AK-PC 772A
Capacity
controller RS8HF102 © Danfoss 2017-07
71
Configuration of inputs
and outputs
1. Go to Configuration menu
2. Select I/O configuration
3. Configuration of Digital outputs
Press the
+
-button to go on to the
next page
4. Setup On/off inputs
Press the
+
-button to go on to the
til næste side.
3 - Outputs
The possible functions are
the following:
Comp. 1
Unloader 1-1
Unloader 1-2
Unloader 1-3
Do for Compressor. 2 and 3
Compressor run
IT compressor release
Injection suction line
Injection ON
Fan 1 / VSD
Fan 2 - 4
HP Control
Hot gas dump
Heat recovery
Alarm
I'm alive relay
Thermostat 1
Pressostat 1
Volt input 1
PI 1-PWM
4 - Digital inputs
The possible functions are
the following:
Ext. Main switch
Ext. compr. stop
Ext. power loss
Night setback
Load shed 1
Load shed 2
All compressors:
Common safety
Comp. 1
Oil pressure safety
Over current safety
Motor protect. safety
Disch. temp. safety
Disch. press. safety
General safety
VSD comp. 1 Fault
Do for Comp. 2 and 3
Fan 1 safety
Do for fan 2-4
VSD cond safety
AC limit
Rec. low liquid level
Rec. high liquid level
Heat recovery
DI 1 Alarm input
DI 2-10 ...
PI-1 Di ref
External DI PI-1
The following displays will depend on the earlier definitions. The dis-
plays will show which connections the earlier settings will require. The
tables are the same as shown earlier.
• Digital outputs
• Digital inputs
• Analog outputs
• Analog inputs
We set up the controller’s digital input functions by keying in which
module and point on this module each one of these has been connected
to.
We furthermore select for each output whether the function is to be ac-
tive when the output is in pos.
Closed
or
Open
.
Open has been selected here for all the safety circuits. This means that
the controller will receive signal under normal operation and register it
as a fault if the signal is interrupted.
Load
Output
Module
Point
Active at
Compressor 1 MT
DO1
1
12
ON
Compressor 2 MT
DO2
1
13
ON
Compressor 3 MT
DO3
1
14
ON
Compressor 1 LT
DO4
1
15
ON
Compressor 2 LT
DO5
1
16
ON
Valve and circulation pump hr
D06
1
17
ON
Fan
DO7
1
18
ON
Hot gas dump
DO8
1
19
ON
We set up the controller’s digital outputs by keying in which module
and point on this module each one of these has been connected to.
We furthermore select for each output whether the load is to be active
when the output is in pos.
ON
or
OFF
.
Function
Input
Module
Point
Active at
Compressor 1 MT Safety
AI1
2
1
Open
Compressor 2 MT Safety
AI2
2
2
Open
Compressor 3 MT Safety
AI3
2
3
Open
All compressors common safety MT
AI4
2
4
Open
Compressor 1 LT Safety
AI5
2
5
Open
Compressor 2 LT Safety
AI6
2
6
Open
All compressors common safety LT
AI7
2
7
Open
Configuration - continued