2.1.6 Ordering numbers, 690 V, 50 Hz
I
AHF,N
Typical Motor
Ordering Number
Danfoss Frequency converter series *
[AMP]
[kW]
AHF 005
AHF 010
AQUA, HVAC,
Automation HO
Automation NO
43 A
37, 45
130B2328
130B2293
72 A
55, 75
130B2330
130B2295
P37K-P45K
P37K
101 A
90
130B2331
130B2296
P55-P75K
P45K-P55K
144 A
110, 132
130B2333
130B2298
P90K-P110
P75K-P90K
180 A
160
130B2334
130B2299
P132
P110
217 A
200
130B2335
130B2300
P160
P132
289 A
250
13 130B2333
130B2301
P200
P160
324 A
315
13 130B2334
130B2302
P250
P200
370 A
400
13 130B2335
130B2304
P315
P250
Table 2.6: AHF005 and AHF010, 690V, 50 Hz
⋆
Please note that the matching of the typical Danfoss frequency converter and filter is pre-calculated based on 690V and assuming typical motor
load. FC 300 is based on an 160% torque application, while FC 100 and FC 200 series are based on 110% torque application.
The pre-calculated filter current may be varying from the input current ratings of FC 100, FC 200 and FC 300 series as stated in the respective
operating instructions, as these numbers are based on different operating conditions.
2.1.7 Calculation of the exact filter size needed
For optimal performance the harmonic filter should be sized for the mains input current to the frequency converter, i.e. the input current drawn based
on the expected load of the frequency converter and not the size of the frequency converter itself!
The mains input current to the frequency converter (I
FC,L
) can by calculated using the nominal motor current (I
M,N
) and displacement power factor (Cos
φ
)) of the motor. Both data are normally printed on the nameplate of the motor. In the case where the nominal motor voltage (U
M,N
) is unequal to the
actual mains-mains voltage (U
L
) the calculated current must be corrected with the ratio between these voltages as shown in the equation below.
IFC
,
L
= 1.1 ×
IM
,
N
×
Cos
(
ϕ
) ×
((
UM
,
N
)/(
UL
))
The harmonic filter chosen must have a nominal current (I
AHF,N
) equal to or larger than the calculated frequency converter mains input current (I
FC,L
).
If several frequency converters are to be connected to the same filter, the harmonic filter must be sized according to the sum of the calculated mains
currents.
If the harmonic filter is sized for the load, and the motor of the corresponding frequency converter is changed, the current must be
re-calculated to avoid overload of the harmonic filter.
2 Description
AHF 005/010 Operating Instructions
10
MG.80.C1.02 - VLT
®
is a registered Danfoss trademark