2.0 Main functions
2.1 Away
2.2 Bypass
Main menu > Away
Use this command when you leave your house for a
prolonged period of time. The
away
command reduces
the ventilation rate of the system to an absolute mini-
mum, inside a defined interval. The unit will automati-
cally assume normal operation when the
away
period is
over. Note: if a heating surface is installed (optional) it
is turned off during
away
mode. If the heating surface
is used for heating the house, the room temperature is
reduced to 15 ˚C during
away
period.
Main menu > Bypass
The
bypass
function opens a passage parallel to the heat
exchanger, which stops the heat exchanging process.
When the
bypass
is open, outdoor air is led directly into
the house. The
bypass
can be activated in two ways:
1. Manually
, by pressing the
bypass
command. This
will start the
bypass
function for 3 hours (the run
time can be changed in the
settings
menu). The
bypass
will not activate if the outdoor temperature
is lower than +5˚C.
2 . Automatically,
if the outdoor air is warmer than
16 ˚C (activation temperature can be changed in
settings
menu). The
bypass
will automatically close
again, when the outdoor air temperature drops
below 15 ˚C.
Automatic activation of
bypass
is not possible in the
manual
run mode.