d1 Abta...

Страница 8: ...gestellt alle Ausg nge au er dem Alarm sind deaktiviert Schalten Sie die Anlage ab und dann wieder ein E8 Alarm Person im K hlraum Setzen Sie den Alarmgeber im K hlraum zur ck Ec Verdichterschutz ausg...

Страница 9: ...marche continue 1 ventilateurs en marche uniquement si le compresseur fonctionne 1 F4 Arr t des ventilateurs pendant le d givrage 0 ventilateurs en marche pendant le d givrage 1 ventilateurs arr t s...

Страница 10: ...l alarme teindre puis rallumer l appareil E8 Alarme de pr sence d une personne dans la chambre R initialiser l entr e de l alarme ou le bouton coup de poing dans la chambre froide Ec Activation de la...

Страница 11: ...en funcionamiento continuo 1 ventiladores en marcha solo durante el funcionamiento del compresor 1 F4 Pausa de los ventiladores durante el desescarche 0 los ventiladores funcionan durante el desescar...

Страница 12: ...r n todas las salidas excepto las de alarma Apague el equipo y vuelva a encenderlo E8 Alarma de persona en la c mara frigor fica Restablezca la entrada de alarma en el interior de la c mara frigor fic...

Страница 13: ...1 normalt st ngd 0 F3 Fl ktstatus med kompressor OFF 0 fl ktarna k r kontinuerligt 1 fl ktarna k r bara n r kompressorn arbetar 1 F4 Fl ktstopp under avfrostning 0 fl ktarna k r under avfrostning 1 fl...

Страница 14: ...ckts Alla utg ngar f rutom larmrel et deaktiverade Sl av och p enheten E8 Man i kylrum larm Reset the alarm input inside the cold room Ec Kompressorskydd utl st termiskt skydd eller tryckbrytare Alla...

Страница 15: ...AK RC 101 103 Instructions RI8NN35K Danfoss 01 2010 15...

Страница 16: ...AK RC 101 103 The Product contains electrical components And may not be disposed together with domestic waste Equipment must be separate collected with Electrical and Elec tronic waste According to Lo...

Отзывы: