86
Capacity
controller RS8HF102 © Danfoss 2017-07
AK-PC 772A
Manual capacity control
1. Go to overview
2. Select suction group
Press the suction group button for the suction group that is to
be controlled manually.
Press the
+
-button to go on to the next page
3. Set capacity control to manual
4. Set capacity in percent
Press in the blue field against
Manual capacity
.
If you need to manually adjust the capacity of the compressors, you can
use the following procedure:
WARNING!
If you force control the compressors, the oil management will be shut
down. This could cause compressor damages.
(If the wiring of the compressors includes safety relays, monitoring will
continue. See Regulating functions.)
Press the blue field against
Control mode
Select
MAN
.
Set the capacity to the required percentage.
Press
OK
.