RS8FR302 © Danfoss 2015-08 

73

Read codes

Normally the selected temperature signal can be read from the 

display, but under certain conditions the display may show other 

codes in order to notify the user of various operating states.

Function

Display readout

OFF

When the "main switch" is set to OFF, the display will read "OFF"

PAS

Requirement for access code. If operation of the display is to be 

protected by an access code, both the definition and the access 

code must be set in the controllers' authorisation menu for the 

local display (LOCD).

Alarm

The three LED's will flash if an alarm is triggered. The alarm code 

can be viewed by pressing the top button. Pressing the button will 

also reset the alarm relay

- - - 

When three dashes appear, the valid temperature reading is faulty 

(sensor switched off or short-circuited), or else the display has been 

deactivated.

Menu overview:

Parameter

name

Function

At start-

up

r12

Main switch:

0: Controller stopped

1: Regulation

x

o93

Configuration lock

You can only select a preset configuration or change refriger-

ant when the configuration lock is open.

0 = Configuration open

1 = Configuration locked

x

o62

Selection of predefined configuration.

This setting will give a choice from a series of predefined 

combinations, which at the same time establish the connec-

tion points.

At the end of the manual there is an overview of the options 

and connection points.

After configuration of this function, the controller will shut 

down and restart.

x

u1-u31

u1

u2

u3

u4

u5

u6

u7

u8

u9

u10

Readouts for use in service situations

Temperature measurement, thermostat 1

Temperature measurement, thermostat 2

Temperature measurement, thermostat 3

Temperature measurement, thermostat 4

Temperature measurement, thermostat 5

Temperature measurement, thermostat 6

Temperature measurement, thermostat 7

Temperature measurement, thermostat 8

Temperature measurement, thermostat 9

Temperature measurement, thermostat 10

u11

u12

u13

u14

u15

Pressure measurement, pressostat 1

Pressure measurement, pressostat 2

Pressure measurement, pressostat 3

Pressure measurement, pressostat 4

Pressure measurement, pressostat 5

u16

u17

u18

u19

u20

u21

u22

u23

u24

u25

u26

u27

u28

u29

u30

u31

Status on alarm DI 1

Status on alarm DI 2

Status on alarm DI 3

Status on alarm DI 4

Status on alarm DI 5

Status on alarm DI 6

Status on alarm DI 7

Status on alarm DI 8

Status on alarm DI 9

Status on alarm DI 10

Status on alarm DI 11

Status on alarm DI 12

Status on alarm DI 13

Status on alarm DI 14

Status on alarm DI 15

Status on alarm DI 16

.

X = When the controller is not set up, the display will only 

read the marked settings

A01

A02

A03

A04

A05

A06

A07

A08

A09

A10

A11

A12

A13

A14

A15

A16

A17

A18

A19

A20

High alarm thermostat 1

Low alarm thermostat 1

High alarm thermostat 2

Low alarm thermostat 2

High alarm thermostat 3

Low alarm thermostat 3

High alarm thermostat 4

Low alarm thermostat 4

High alarm thermostat 5

Low alarm thermostat 5

High alarm thermostat 6

Low alarm thermostat 6

High alarm thermostat 7

Low alarm thermostat 7

High alarm thermostat 8

Low alarm thermostat 8

High alarm thermostat 9

Low alarm thermostat 9

High alarm thermostat 10

Low alarm thermostat 10

A21

A22

A23

A24

A25

A26

A27

A28

A29

A30

Low alarm pressostat 1

High alarm pressostat 1

Low alarm pressostat 2

High alarm pressostat 2

Low alarm pressostat 3

High alarm pressostat 3

Low alarm pressostat 4

High alarm pressostat 4

Low alarm pressostat 5

High alarm pressostat 5

A31

A32

A33

A34

A35

A36

A37

A38

A39

A40

Low alarm voltage input 1

High alarm voltage input 1

Low alarm voltage input 2

High alarm voltage input 2

Low alarm voltage input 3

High alarm voltage input 3

Low alarm voltage input 4

High alarm voltage input 4

Low alarm voltage input 5

High alarm voltage input 5

A41

A42

A43

A44

A45

A46

A47

A48

A49

A50

A51

A52

A53

A54

A55

A56

Alarm DI 1

Alarm DI 2

Alarm DI 3

Alarm DI 4

Alarm DI 5

Alarm DI 6

Alarm DI 7

Alarm DI 8

Alarm DI 9

Alarm DI 10

Alarm DI 11

Alarm DI 12

Alarm DI 13

Alarm DI 14

Alarm DI 15

Alarm DI 16

A60

Manual control of DO / DI

E01

E02

Sensor alarm

System alarm

- - 1

Initiation. Display is connected to output A. (- - 2 = output B, etc.)

Alarm overview:

Содержание AK-LM 330

Страница 1: ...Monitoring unit AK LM 330 Design Guide ADAP KOOL Refrigeration control systems...

Страница 2: ...1 Connections 32 Planning table 33 Length 34 Linking of modules 34 Determine the connection points 35 Connection diagram 36 Supply voltage 37 Ordering 38 3 Mounting and wiring 39 Mounting 40 Mounting...

Страница 3: ...tion Pressure monitoring with alarm function Pressure control with relay function Voltages of 0 10 V Voltage detection Voltage monitoring with alarm function Voltage monitoring with relay function On...

Страница 4: ...irements are changed Flexible concept Controller series with common construction One principle many regulation uses modules are selected for the actual connection requirements The same modules are use...

Страница 5: ...ccess to a number of general functions such as overview manual operation log function alarms and service configuration Network linking The controller can be linked up into a network together with othe...

Страница 6: ...memory and can contain more data If you are in a service situation you can show measurements in a trend function The measurements are then made real time and displayed instantly Alarm The display giv...

Страница 7: ...specific software and by which input and output signals the relevant application will require If it is an application with few connections the controller module top part with belonging bottom part ma...

Страница 8: ...n is planned set up it will generate a need for a number of connections distributed on the mentioned types This connection must then be made on either the controller module or an extension module The...

Страница 9: ...DA cable and AK controller AK RS 232 Accessories Transformer module 230 V 115 V to 24 V AK PS 075 18 VA 24 V d c Supply for controller AK PS 150 36 VA 24 V d c Accessories External display that can be...

Страница 10: ...lid state outputs Can be used for loads that are cut in and out frequently e g rail heat fans and AKV valve Max 240 V a c Min 48 V a c Max 0 5 A Leak 1 mA Max 1 AKV Ambient temperature During transpor...

Страница 11: ...2015 08 11 Dimensions The module dimension is 72 mm Modules in the 100 series consist of one module Modules in the 200 series consist of two modules Controllers consist of three modules The length of...

Страница 12: ...arate instructions for LON communication Address setting When the controller is connected to a gateway type AKA 245 the controller s address must be set between 1 and 119 If it is a system manager AK...

Страница 13: ...1 22 10 AI 10 23 24 11 AI 11 25 26 12 DO 1 31 32 13 DO 2 33 34 14 DO 3 35 36 15 DO 4 37 38 16 DO 5 39 40 41 17 DO6 42 43 44 18 DO7 45 46 47 19 DO8 48 49 50 Terminal 15 12 V Terminal 16 5 V Terminal 27...

Страница 14: ...pply voltage The supply voltage to the module comes from the previous module in the row Supply voltage to a pressure transmitter can be taken from either the 5 V output or the 12 V output depending on...

Страница 15: ...2 P0 Pc Paux AKS 32R AKs 2050 1 xx bar AKS 32 1 zz bar U 0 5 V 0 10 V On Off Ext Main switch Day Night Door Defrost Active at Closed Open Point 5 6 7 8 Type AI5 AI6 AI7 AI8 Point 1 2 3 4 Type AI1 AI2...

Страница 16: ...he module contains 8 inputs for on off voltage signals Signal AK XM 102A is for low voltage signals AK XM 102B is for high voltage signals Supply voltage The supply voltage to the module comes from th...

Страница 17: ...I 2 3 4 3 DI 3 5 6 4 DI 4 7 8 5 DI 5 9 10 6 DI 6 11 12 7 DI 7 13 14 8 DI 8 15 16 Point Signal Active at DI Ext Main switch Day Night Door Defrost Closed voltage on Open voltage off Point 5 6 7 8 Type...

Страница 18: ...o override the relay s function Either to position OFF or ON In position Auto the controller carries out the control Light emitting diodes There are two rows with LED s They indicate the following Lef...

Страница 19: ...t 1 DO 1 25 26 27 2 DO 2 28 29 30 3 DO 3 31 32 33 4 DO 4 34 35 36 5 DO 5 37 38 39 6 DO 6 40 41 42 7 DO 7 43 44 45 8 DO 8 46 47 48 Signal Active at DO Fan Alarm Light Rail heat Defrost Night blinds Val...

Страница 20: ...ight change over switches at the front make it possible to override the relay s function Either to position OFF or ON In position Auto the controller carries out the control Light emitting diodes Ther...

Страница 21: ...ohm 0 C S2 S3 S4 S5 Saux Pt 1000 P AKS 32R AKS 2050 AKS 32 P0 Pc Paux AKS 32R AKS 2050 1 xx bar AKS 32 1 zz bar U 0 5 V 0 10 V On Off Ext Main switch Day Night Door Defrost Active at Closed Open DO F...

Страница 22: ...g or an On Off signal DI function Supply voltage The supply voltage for the module comes from the previous mod ule in the sequence LEDs These indicate the following Voltage of the module Communication...

Страница 23: ...Signal Module Point Terminal Active at 1 CI 1 1 2 2 CI 2 3 4 3 CI 3 5 6 4 CI 4 7 8 5 CI 5 9 10 6 CI 6 11 12 7 CI 7 13 14 8 CI 8 15 16 Point Point 5 6 7 8 Type CI5 CI6 CI7 CI8 Point 1 2 3 4 Type CI1 C...

Страница 24: ...night change over Fixed defrost times Saving of alarm log in case of power failure Saving of temperature log in case of power failure Connection The module is provided with plug connection Placing Th...

Страница 25: ...The extension module is connected to the controller module via a cable with plug connections You have to use one cable per module The cable is supplied in various lengths Both types of display with or...

Страница 26: ...roller Supply voltage 230 V a c or 115 V a c from 100 V a c to 240 V a c Placing On DIN rail Effect Type Output tension Output current Power AK PS 075 24 V d c 0 75 A 18 VA AK PS 150 24 V d c adjustab...

Страница 27: ...AK LM 330 RS8FR302 Danfoss 2015 08 27...

Страница 28: ...hat the need for connections can be established Functions Clock function Clock function and change over between summer time and winter time are contained in the controller The clock is zeroset when th...

Страница 29: ...dule s terminal board where there is both a 5 V supply and a 12 V supply When programming the pressure transmitter s pressure range must be set ON OFF voltage inputs DI This signal must be connected t...

Страница 30: ...the controller module If not can they be obtained by changing an ON OFF input signal from voltage signal to contact signal or will an extension module be required 6 Decide which extension modules are...

Страница 31: ...y times x Voltage signal Number 5 Scaling of read out signal for ex 0 10 V 0 100 humidity x Cutin and Cutout values for relay x Alarm limits and delay times x Delay times on cutin and cutout of relays...

Страница 32: ...eset the alarm relay mute function Pulse inputs Energy reading Synchronisation On off outputs Relay outputs Thermostat functions 1 10 Voltage signals 1 5 Pressostat functions 1 5 Digital input functio...

Страница 33: ...larm relay Pulse inputs Energy measurement 1 4 1 Synchronizing signal On off outputs Relays for thermostat functions 1 10 1 Relays for voltage signals 1 5 1 Relays for pressostat functions 1 5 1 Relay...

Страница 34: ...d the controller will all the time check whether there is connection to the connected modules This status can be followed by the light emitting diode When the two catches for the DIN rail mounting are...

Страница 35: ...y look like a separate module But it isn t Columns 1 2 3 and 5 are used for the programming Columns 2 and 4 are used for the connection diagram Signal Module Point Terminal Signal type Active at Air t...

Страница 36: ...AK LM 330 11 Connection diagram Drawings of the individual modules may be ordered from Danfoss Format dwg and dxf You may then yourself write the module number in the circle and draw the individual co...

Страница 37: ...The 24 V must not be shared by other controllers or units The analog inputs and outputs are not galvanically separated from the supply The and 24V input must not be earthed Transformer size The power...

Страница 38: ...x Type Function Application Code no Example continued Operation AK ST 500 Software for operation of AK controllers AK operation 080Z0161 x Cable between PC and AK controller AK Com port 080Z0262 x Cab...

Страница 39: ...ribes how the controller Is fitted Is connected We have decided to work on the basis of the example we went through previously i e the following modules AK LM 330 Monitoring unit AK XM 102B digital in...

Страница 40: ...embly 2 Assemble the extension module and the basic module The basic module must not be connected to voltage When the two snap catches for the DIN rail mounting are in the open position the module can...

Страница 41: ...8 AI 8 19 20 9 AI 9 21 22 Pressure measurement Paux1 to 12 bar 10 AI 10 23 24 AKS 32R 12 Pressure measurement Paux2 to 34 bar 11 AI 11 25 26 AKS 32R 34 12 DO 1 31 32 13 DO 2 33 34 14 DO 3 35 36 15 DO...

Страница 42: ...and activate the Service Pin When the controller is set correct on the network the LED sta tus will flash quickly for 10 minutes 6 The controller is now ready to be configured Power Comm DO1 Status DO...

Страница 43: ...n describes how the controller Is configured Is operated We have decided to work on the basis of the example we went through previously i e temperature monitoring pressure monitoring monitoring of 230...

Страница 44: ...Saux1 Temperature reading Saux2 and one 230 V signal for activation during defrosting so that the alarm delay is postponed DI1 and one 230 V signal detecting that the appliance is not in operation DI2...

Страница 45: ...w of it will always appear In this case the overview is empty This is because the controller has not yet been set up The red alarm bell at the bottom right tells you that there is an active alarm in t...

Страница 46: ...isor for the specific system and a corresponding access code for this person The controller will utilize the same language that is selected in the service tool but only if the controller contains this...

Страница 47: ...ation lock can be Unlocked Configuration lock The controller can only be fully configured when the configuration lock is set to Un locked The settings are only applied when it is set to Locked again A...

Страница 48: ...e that alarm text should be displayed in here Alarm text can be in a different language to the operating language Clock When the time is set the PC s time can be transferred to the controller When the...

Страница 49: ...number When a number is selected for the four settings above the same number of relays are automatically reserved The connections for the respective functions then need to be defined under I O settin...

Страница 50: ...concerned For thermostats it is the tempera ture reading after calibration For pressostats it is the pressure reading after calibration For On Off signals it is the current alarm s status the input s...

Страница 51: ...the controller s digital input functions by keying in which module and point on this module each one of these has been con nected to We furthermore select for each output whether the function is to be...

Страница 52: ...34 Bar AKS 32R 1 34 Bar AKS 32 1 50 Bar AKS 32R 1 50 Bar AKS 2050 1 59 Bar AKS 2050 1 99 Bar AKS 2050 1 159 Bar User defined only ratio metric The min and max values of the pressure interval must be s...

Страница 53: ...ected Your choice of functions and settings has connected all the relevant alarms that are current They will be shown with text in the three pictures All alarms that can occur can be set for a given o...

Страница 54: ...54 RS8FR302 Danfoss 2015 08 AK LM 330 5 Set alarm priorities for General alarms Configuration continued In our example we select the settings shown here in the display...

Страница 55: ...s at the bottom of the pages the ones that can only be seen via the Scroll bar When this function is set to YES a relay will be reserved which couples with the thermostat Definition of the connection...

Страница 56: ...ct voltage signals 11 Overview for voltage signals Check of settings contiuned When this function is set to YES a relay will be reserved which couples with the pressostat Definition of the connection...

Страница 57: ...that will be presented when the input signal is at its maximum e g 10 V Cut in and cut out values and alarm settings refer to the scaled values When this function is set to YES a relay will be reserv...

Страница 58: ...m3 when measuring gas Also define How many pulses are to be received for each unit of measure Any necessary scaling Any reset or other start value of the display The measurement can be monitored in th...

Страница 59: ...of selected func tions and define inputs and outputs The result can be seen in the next section where the setup is controlled Configuration continued Press in the field against Configuration lock Sel...

Страница 60: ...exist The selected point number on the selected mod ule had been set up for something different The error is corrected by setting up the output correctly Remember that the setup must be unlocked be f...

Страница 61: ...hecked whether the output has been correctly connected AUTO The output is controlled by the controller MAN OFF The output is forced to pos OFF MAN ON The output is forced to pos ON Activate the variou...

Страница 62: ...row of the two other address switches must point at 0 2 Push the Service Pin Press down the service pin and keep it down until the Service Pin LED lights up 3 Wait for answer from the system unit Depe...

Страница 63: ...remove cancelled alarms from the alarm list 5 Check active alarm again In our case we have a series of alarms We will tidy them up so that we only have those that are relevant In our case an active al...

Страница 64: ...e display 2 Start control First start of control continued Press in the field against Main switch Select ON Press OK The controller will now start controlling when the external switch also are activat...

Страница 65: ...the following The log function requires that the clock function is set Even a minor power failure will stop the clock If you want to ensure that the clock is always set the controller must either be i...

Страница 66: ...Here is the survey of all the parameters that are collected in the log If a parameter has to be removed from the log collection you must select the parameter and then press Remove If a parameter has...

Страница 67: ...AK LM 330 RS8FR302 Danfoss 2015 08 67 5 Regulating functions This section describes how the different functions work...

Страница 68: ...ns Name Sensor signal Display of the current reading Selection of relay function Setting the cut out value for relays Setting the cut in value for relays Selection of the input signal that changes to...

Страница 69: ...the voltage readings V1 V2 V3 etc The following signals can be received 0 5 V 1 5 V 0 10 V 2 10 V A current signal can also be detected if external resistances are placed on the input so that the sign...

Страница 70: ...eters measure an element of consumption It might be interesting to know for example the freezer department s energy consumption Measurement intervals for synchronisation are set jointly for all energy...

Страница 71: ...Interrupted results in no action Miscellaneous Alarm relay If the controller must give an alarm on a relay output the relay must be defined 2 relays can be defined One which is active at alarms with...

Страница 72: ...from a display This display must be of display type EKA 163B or EKA 164B Up to four displays per controller can be fitted Connection is effected by means of wires with plug connectors The display can...

Страница 73: ...ssostat 1 Pressure measurement pressostat 2 Pressure measurement pressostat 3 Pressure measurement pressostat 4 Pressure measurement pressostat 5 u16 u17 u18 u19 u20 u21 u22 u23 u24 u25 u26 u27 u28 u2...

Страница 74: ...e conditions can give rise to malfunctions of the control system and ultimately lead to a plant breakdown Every possible safeguard is incorporated into our products to prevent this However a wrong ins...

Страница 75: ...X High alarm The voltage signal has been above the high alarm limit for longer time than set delay DI X alarm input X 1 16 Medium DI X alarm Alarm on general alarm input DI x System alarms The alarm...

Страница 76: ...DI2 AL 2 8 Saux1 Saux2 DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 Th1 Th2 DI1 AL DI2 AL DI3 AL DI4 AL 4 5 2 Saux1 Saux2 Saux3 Saux4 Paux1 Paux2 DI1 DI2 DI3 DI4 DI5 Th1 Th2 Th3 Th4 P1 P2 5 2 2 2 Saux1 Saux2 Saux...

Страница 77: ...DI1 AL Hi AL 5 5 P2 Hi AL 6 6 P2 Hi AL DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 7 7 Th7 Hi AL Cl1 Cl2 Synch Al Mute 8 8 DI1 AL Hi AL Cl1 Cl2 Synch Al Mute 9 9 DI3 AL Hi AL Cl1 Cl2 Synch Al Mute 10 10 DI5 AL Hi...

Страница 78: ...78 RS8FR302 Danfoss 2015 08 AK LM 330...

Страница 79: ...AK LM 330 RS8FR302 Danfoss 2015 08 79...

Страница 80: ...s the right to alter its products without notice This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specificati...

Отзывы: