24
Manual RS8FS402 © Danfoss 2016-03
AK-CC
550A
*) Emergency cooling will take effect when there is lack of signal from a defined S3 or S4 sensor or signal from the pressure transmitter is outside signal
range.. The regulation will continue with a registered average cutin frequency. There are two registered values – one for day operation and one for
night operation.
Operating status
(Measurement)
The controller goes through some regulating situations where it is just waiting for the next point
of the regulation. To make these “why is nothing happening” situations visible, you can see an
operating status on the display. Push briefly (1s) the upper button. If there is a status code, it will
be shown on the display. The individual status codes have the following meanings:
Ctrl. state:
(Shown in all menu displays)
Normal regulation
S0
0
Waiting for end of the coordinated defrost
S1
1
When the compressor is operating it must run for at least x minutes.
S2
2
When the compressor is stopped, it must remain stopped for at least x minutes.
S3
3
The evaporator drips off and waits for the time to run out
S4
4
Refrigeration stopped by main switch. Either with r12 or a DI-input
S10
10
Refrigeration stopped by thermostat
S11
11
Defrost sequence. Defrost in progress
S14
14
Defrost sequence. Fan delay — water attaches to the evaporator
S15
15
Refrigeration stopped due to open ON input or stopped regulation
S16
16
Door is open. DI input is open
S17
17
Melt function in progress. Refrigeration is interrupted
S18
18
Modulating thermostat control
S19
19
Emergency cooling due to sensor error
S20
20
Regulation problem in the injections function
S21
21
Start-up phase 2. Evaporator being charged
S22
22
Adaptive control
S23
23
Start-up phase 1. Signal reliability from sensors is controlled
S24
24
Manual control of outputs
S25
25
No refrigerant selected
S26
26
Appliance cleaning
S29
29
Forced cooling
S30
30
Delay on outputs during start-up
S32
32
Heat function r36 is active
S33
33
Case shut down
S45
45
Other displays:
The defrost temperature cannot be displayed. There is stop based on time
non
Defrost in progress / First cooling after the defrost
where the temperature is still above the
thermostat band.
-d-
Password required. Set password
PS
Regulation is stopped via main switch
OFF
Status on function "Adaptive defrost"
0: Off. Function is not activated and is zero set
1: Sensor error S3/S4 are reversed.
2: Tuning is in progress
3: Normal
4: Light build-up of ice
5: Medium build-up of ice
6: Heavy build-up of ice
U01
AD state
Number of defrosts carried out since the initial power up or since the resetting of
the function
U10
Acc.defrost
Number of defrosts skipped since the initial power up or since the resetting of the
function
U11
Acc.def.skip
*) Not all will be displayed. Only the function belonging to the selection application is displayed.