AK-CC 

550A

Melt function

Only for control of refrigeration (-5 to +10°C). The function ensures that the evapora-

tor will not be blocked by frost. Here you set how often the function is to stop the 

refrigeration and hence transform the frost to water (or ice if there is too much frost).

r16

MeltInterval

Melt period

Here you set how long an on-going melt function is to last.

r17

Melt period

Set point 2

 

The thermostat’s cutout value when the thermostat band 2 is activated via a digital 

input.

r21

Cutout2 temp

Correction of signal from S6

Compensation possibility due to long sensor cable

r59

Adjust S6

Selection of thermostat sensor S4% during night operation

Here you define the sensor the thermostat is to use for its control function. S3, S4, or a 

combination of them. With the setting 0%, only S3 is used (Sin). With 100%, only S4.

r61

Ther.S4% Ngt

Heat function

Set the size of the Neutral Zone for changeover from cooling to heating 

r62

Heat NZ

Time delay on transition from refrigeration phase to heating phase.

(there is not time delay on transition from heating phase to refrigeration phase).

r63

HeatStartDel

Night setbck

(start of night signal.  0=Day, 1=Night)
Forced cool.

(start of forced cooling)
Forced close 

(Forced stop of cooling)

Alarm

Alarm settings

The controller can give alarm in different situations. When there is an alarm all the 

light-emitting diodes (LED) will flash on the controller front panel, and the alarm relay 

will cut in.

With data communication the impor-

tance of the individual alarms can be 

defined. Setting is carried out in the 

“Alarm destinations” menu via AKM. 

Alarm delay 

(short alarm delay on air temperature)

If the upper or the lower alarm limit values are exceeded, a timer function will com-

mence. The alarm will not become active until the set time delay has been passed. 

The time delay is set in minutes.

A03

Alarm delay

Time delay for door alarm

The time delay is set in minutes.

The function is defined in o02 , o37 or in o84.

A04

DoorOpen del

Time delay for cooling 

(long alarm delay)

This time delay is used during start-up, during defrost, and after a Appliance cleaning.

There will be change-over to the normal time delay (A03) when the temperature has 

dropped below the set upper alarm limit.

The time delay is set in minutes.

A12

Pulldown del

Upper alarm limit

Here you set when the alarm for high temperature is to start. The limit value is set in 

°C (absolute value). 

The limit value will be raised during night operation. The value is the same as the one 

set for night setback, but will only be raised if the value is positive.

A13

HighLim Air

Lower alarm limit

Here you set when the alarm for low temperature is to start. The limit value is set in °C 

(absolute value).

A14

LowLim Air

Upper alarm limit for thermostat 2 (Thermostat band 2)

(Same function as for thermostat 1)

A20

HighLim2 Air

Lower alarm limit for thermostat 2 (Thermostat band 2)

(Same function as for thermostat 1)

A21

LowLim2 Air

Upper alarm limit for S6 temperature at thermostat 1

A22

HighLim1 S6

Lower alarm limit for S6 temperature at thermostat 1

A23

LowLim1 S6

Upper alarm limit for S6 temperature at thermostat 2 (Thermostat band 2)

A24

HighLim2 S6

Lower alarm limit for S6 temperature at thermostat 2 (Thermostat band 2)

A25

LowLim2 S6

S6 temperature alarm delay

The alarm is activated if one of the relevant alarm limits A22, A23, A24 or A25 is  

exceeded. The time delay is set in minutes.

(Alarms will not activate when the setting is set to the maximum value.)

A26

Al. Delay S6

Delay of a DI1 alarm

A cut-out/cut-in input will result in alarm when the time delay has been passed. The 

function is defined in o02.

A27

AI.Delay DI1

Delay of a DI2 alarm

 

A cut-out/cut-in input will result in alarm when the time delay has been passed. The 

function is defined in o37

A28

AI.Delay DI2

Содержание AK-CC 550A

Страница 1: ...Controller for appliance control AK CC 550A User Guide ADAP KOOL Refrigeration control systems...

Страница 2: ...ting sensor In addition to the outlet to the electronic injection valve of the type AKV the controller has 5 relay outputs which are defined by the use selected the individual usage options are descri...

Страница 3: ...ange depending on the selected applica tion Application 9 This use is for refrigeration appliances with one valve two evapo rators and two refrigeration sections Here the temperature and alarm monitor...

Страница 4: ...after the evaporator S4 respectively A setting for the thermostat alarm thermostat and display reading deter mines how much the two sensor values should influence each individual function e g 50 will...

Страница 5: ...s for the product sensor Appliance cleaning This function makes it easy for the shop s staff to carry out a cleaning of the appliance according to a standard procedure Appliance cleaning is activated...

Страница 6: ...efrosting When defrosting is commenced the heating element is activated The heating element remains activated until a set time after defrosting has ended by time or temperature Start of defrost A defr...

Страница 7: ...ght The setting is also recommended for rooms A value is calculated for the evaporator air flow The evaporator is monitored and the next scheduled defrost will be carried out as required If the functi...

Страница 8: ...ave top priority during normal regulation But if one of the override functions is activated the Min On time will be disregarded Railheat It is possible to pulse control the power to the rail heat in o...

Страница 9: ...the data communication from a system unit Here there are two operational options if data communication should fail The light can go ON The light can stay in its current mode The light load must be con...

Страница 10: ...forced closing the fans can be defined to be stopped or in operation Door contact The door contact function can via the digital inputs be defined for two different applications Alarm monitoring The co...

Страница 11: ...hanged to one of the same type but with Index A version with screw terminals The controllers address must be set higher than 0 in order for the display to be able to communicate with the controller If...

Страница 12: ...a product sensor but in application 9 and 10 it has a different use DI1 DI2 and DI3 are contact functions that can be used for one of the fol lowing functions door function alarm function defrost star...

Страница 13: ...en the light is switched off the night blinds are down In addition a digital input provides the option of forced opening of the blinds so that the appliance can be filled with products Application 8 H...

Страница 14: ...dicating application 1 If you employ another use signs are provided so that you can mount the relevant one It is only the lower sign that needs to be mounted The number is indicated on the left hand s...

Страница 15: ...re values in C or in F r05 Temp unit C 0 F 1 Only C on AKM whatever the set ting Correction of signal from S4 Compensation possibility due to long sensor cable r09 Adjust S4 Correction of signal from...

Страница 16: ...et time delay has been passed The time delay is set in minutes A03 Alarm delay Time delay for door alarm The time delay is set in minutes The function is defined in o02 o37 or in o84 A04 DoorOpen del...

Страница 17: ...ress u58 comp7 LLSV Here you can read the status of the compressor relay Defrost Defrost control The controller contains a timer function that is zeroset after each defrost start The timer function wi...

Страница 18: ...ost Here you set the time that is to elapse from compressor start after a defrost and until the fan may start again The time when water is tied to the evaporator d07 FanStartDel Fan start temperature...

Страница 19: ...ers a higher temperature than the one set here the fans will be stopped There will be re start at 2 K below the setting The function is not active during a defrost or start up after a defrost With set...

Страница 20: ...he address is set between 0 and 240 depending on the system unit and the selected data communication If the system unit is gateway type AKA 245 the version must be 6 20 or higher o03 The address is se...

Страница 21: ...et ting is selected to either 2 or 3 When the door is opened the relay will cut in When the door is closed again there will be a time delay of two minutes before the light is switched off 4 As 2 but i...

Страница 22: ...that a signal is received about the dew point value The value is measured by a system manager and sent to the controller via the data communication o85 Railh mode Dew point value where the rail heat i...

Страница 23: ...ctual superheat reference u22 SH ref Read the valve s actual opening degree u23 AKV OD Read the evaporating pressure u25 Evap press Pe Read the evaporating temperature u26 Evap temp Te Read the temper...

Страница 24: ...or S15 15 Refrigeration stopped due to open ON input or stopped regulation S16 16 Door is open DI input is open S17 17 Melt function in progress Refrigeration is interrupted S18 18 Modulating thermost...

Страница 25: ...A14 Low temp S6 Temperature alarm Low S6 2 A15 DI1 alarm DI1 alarm 8 A16 DI2 alarm DI2 alarm 8 A45 Standby mode Standby position stopped refrigeration via r12 or DI input A59 Case clean Appliance cle...

Страница 26: ...on to scan the rolling stack Set temperature 1 Push the middle button until the temperature value is shown 2 Push the upper or the lower button and select the new value 3 Push the middle button again...

Страница 27: ...arm limit high A13 8 C 6 C 15 C 10 C 8 C 15 C Alarm limit low A14 5 C 5 C 30 C 0 C 0 C 30 C Sensor signal for alarm funct S4 A36 0 100 0 Interval between defrost d03 6 h 6h 12h 8h 8h 6h Defrost sensor...

Страница 28: ...m A04 1 1 1 1 1 1 1 1 1 1 0 min 240 min 60 Delay for temperature alarm after defrost A12 1 1 1 1 1 1 1 1 1 1 0 min 240 min 90 High alarm limit for thermostat 1 A13 1 1 1 1 1 1 1 1 1 1 50 C 50 C 8 Low...

Страница 29: ...07 1 1 1 1 1 1 1 1 1 1 0 hrs 23 hrs 0 Clock Setting of minute t08 1 1 1 1 1 1 1 1 1 1 0 min 59 min 0 Clock Setting of date t45 1 1 1 1 1 1 1 1 1 1 1 day 31 day 1 Clock Setting of month t46 1 1 1 1 1 1...

Страница 30: ...ulse signal 5 ext main switch 6 night operation 7 thermostat band changeover activate r21 8 Not used 9 Not used 10 Appliance cleaning pulse signal 11 forced cooling at hot gas defrost 12 night cover 1...

Страница 31: ...ction line u64 1 Status on relay for compressor 2 u67 1 Temperature measured with S5B sensor u75 1 Temperature measured with S3B sensor u76 1 Status on relay for hot gas drain valve u80 1 Status on re...

Страница 32: ...Display If there is be external reading operation of the controller display type EKA 163B or EKA 164B can be connected RS485 terminal 51 52 53 For data communication but only if a data communication...

Страница 33: ...he hot gas valves must open DO5 Fan There is connection between terminal 15 and 16 when the fan is on DO6 Light relay There is connection between terminal 17 and 18 when the light must be on Rail heat...

Страница 34: ...During operations 40 to 70 C During transport 20 80 Rh not condensed No shock influence vibrations Density IP 20 Mounting DIN rail or wall Weight 0 4 Kg Data communication Fixed MODBUS Extension optio...

Страница 35: ...ernal display with plug for direct connection 084B8574 EKA 164B External display with operation buttons and plug for direct connections 084B8575 EKA 163A External display with screw terminals 084B8562...

Страница 36: ...erves the right to alter its products without notice This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifi...

Отзывы: