Manual  RS8EX202  ©  Danfoss  02-2009 

AK-PI 200

Introduction

Function

The AK-PI 200 is an intermediary link allowing AKC and AKL type 
controllers to be operated via a system manager, e.g. AK-SM 720. 
The actual operation of the controllers is carried out with an AK-ST 
500.

(AKC and AKL controllers use the DANBUSS data communication 
system. The communication is controlled by a gateway, e.g. AKA 
245.
In a solution with an AK-PI 200 and a system manager, the 
gateway should not be used.)

Application

The AK-PI 200 is used on systems where the system unit is an 
AK-SM 720 and where there are one or more controllers with 
DANBUSS data communication. 
The unit links the communication to DANBUSS so that the system 
manager can present all the controllers on the system.
DANBUSS controllers are presented on an equal footing together 
with LON RS 485 controllers and MODBUS controllers.
All controllers can be viewed and operated from the system 
manager’s network overview.
The solution can be used on existing systems where the majority 
are DANBUSS controllers and where it would be desirable to 
change the system operation to a browser-based interface instead 
of an AKM software interface.
Or it can be used on new systems where the majority might be 
controllers with LON communication and other individual controls 
can be AKC controllers. 

Principle

The link between the system manager and the AK-PI 200 is via a 
TCP/IP. 
In this very simple connection the two units can be connected to 
each other via a crossed cable.
This is where the IP addresses are set to static addresses.

On larger systems or where there is also outgoing IP 
communication from the system, the connection must be made 
via a router.
Here the IP addresses can be dynamic, but if there is 
communication to the system from outside, they must be static.

If you are not sure whether you should select static or dynamic, abide 
by the following recommendation:

Dynamic is the easiest. Here the router itself allocates an address 
for the system manager and another for the PI unit. But you 
should only select this solution if the system is closed without a 
connection for an external operation interface.

With static you must obtain a couple of addresses yourself at the 
local IT department and you must also set the addresses yourself 
in the two units. This solution must always be used when the 
system is operated by an external service company, e.g. for log 
collection, alarm management or service. 

Contents

Introduction ....................................................................................................... 2
Installation .......................................................................................................... 4
Requirements and terms ............................................................................... 6
Ordering .............................................................................................................. 8
Data ....................................................................................................................... 8

Содержание AK-PI 200

Страница 1: ...REFRIGERATION AND AIR CONDITIONING Protocol interface AK PI 200 Manual ...

Страница 2: ...ware interface Or it can be used on new systems where the majority might be controllers with LON communication and other individual controls can be AKC controllers Principle The link between the system manager and the AK PI 200 is via a TCP IP In this very simple connection the two units can be connected to each other via a crossed cable This is where the IP addresses are set to static addresses O...

Страница 3: ...e network The PI unit is perceived as a controller on the network and its address can be viewed in the IP list Up to two PI units can be connected to the system manager which is master i e has address 1 You set the network address on the front of the system units and on the front of the PI units Set the system manager to address 1 If there are several system managers slave network set these to add...

Страница 4: ...the two units must be a crossed cable A static IP address is always used here b Cables from the units are connected to a router or to a switch A dynamic or static IP address is used here 2 Setting a Router Dynamic There are no settings in the router Static A static address range must be set in the router b AK SM 720 Select static if the connection between the system unit and the AK PI 200 is with ...

Страница 5: ...ion 1 1x it must be set to 1 5 You can activate the Service PIN function at this point If you do this means you do not have to start the scan function in the next point Perform the first scan 1 Start the scan function in the system manager wait for the results the controllers on the LON and MODBUS communication will now be located and visible in the network overview 2 Go to the next page of the ne...

Страница 6: ...networks and addresses that can occur 11 001 is the master system manager 11 002 to 11 010 are slave networks controlled by 11 001 the figure 11 keeps track of the networks and cannot be changed 11 012 to 11 999 are addresses for units on the network The units can be AK PI 200 units or wireless units or they can be controllers in which the data communication takes place via TCP IP 1 xxx will be co...

Страница 7: ... manager that AK PI 200 is connected to The status of the alarm transmission Date and time The quality of the DANBUSS communication signal The configuration display gives access to the following The configuration lock is only used if a static IP address is to be set Under System setup you can give the unit a name IP settings can be entered ...

Страница 8: ...AK PS 075 18 VA Supply 080Z0053 Type Function Application Language Code no AK PI 200 Protocol interface Intermediary link between system manager and controllers with DANBUSS data communication English German French Italian Dutch Spanish Portuguese Danish Swedish and Finnish 080Z8521 Data Supply voltage 24 V a c 20 Power consumption AK PI 200 12 VA Ambient temperature During transport 40 to 70 C Du...

Отзывы: