Time delay before opening of hot gas valve, so a PMLX valve can close.

d23

HotGasInjDel

Rail heat during defrost

0=off. 1=on. 2=Pulsating

d27

Railh. at def.

If you wish to see the temperature at the defrost sensor, push the controller’s lower-

most button. (May be changed to another function in o92.)

Defrost temp.

If you wish to start an extra defrost, push the controller’s lowermost button for four 

seconds.

You can stop an ongoing defrost in the same way

Def Start

Here you can start a manual defrost

Hold After Def

Shows ON when the controller is

operating with coordinated defrost.
Disable def.

Defrost in progress can be stopped

Defrost State

Status on defrost

1= pump down / defrost

Parameter for cooling function
Max. value for the superheat reference

n09

Max SH

Min. value for the superheat reference

n10

Min SH

MOP temperature

If no MOP function is required, select pos. OFF

n11

MOP temp

(A value of 15 corresponds to OFF)

AKV valve’s time period in seconds

Should only be set to a lower value if it is a decentralised plant and the suction  

pressure fluctuates a lot and in line with the opening of the AKV valve.

n13

AKV Period

Fan

Fan control

Fan stop temperature

The function stops the fans in an error situation, so that they will not provide power 

to the appliance. If the defrost sensor registers a higher temperature than the one set 

here, the fans will be stopped. There will be re-start at 2 K below the setting.

The function is not active during a defrost or start-up after a defrost.

With s50°C the function is interrupted.

F04

FanStopTemp.

Pulse operation of fan

0: No pulse operation

1: Pulse operation when the thermostat does not call for refrigeration

2: Pulse operation when the thermostat does not call for refrigeration, but only dur-

ing night operation

F05

FanPulseMode

Pulse operation period for fan

Here the overall pulse time is set. The sum of ON-to and OFF time.

F06

Fan cycle

ON time for fan

Here the % part of the period the fans are to be in operation is set.

F07

Fan ON %

The LED on the controller’s front will indicate whether a defrost is going on.

u59 Fan Relay

Here you can read the fan relay status, 

or force-control the relay in “Manual 

control” mode.

Internal defrosting schedule/clock function

(Not used if an external defrosting schedule is used via data communication.)

Up to six individual times can be set for the defrost start throughout the day.
Defrost start, hour setting

t01-t06

Defrost start, minute setting (1 and 11 belong together, etc.)

When all t01 to t16 equal 0 the clock will not start defrosts.

t11-t16

Real-time clock::

Setting the clock is only necessary when there is no data communication.

In the event of a power failure of less than four hours, the clock function will be saved.
Clock: Hour setting

t07

Clock: Minute setting

t08

Clock: Date setting

t45

Clock: Month setting

t46

Clock: Year setting

t47

Содержание AK-CC 550A

Страница 1: ...Controller for appliance control AK CC 550A User Guide ADAP KOOL Refrigeration control systems...

Страница 2: ...ting sensor In addition to the outlet to the electronic injection valve of the type AKV the controller has 5 relay outputs which are defined by the use selected the individual usage options are descri...

Страница 3: ...ange depending on the selected applica tion Application 9 This use is for refrigeration appliances with one valve two evapo rators and two refrigeration sections Here the temperature and alarm monitor...

Страница 4: ...after the evaporator S4 respectively A setting for the thermostat alarm thermostat and display reading deter mines how much the two sensor values should influence each individual function e g 50 will...

Страница 5: ...s for the product sensor Appliance cleaning This function makes it easy for the shop s staff to carry out a cleaning of the appliance according to a standard procedure Appliance cleaning is activated...

Страница 6: ...efrosting When defrosting is commenced the heating element is activated The heating element remains activated until a set time after defrosting has ended by time or temperature Start of defrost A defr...

Страница 7: ...ght The setting is also recommended for rooms A value is calculated for the evaporator air flow The evaporator is monitored and the next scheduled defrost will be carried out as required If the functi...

Страница 8: ...ave top priority during normal regulation But if one of the override functions is activated the Min On time will be disregarded Railheat It is possible to pulse control the power to the rail heat in o...

Страница 9: ...the data communication from a system unit Here there are two operational options if data communication should fail The light can go ON The light can stay in its current mode The light load must be con...

Страница 10: ...forced closing the fans can be defined to be stopped or in operation Door contact The door contact function can via the digital inputs be defined for two different applications Alarm monitoring The co...

Страница 11: ...hanged to one of the same type but with Index A version with screw terminals The controllers address must be set higher than 0 in order for the display to be able to communicate with the controller If...

Страница 12: ...a product sensor but in application 9 and 10 it has a different use DI1 DI2 and DI3 are contact functions that can be used for one of the fol lowing functions door function alarm function defrost star...

Страница 13: ...en the light is switched off the night blinds are down In addition a digital input provides the option of forced opening of the blinds so that the appliance can be filled with products Application 8 H...

Страница 14: ...dicating application 1 If you employ another use signs are provided so that you can mount the relevant one It is only the lower sign that needs to be mounted The number is indicated on the left hand s...

Страница 15: ...re values in C or in F r05 Temp unit C 0 F 1 Only C on AKM whatever the set ting Correction of signal from S4 Compensation possibility due to long sensor cable r09 Adjust S4 Correction of signal from...

Страница 16: ...et time delay has been passed The time delay is set in minutes A03 Alarm delay Time delay for door alarm The time delay is set in minutes The function is defined in o02 o37 or in o84 A04 DoorOpen del...

Страница 17: ...ress u58 comp7 LLSV Here you can read the status of the compressor relay Defrost Defrost control The controller contains a timer function that is zeroset after each defrost start The timer function wi...

Страница 18: ...ost Here you set the time that is to elapse from compressor start after a defrost and until the fan may start again The time when water is tied to the evaporator d07 FanStartDel Fan start temperature...

Страница 19: ...ers a higher temperature than the one set here the fans will be stopped There will be re start at 2 K below the setting The function is not active during a defrost or start up after a defrost With set...

Страница 20: ...he address is set between 0 and 240 depending on the system unit and the selected data communication If the system unit is gateway type AKA 245 the version must be 6 20 or higher o03 The address is se...

Страница 21: ...et ting is selected to either 2 or 3 When the door is opened the relay will cut in When the door is closed again there will be a time delay of two minutes before the light is switched off 4 As 2 but i...

Страница 22: ...that a signal is received about the dew point value The value is measured by a system manager and sent to the controller via the data communication o85 Railh mode Dew point value where the rail heat i...

Страница 23: ...ctual superheat reference u22 SH ref Read the valve s actual opening degree u23 AKV OD Read the evaporating pressure u25 Evap press Pe Read the evaporating temperature u26 Evap temp Te Read the temper...

Страница 24: ...or S15 15 Refrigeration stopped due to open ON input or stopped regulation S16 16 Door is open DI input is open S17 17 Melt function in progress Refrigeration is interrupted S18 18 Modulating thermost...

Страница 25: ...A14 Low temp S6 Temperature alarm Low S6 2 A15 DI1 alarm DI1 alarm 8 A16 DI2 alarm DI2 alarm 8 A45 Standby mode Standby position stopped refrigeration via r12 or DI input A59 Case clean Appliance cle...

Страница 26: ...on to scan the rolling stack Set temperature 1 Push the middle button until the temperature value is shown 2 Push the upper or the lower button and select the new value 3 Push the middle button again...

Страница 27: ...arm limit high A13 8 C 6 C 15 C 10 C 8 C 15 C Alarm limit low A14 5 C 5 C 30 C 0 C 0 C 30 C Sensor signal for alarm funct S4 A36 0 100 0 Interval between defrost d03 6 h 6h 12h 8h 8h 6h Defrost sensor...

Страница 28: ...m A04 1 1 1 1 1 1 1 1 1 1 0 min 240 min 60 Delay for temperature alarm after defrost A12 1 1 1 1 1 1 1 1 1 1 0 min 240 min 90 High alarm limit for thermostat 1 A13 1 1 1 1 1 1 1 1 1 1 50 C 50 C 8 Low...

Страница 29: ...07 1 1 1 1 1 1 1 1 1 1 0 hrs 23 hrs 0 Clock Setting of minute t08 1 1 1 1 1 1 1 1 1 1 0 min 59 min 0 Clock Setting of date t45 1 1 1 1 1 1 1 1 1 1 1 day 31 day 1 Clock Setting of month t46 1 1 1 1 1 1...

Страница 30: ...ulse signal 5 ext main switch 6 night operation 7 thermostat band changeover activate r21 8 Not used 9 Not used 10 Appliance cleaning pulse signal 11 forced cooling at hot gas defrost 12 night cover 1...

Страница 31: ...ction line u64 1 Status on relay for compressor 2 u67 1 Temperature measured with S5B sensor u75 1 Temperature measured with S3B sensor u76 1 Status on relay for hot gas drain valve u80 1 Status on re...

Страница 32: ...Display If there is be external reading operation of the controller display type EKA 163B or EKA 164B can be connected RS485 terminal 51 52 53 For data communication but only if a data communication...

Страница 33: ...he hot gas valves must open DO5 Fan There is connection between terminal 15 and 16 when the fan is on DO6 Light relay There is connection between terminal 17 and 18 when the light must be on Rail heat...

Страница 34: ...During operations 40 to 70 C During transport 20 80 Rh not condensed No shock influence vibrations Density IP 20 Mounting DIN rail or wall Weight 0 4 Kg Data communication Fixed MODBUS Extension optio...

Страница 35: ...ernal display with plug for direct connection 084B8574 EKA 164B External display with operation buttons and plug for direct connections 084B8575 EKA 163A External display with screw terminals 084B8562...

Страница 36: ...erves the right to alter its products without notice This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifi...

Отзывы: